September, 2007
                                 Revised April, 2009
                                  07/30/WQPC-SWP
                                  EPA/600/R-07/120
   Environmental Technology
        Verification Report

     In-Drain Treatment Device

The Hydro International Up-Flo™ Filter


                Prepared by
            Penn State Harrisburg
           Middletown, Pennsylvania
       Under a Cooperative Agreement with
       U.S. Environmental Protection Agency

-------
         THE ENVIRONMENTAL TECHNOLOGY VERIFICATION
                                      PROGRAM
   U.S. Environmental Protection Agency
                                                  NSF International
                      ETV Joint Verification Statement
    TECHNOLOGY TYPE:
    APPLICATION:
    TECHNOLOGY NAME:
    TEST LOCATION:
    COMPANY:
    ADDRESS:

    WEB SITE:
    EMAIL:
        UPFLOW WATER TREATMENT
        IN-DRAIN TREATMENT DEVICE
        UP-FLO™ FILTER WITH CPZ MIX™ FILTER MEDIA

        PENN STATE HARRISBURG
        HYDRO INTERNATIONAL
        94 Hutchins Drive
        Portland, Maine 04102
        http://www.hydrointernational.biz/us/
        stormwaterinquiries@hil-tech.com
PHONE:  (207)756-6200
FAX: (207)756-6212
NSF International (NSF), in cooperation with the U.S. Environmental Protection Agency (EPA), operates
the Water Quality Protection Center (WQPC), one of six centers under the Environmental Technology
Verification (ETV) Program. The WQPC recently evaluated the performance of the Up-Flo™ Filter,
manufactured  by Hydro International.  The Up-Flo™ Filter was tested at the  Penn State Harrisburg
Environmental Engineering Laboratory in Midletown, Pennsylvania.

EPA created ETV to facilitate the deployment of innovative or improved environmental technologies
through performance verification and dissemination of information. The ETV program's goal is to further
environmental protection by accelerating  the acceptance and use of improved and more cost-effective
technologies. ETV seeks to achieve this goal by providing high quality, peer-reviewed data on technology
performance to those involved in the design, distribution, permitting, purchase, and use of environmental
technologies.
ETV works in partnership with recognized standards and testing organizations; stakeholder groups, which
consist of buyers, vendor  organizations,  and permitters;  and with the full participation of individual
technology developers. The program evaluates the performance of innovative technologies by developing
test plans that are  responsive  to the needs of stakeholders, conducting field or laboratory  tests  (as
appropriate),  collecting and analyzing data, and preparing peer-reviewed  reports. All evaluations  are
conducted in accordance with  rigorous quality assurance protocols to ensure that data of known and
adequate quality are generated and that the results are defensible.
07/30/WQPC-SWP
The accompanying notice is an integral part of this verification statement.

