Jump to main content.


EF/ ICR Logo Summary Report for Pueblo Board of Water Works



[ Quarterly DBP ] [ Monthly DBP ] [ Monthly Microbials ]

Water Systems and Water Treatment Plants: A water system may consist of more than one treatment plant. Therefore, you may see data from more than one treatment plant in your water system report.


Sampled Quarterly - DISINFECTION BYPRODUCT (Treated Water)

Whitlock Water Treatment Facility - 260

Quarter Total Trihalomethanes(ppb) Haloacetic Acids 5(ppb)
JUL 1997 - SEP 1997
10.9
15.8
OCT 1997 - DEC 1997
7.1
18
JAN 1998 - MAR 1998
7
13.3
APR 1998 - JUN 1998
5.6
16
JUL 1998 - SEP 1998
9.7
14.3
OCT 1998 - DEC 1998
8.2
13.7

Detailed water system reports are available for: Total Trihalomethanes and Haloacetic Acids 5.



Sampled Monthly - DISINFECTION BYPRODUCT (Treated Water)

Detailed water system reports are available for: Total Trihalomethanes and Haloacetic Acids 5.


Sampled Monthly - DISINFECTION BYPRODUCT (Treated Water)

NO DATA - Click here to find out why.

Detailed water system reports are available for: Bromate and Chlorite


Sampled Monthly - MICROBIALS (Source Water)

Whitlock Water Treatment Facility - 260

Month Cryptosporidium
(#oocysts/100L)
Giardia
(#cysts/100L)
Virus
(MPN/100L)
Total Coliform
(Total Coliforms/100mL)
Fecal Coliform
(Fecal Coliforms/100mL)
E. coli
(E. coli/100mL)
JUL 1997
0
0
0
1000
6
NO DATA
AUG 1997
0
0
0
400
6
NO DATA
SEP 1997
0
0
1
1000
12
NO DATA
OCT 1997
0
9
0
1000
7
NO DATA
NOV 1997
0
0
0
400
10
NO DATA
DEC 1997
NO DATA
NO DATA
1
75
9
NO DATA
JAN 1998
0
10
3.2
125
26
NO DATA
FEB 1998
5
9
0
75
12
NO DATA
MAR 1998
0
0
0
40
0
NO DATA
APR 1998
0
0
0
45
1
NO DATA
MAY 1998
0
0
0
140
19
NO DATA
JUN 1998
0
0
0
50
2
NO DATA
JUL 1998
0
0
0
400
4
NO DATA
AUG 1998
NO DATA
NO DATA
0
1000
20
NO DATA
SEP 1998
0
0
0
650
16
NO DATA
OCT 1998
0
0
0
750
28
NO DATA
NOV 1998
29
0
0
250
18
NO DATA
DEC 1998
0
0
0
110
5
NO DATA

Detailed water system reports are available for: Cryptosporidium, Giardia, Virus, Total Coliform, Fecal Coliform, and E. coli

You can click on column titles to obtain more information about the subject. You can click on the "NO DATA" to find out why data is missing. "0" value does not mean that the value was missing. Missing values are indicated by a "NO DATA" label. For microbial results, "0" indicates that a sample was analyzed, but that no microbes were found. For DBP results, "0" may indicate that a sample was analyzed, but that the result was less than the lowest value that the analytical method can reliably report.