EF/ ICR Logo Summary Report for City of Wilmington Delaware



[ Quarterly DBP ] [ Monthly DBP ] [ Monthly Microbials ]

Water Systems and Water Treatment Plants: A water system may consist of more than one treatment plant. Therefore, you may see data from more than one treatment plant in your water system report.


Sampled Quarterly - DISINFECTION BYPRODUCT (Treated Water)

Porter Filter Plant - 273

Quarter Total Trihalomethanes(ppb) Haloacetic Acids 5(ppb)
JUL 1997 - SEP 1997
80.3
NO DATA
OCT 1997 - DEC 1997
51.4
29.1
JAN 1998 - MAR 1998
41.7
36
APR 1998 - JUN 1998
50.2
32.3
JUL 1998 - SEP 1998
46.5
26.2
OCT 1998 - DEC 1998
47.8
30.5

Brandywine Filter Plant - 274

Quarter Total Trihalomethanes(ppb) Haloacetic Acids 5(ppb)
JUL 1997 - SEP 1997
72.7
NO DATA
OCT 1997 - DEC 1997
63.6
40.1
JAN 1998 - MAR 1998
36.3
35.3
APR 1998 - JUN 1998
35.4
37.2
JUL 1998 - SEP 1998
NO DATA
34.4
OCT 1998 - DEC 1998
56.8
42.1

Detailed water system reports are available for: Total Trihalomethanes and Haloacetic Acids 5.



Sampled Monthly - DISINFECTION BYPRODUCT (Treated Water)

Detailed water system reports are available for: Total Trihalomethanes and Haloacetic Acids 5.


Sampled Monthly - DISINFECTION BYPRODUCT (Treated Water)

NO DATA - Click here to find out why.

Detailed water system reports are available for: Bromate and Chlorite


Sampled Monthly - MICROBIALS (Source Water)

Porter Filter Plant - 273

Month Cryptosporidium
(#oocysts/100L)
Giardia
(#cysts/100L)
Virus
(MPN/100L)
Total Coliform
(Total Coliforms/100mL)
Fecal Coliform
(Fecal Coliforms/100mL)
E. coli
(E. coli/100mL)
JUL 1997
0
0
0
387
NO DATA

AUG 1997
0
25
0
228
NO DATA

SEP 1997
0
0
0
435
NO DATA

OCT 1997
0
0
0
613
NO DATA

NOV 1997
0
3.7
0
214
NO DATA

DEC 1997
0
12.5
0
88
NO DATA

JAN 1998
0
5
1
86
NO DATA

FEB 1998
0
10
0
109
NO DATA

MAR 1998
0
135.7
0
52
NO DATA

APR 1998
NO DATA
NO DATA
NO DATA
71
NO DATA

MAY 1998
0
0
0
579
NO DATA

JUN 1998
0
0
0
770
NO DATA

JUL 1998
0
0
0
325
NO DATA

AUG 1998
0
7.4
0
1120
NO DATA

SEP 1998
0
0
0
435
NO DATA

OCT 1998
0
0
0
150
NO DATA

NOV 1998
0
20
0
56
NO DATA

DEC 1998
0
20
0
99
NO DATA


Brandywine Filter Plant - 274

Month Cryptosporidium
(#oocysts/100L)
Giardia
(#cysts/100L)
Virus
(MPN/100L)
Total Coliform
(Total Coliforms/100mL)
Fecal Coliform
(Fecal Coliforms/100mL)
E. coli
(E. coli/100mL)
JUL 1997
0
0
0
770
NO DATA

AUG 1997
0
0
0
344
NO DATA

SEP 1997
0
0
0
365
NO DATA

OCT 1997
0
0
0
365
NO DATA

NOV 1997
0
0
0
186
NO DATA

DEC 1997
0
5
0
93
NO DATA

JAN 1998
0
3.1
1
61
NO DATA

FEB 1998
0
0
0
866
NO DATA

MAR 1998
0
53.6
0
50
NO DATA

APR 1998
0
0
2.1
201
NO DATA

MAY 1998
0
0
2.1
1120
NO DATA

JUN 1998
0
0
0
325
NO DATA

JUL 1998
0
0
0
1120
NO DATA

AUG 1998
0
0
11.9
2419
NO DATA

SEP 1998
0
7.7
0
517
NO DATA

OCT 1998
0
16.7
0
133
NO DATA

NOV 1998
5
10
0
71
NO DATA

DEC 1998
0
37.5
0
613
NO DATA


Detailed water system reports are available for: Cryptosporidium, Giardia, Virus, Total Coliform, Fecal Coliform, and E. coli

You can click on column titles to obtain more information about the subject. You can click on the "NO DATA" to find out why data is missing. "0" value does not mean that the value was missing. Missing values are indicated by a "NO DATA" label. For microbial results, "0" indicates that a sample was analyzed, but that no microbes were found. For DBP results, "0" may indicate that a sample was analyzed, but that the result was less than the lowest value that the analytical method can reliably report.