                        VS-i
                September 2007

-------
TECHNOLOGY DESCRIPTION
The  following description of the Up-Flo™ Filter was provided by the vendor and does not represent
verified information.
The  Up-Flo™ Filter is  a passive,  modular filtration system that incorporates multiple elements of a
treatment train into a single, small-footprint device. The Up-Flo™ Filter uses a sedimentation sump and
screening system to pretreat runoff before it flows up through the filter media, housed in one to six filter
modules, where final  polishing occurs. A high-capacity,  siphonic bypass safeguards against upstream
ponding during high-flow events. The siphon also serves as a floatables baffle to prevent the escape of
floatable trash and debris from the Up-Flo™ Filter chamber.
The  Up-Flo™ Filter is  self-activating and operates by  simple hydraulics.  Challenge water enters the
chamber from an inlet pipe or an overhead grate and flows into the sump region where gross debris and
coarse grit are removed by settling. Runoff continues to fill the chamber until there is enough  driving
head to initiate flow through the filter media. At this point, the water flows up through the angled screen
into the filter module. In the filter module, flow passes up through the filter media and is conveyed to the
outlet module via the flow conveyance channel. Flows in excess of the  filtration capacity are discharged
directly to  the outlet module by the siphonic bypass. The siphon also serves as a floatables baffle to
prevent the escape of buoyant litter and debris.   The Up-Flo™ Filter is equipped with a drain-down
mechanism to ensure that the filter media sits above the standing water level during no-flow conditions, to
prevent anoxic conditions that could promote  bacterial growth  in the  filter  media and the release of
harmful leachates. As flows subside, water slowly drains  out of the chamber through four small drain-
down ports located at the  base of the outlet module. The  drain-down ports are covered with a layer of
filter fabric to provide treatment to the drain-down flows.
Performance  of a regularly maintained Up-Flo™ Filter should provide removal of over 80% of total
suspended solids (TSS) from challenge water runoff. It will also remove a portion of metals, organics and
other pollutants commonly found sorbed  to the surface  of suspended sediment particles. Each  filter
module filled with the CPZ Mix™ will have  a  flow rate of 20-25  gpm when the  water level in the
chamber provides 20 in. of driving head. Water will continue to be filtered up through the  filter media
until the water level in the chamber falls to zero inches of driving head. When the inflows exceed the
filtration capacity, the excess flows will  discharge through the bypass siphon directly to the outlet
module.
VERIFICATION TESTING DESCRIPTION
Methods and Procedures

The testing methods and procedures  employed during the study were outlined in the Test Plan for Hydro
International, Inc. Up-Flo™ Filter for Stormwater Treatment (February 2006).  The Up-Flo™ Filter was
installed in a specially designed testing rig to simulate a catch basin receiving surface runoff.  The  rig was
designed to provide for  controlled dosing and  sampling, and to  allow  for observation of  system
performance.

The  Up-Flo™ Filter was challenged by a variety of hydraulic flow and contaminant load conditions to
evaluate  the  system's performance  under normal and elevated loadings.    The test  conditions are
summarized in Table 1.  Additional tests were conducted at the vendor's request to determine the media's
sediment removal  capabilities with challenge  water consisting  of only sediments  and nutrients (no
hydrocarbons) at continuous flow. The results of these tests will be published in an addendum at a later
time.
07/30/WQPC-SWP       The accompanying notice is an integral part of this verification statement.         September 2007

                                              VS-ii

-------
Table 1. Test Phase Summary
Phase
I

II

III-l

III-2

III-3

IV

and Flow Condition
Intermittent Flow

Contaminant Capacity

Hydraulic Capacity, Clean Water

Hydraulic Capacity, Synthetic
Wastewater
Hydraulic Capacity, Spiked
Wastewater
Contaminant Capacity at High
Hydraulic Throughput
Flow
1 1 gpm, 15 min on, 15
min off
16 gpm continuous

10 to 45 gpm, increased
in 5 gpm increments
10 to 45 gpm, increased
in 5 gpm increments
10 to 45 gpm, increased
in 5 gpm increments
32 gpm continuous

Loadings
Normal

Normal

None

Normal

Spiked
(4X)
Normal

Test Duration
40 hr

Continue until
exhaustion
15 min at each
flow interval
15 min at each
flow interval
15 min at each
flow interval
Continue until
exhaustion
A synthesized wastewater mixture containing petroleum hydrocarbons (gasoline, diesel fuel, motor oil,
and brake fluid), automotive fluids (antifreeze and windshield washer solvent), surfactants, and sediments
(sand, topsoil and clay), was used to simulate constituents found in surface runoff from a commercial or
industrial setting.  Influent and effluent samples were collected and analyzed for several parameters,
including TSS, suspended sediment concentration (SSC), total phosphorus (TP), and chemical oxygen
demand (COD).  Complete descriptions of the testing and quality assurance/quality control  (QA/QC)
procedures  are included in the verification report.
PERFORMANCE VERIFICATION
System Installation and Maintenance
The Up-Flo™ Filter was found to be durable and easy to install, requiring no special tools.  Maintenance
on the system during testing  consisted of replacing the filter media bags, and removing sediment and
water collected in the sump.  Maintenance took approximately 30-45 minutes, with the most difficult
activity being removal of the filter media bags, due to their size and weight.
Hydraulic Capacity

