Jump to main content.


EF/ ICR Logo Summary Report for Mobile Area Water and Sewer System



[ Quarterly DBP ] [ Monthly DBP ] [ Monthly Microbials ]

Water Systems and Water Treatment Plants: A water system may consist of more than one treatment plant. Therefore, you may see data from more than one treatment plant in your water system report.


Sampled Quarterly - DISINFECTION BYPRODUCT (Treated Water)

E.M. Stickney Water Treatment Plant - 110

Quarter Total Trihalomethanes(ppb) Haloacetic Acids 5(ppb)
JUL 1997 - SEP 1997
91.3
41.6
OCT 1997 - DEC 1997
94.1
39.5
JAN 1998 - MAR 1998
48.2
41.1
APR 1998 - JUN 1998
72.1
44.7
JUL 1998 - SEP 1998
NO DATA
34.4
OCT 1998 - DEC 1998
95.4
48.3

H.E. Myers Water Treatment PLant - 111

Quarter Total Trihalomethanes(ppb) Haloacetic Acids 5(ppb)
JUL 1997 - SEP 1997
92.5
38.8
OCT 1997 - DEC 1997
78
37.5
JAN 1998 - MAR 1998
43.7
33.7
APR 1998 - JUN 1998
64.9
42
JUL 1998 - SEP 1998
NO DATA
29.4
OCT 1998 - DEC 1998
81.6
42

Detailed water system reports are available for: Total Trihalomethanes and Haloacetic Acids 5.



Sampled Monthly - DISINFECTION BYPRODUCT (Treated Water)

E.M. Stickney Water Treatment Plant - 110

Month Bromate(ppb) Chlorite(ppm)
JUL 1997
0
.488
AUG 1997
0
.505
SEP 1997
0
.54
OCT 1997
0
.551
NOV 1997
0
.54
DEC 1997
0
.543
JAN 1998
.2
.635
FEB 1998
0
.723
MAR 1998
0
.795
APR 1998
0
.558
MAY 1998
.3
.528
JUN 1998
0
.596
JUL 1998
0
.554
AUG 1998
0
.529
SEP 1998
0
.571
OCT 1998
0
.51
NOV 1998
0
.532
DEC 1998
0
NO DATA

H.E. Myers Water Treatment PLant - 111

Month Bromate(ppb) Chlorite(ppm)
JUL 1997
0
.643
AUG 1997
0
.711
SEP 1997
0
.792
OCT 1997
0
.525
NOV 1997
0
.583
DEC 1997
0
.543
JAN 1998
0
.803
FEB 1998
0
.802
MAR 1998
0
.871
APR 1998
0
.638
MAY 1998
0
.618
JUN 1998
0
.625
JUL 1998
0
.583
AUG 1998
0
.552
SEP 1998
0
.58
OCT 1998
0
.61
NOV 1998
0
.465
DEC 1998
0
NO DATA

H.E. Myers Water Treatment PLant - 111

Month Bromate(ppb) Chlorite(ppm)
JUL 1997
0
.643
AUG 1997
0
.711
SEP 1997
0
.792
OCT 1997
0
.525
NOV 1997
0
.583
DEC 1997
0
.543
JAN 1998
0
.803
FEB 1998
0
.802
MAR 1998
0
.871
APR 1998
0
.638
MAY 1998
0
.618
JUN 1998
0
.625
JUL 1998
0
.583
AUG 1998
0
.552
SEP 1998
0
.58
OCT 1998
0
.61
NOV 1998
0
.465
DEC 1998
0
NO DATA

Detailed water system reports are available for: Bromate and Chlorite


Sampled Monthly - MICROBIALS (Source Water)

E.M. Stickney Water Treatment Plant - 110

Month Cryptosporidium
(#oocysts/100L)
Giardia
(#cysts/100L)
Virus
(MPN/100L)
Total Coliform
(Total Coliforms/100mL)
Fecal Coliform
(Fecal Coliforms/100mL)
E. coli
(E. coli/100mL)
JUL 1997
0
0
0
2700
42

AUG 1997
0
0
NO DATA
7800
4

SEP 1997
0
0
0
1000
0

OCT 1997
0
0
0
3600
0

NOV 1997
0
0
NO DATA
7000
8

DEC 1997
0
0
0
1000
4

JAN 1998
0
0
5.8
1900
18

FEB 1998
0
0
1
700
5

MAR 1998
0
0
0
1900
5

APR 1998
0
0
0
1690
0

MAY 1998
0
0
0
4000
5

JUN 1998
0
0
0
10400
500

JUL 1998
0
0
0
29800
60

AUG 1998
0
0
0
12800
33

SEP 1998
0
0
0
7200
10

OCT 1998
0
0
2.1
900
9

NOV 1998
0
0
0
1600
2

DEC 1998
NO DATA
NO DATA
0
1400
1


H.E. Myers Water Treatment PLant - 111

Month Cryptosporidium
(#oocysts/100L)
Giardia
(#cysts/100L)
Virus
(MPN/100L)
Total Coliform
(Total Coliforms/100mL)
Fecal Coliform
(Fecal Coliforms/100mL)
E. coli
(E. coli/100mL)
JUL 1997
0
0
0
6500
74

AUG 1997
0
0
0
8000
306

SEP 1997
0
0
0
3000
0

OCT 1997
0
0
0
1200
30

NOV 1997
0
0
NO DATA
3000
10

DEC 1997
0
0
0
2000
18

JAN 1998
0
0
7.1
3550
23

FEB 1998
0
0
2.1
1200
8

MAR 1998
0
0
0
900
9

APR 1998
0
0
0
2790
0

MAY 1998
0
0
0
6700
200

JUN 1998
0
0
1
36700
230

JUL 1998
0
0
0
35800
90

AUG 1998
0
0
0
12500
35

SEP 1998
0
0
0
5400
4

OCT 1998
0
0
0
1300
4

NOV 1998
0
0
0
2800
10

DEC 1998
NO DATA
NO DATA
0
2200
6


Detailed water system reports are available for: Cryptosporidium, Giardia, Virus, Total Coliform, Fecal Coliform, and E. coli

You can click on column titles to obtain more information about the subject. You can click on the "NO DATA" to find out why data is missing. "0" value does not mean that the value was missing. Missing values are indicated by a "NO DATA" label. For microbial results, "0" indicates that a sample was analyzed, but that no microbes were found. For DBP results, "0" may indicate that a sample was analyzed, but that the result was less than the lowest value that the analytical method can reliably report.


ICR Overview
Envirofacts Home Page


Local Navigation


Jump to main content.