The hydraulic capacity of the Up-Flo™ Filter was determined using clean water (Phase III-l), synthetic
wastewater (Phase III-2), and synthetic wastewater with spiked constituents (Phase  III-3).  Capacity was
evaluated as a function  of influent and effluent flow rates, and water levels in the sump.  The testing
determined the effluent flow rates were comparable to the influent for all flow rates tested, up to and past
the point where the bypass was activated.  The hydraulic capacity results are expressed graphically in
Figure 1.
An Up-Flo™ with new filter media can accept a hydraulic flow of up to approximately 30 gpm with no
bypass, depending on the concentration of contaminants in the  wastewater. At flows greater than 30 gpm
the water elevation in the sump approaches the bypass siphon elevation, and a portion of the influent flow
exits the system as  untreated bypass. The maximum treated flow decreases as the filter media trap
contaminants,  preventing water from flowing through the filter bags. This was particularly evident with
the Phase III-3 (spiked  contaminant loadings), where the effluent flow diminished prior to eventually
reaching bypass conditions.
07/30/WQPC-SWP
The accompanying notice is an integral part of this verification statement.

                         VS-iii
September 2007

-------
                                         Flow Rate - Phase I
                       50
                       40 -
                       30 -
                     &
                     ra
                     a:
                       20 -
                       10 -
                              influent
                              III-2
                              III-3
      d
                            10     15     20     25     30     35
                                         Flow Conditions (GPM)
                                                                40    45
Figure 1. Comparison of influent versus effluent flow rates for Phase III hydraulics testing.
Contaminant Removal
Table 2  summarizes the influent and effluent constituent concentrations and the respective  removal
efficiencies for the Phase I (intermittent flow) and Phase II (continuous flow tests). During both of these
tests, the flow was held constant at 11 gpm for Phase I and 16 gpm for Phase II,  both of which are less
than the Up-Flo™ Filter's 20  gpm  rated capacity.   These tests were  done consecutively, and were
completed when filter media exhaustion or blinding was observed.  During testing, the filter media was
blinded off by contaminant loading prior to breakthrough occurring. In general, the effluent constituent
concentrations remained constant throughout testing.
Table 2. Up-Flo™ Filter Treatment Efficiency Summary for Phase I and Phase II Tests
Influent Concentration
Results (mg/L)

TSS
ssc
TP
COD
Mean
136
147
47
157
Median
112
130
44
134
Max.
492
555
183
523
Min.
<5
<5
0.6
60
Effluent Concentration
Results (mg/L)
Mean
36
39
38
63
Median
30
30
38
65
Max.
100
108
81
89
Min.
9
<5
0.6
33
Removal Efficiency ("/o)1
Mean
73
74
19
60
Median
73
77
14
51
Max.
92
99
91
88
Min.
-1,280
-480
-530
-3.3
1.  Mean and median removal efficiencies are calculated using the calculated mean and median influent and effluent
   concentrations, while maximum and minimum removal efficiencies are evaluated from the paired sample data points.

The  median sediment removal efficiency is 73% and 77% for TSS  and SSC,  respectively, which  is
slightly below the vendor's 80% sediment removal efficiency performance claim. The Up-Flo™ Filter
was also shown to be capable of reducing TP and COD, demonstrated by median removal efficiencies of
14% and 51%, respectively.
07/30/WQPC-SWP
The accompanying notice is an integral part of this verification statement.

                         VS-iv
September 2007

-------
Media Blinding/Bypass

During the  Phase II and Phase IV tests, the testing organization observed that when the filter media
reached capacity, it would shift within the filter module.  This shift opened a preferential pathway in the
corner of the filter module for water to pass through the system without passing through the filter media.
This failure mechanism was not anticipated by the vendor. The vendor indicated that the Up-Flo™ Filter
would fail as the filter bags clog, forcing a rise of the water level in the tank to an elevation that would
eventually reach the bypass siphon and flow out through the bypass.

Quality Assurance/Quality Control

NSF personnel completed a technical  systems audit during testing  to ensure  that the testing was in
compliance  with the test plan. NSF also completed a data quality audit of at least 10% of the test data to
ensure that the reported data represented the data generated during testing.  In addition to QA/QC audits
performed by NSF, EPA personnel conducted an audit of NSF's QA Management Program.
    Original signed by                                 Original signed by
    Sally Gutierrez	October 15, 2007       Robert Ferguson	October 3, 2007
    Sally Gutierrez                   Date             Robert Ferguson         Date
    Director                                          Vice President
    National Risk Management Research Laboratory     Water Systems
    Office of Research and Development                NSF International
    United States Environmental Protection Agency
    NOTICE:  Verifications  are  based  on  an evaluation  of technology performance under  specific,
    predetermined criteria and the appropriate quality assurance procedures. EPA and NSF make no expressed
    or implied warranties as to the performance of the technology and do not certify that a technology will
    always operate as verified. The end user is solely responsible for complying with any and all applicable
    federal, state, and local requirements. Mention of corporate names, trade names, or commercial products
    does not constitute endorsement or recommendation for use of specific products. This report is not an NSF
    Certification of the specific product mentioned herein.
        Availability of Supporting Documents
        Copies of the Protocol for the Verification ofln-Drain Treatment Technologies, April 2001, the
        verification statement, and the verification report (NSF Report Number 07/30/WQPC-SWP) are
        available from:
           ETV Water Quality Protection Center Program Manager (hard copy)
           NSF International
           P.O. Box 130140
           Ann Arbor, Michigan 48113-0140
        NSF website: http://www.nsf.org/etv (electronic copy)
        EPA website: https://www.epa.gov/etv (electronic copy)
        Appendices are not included in the verification report, but are available from NSF upon request.
07/30/WQPC-SWP      The accompanying notice is an integral part of this verification statement.          September 2007

                                                VS-v

-------
            Environmental Technology Verification Report


              In-Drain Treatment Device

The Hydro International Up-Flo™ Treatment
                             Device
                          Prepared by:
                       Penn State Harrisburg
                  Middletown, Pennsylvania 17057
 Under a cooperative agreement with the U.S. Environmental Protection Agency

                 Raymond Frederick, Project Officer
                 ETV Water Quality Protection Center
             National Risk Management Research Laboratory
              Water Supply and Water Resources Division
                U.S. Environmental Protection Agency
                       Edison, New Jersey
                         September 2007
      Revised April 2009 with Supplemental Vendor Testing (Chapter 6)

-------
                                      Notice
This document has been peer reviewed and reviewed by NSF and EPA and recommended for
public release. Mention of trade names or commercial products does not constitute endorsement
or recommendation by the EPA for use or certification by NSF.
                                        in

-------
                                      Foreword

The EPA is charged by Congress with protecting the Nation's land, air,  and water resources.
Under a mandate of national environmental laws, the Agency strives to formulate and implement
actions leading to a compatible balance between human activities  and the  ability of natural
systems to support and nurture life. To meet this mandate, EPA's research program is providing
data  and technical support for  solving environmental problems today and building a science
knowledge base necessary to manage our ecological resources wisely, understand how pollutants
affect our health, and prevent or reduce environmental risks in the future.

The National Risk Management Research Laboratory (NRMRL) is the  Agency's center for
investigation of technological and management approaches for preventing and reducing risks
from pollution that threaten human health and the environment.  The focus of the Laboratory's
research  program  is on  methods and their cost-effectiveness for prevention and control  of
pollution to air, land, water, and subsurface resources; protection of water quality in public water
systems;  remediation of contaminated sites, sediments and ground water; prevention and control
of indoor air pollution; and restoration of ecosystems.  NRMRL  collaborates  with both public
and private  sector partners to foster technologies that reduce the cost of compliance and to
anticipate emerging  problems.   NRMRL's research provides  solutions to environmental
problems by: developing and promoting technologies that protect and improve  the environment;
advancing scientific and engineering information to support regulatory and policy decisions; and
providing the  technical   support  and  information   transfer  to ensure  implementation  of
environmental regulations and strategies at the national, state, and community levels.

This publication has been produced as part of the Laboratory's strategic long-term research plan.
It is published and made  available by EPA's Office of Research and Development to assist the
user community and to link researchers with their clients.
                                  Sally Gutierrez, Director
                                  National Risk Management Research Laboratory
                                           IV

-------
                                       Contents

Verification Statement	VS-i
Notice	iii
Foreword	iv
Contents	v
Figures	vi
Tables	viii
Abbreviations and Acronyms	ix
Chapter 1 Introduction	1
  1.1    ETV Purpose and Program Operation	1
  1.2    Testing Participants and Responsibilities	1
       1.2.1  U.S. Environmental Protection Agency	1
       1.2.2  NSF International - Verification Organization (VO)	2
       1.2.3  Testing Organization - Penn State Harrisburg	3
       1.2.4  Vendor - Hydro International	3
  1.3    Verification Testing Site	4
Chapter 2 Up-Flo™ Filter Equipment Description and Operating Processes	5
  2.1    Equipment Description	5
       2.1.1  Up-Flo™ Filter Components	5
  2.2    Hydraulic Flow Path	6
  2.3    Flow Conditions	6
       2.3.1  Operating Flow Conditions	6
       2.3.2  Bypass Flow Conditions	7
       2.3.3  Drain Down	8
  2.4    Sizing and Hydraulic Capacity	8
  2.5    Test Unit Specifications and Test Setup Description	9
  2.6    Up-Flo™ Filter Capabilities and Claims	12
       2.6.1  System Capability	12
       2.6.2  Vendor Claims	12
  2.7    Performance Measures for the Verification Test	13
       2.7.1  Contaminant Selection and Monitoring for Performance	13
       2.7.2  System Component Operation and Maintenance Performance	14
       2.7.3  Quantification of Residuals	14
Chapters Verification Testing Procedures	15
  3.1    Testing Objectives	15
  3.2    Test Equipment	16
  3.3    Test Phases -Hydraulic Loading	19
       3.3.1  Phase I — Performance under Intermittent Flow Conditions	19
       3.3.2  Phase II - Determination of the Capacity of the Unit	20
       3.3.3  Phase III - Performance Under Varied Hydraulic and Concentration Conditions21
       3.3.4  Phase IV- Contaminant Capacities at High Hydraulic Throughput	22
  3.4    Influent Characterization	23
       3.4.1  Synthetic Challenge Water	23
       3.4.2  Stock Solutions	24
       3.4.3  Influent Characterization during the Verification Testing	25

-------
       3.4.4   Solids Characterization during the Verification Testing	25
  3.5    Effluent Characterization	26
  3.6    Residue Management	26
  3.7    Operation and Maintenance Observations	26
Chapter 4 Verification Testing Results and Discussion	28
  4.1    Synthetic Wastewater Composition	28
  4.2    Synthetic Wastewater Laboratory Analytical Results	31
  4.3    Test Phases in the Test Plan	32
       4.3.1   Phase I - Performance under Intermittent Flow Conditions	32
       4.3.2   Phase II - Determination of the Capacity of the Unit	36
       4.3.3   Phase III - Performance under Varied Hydraulic and Concentration Conditions 42
       4.3.4   Phase IV- Contaminant Capacities at High Hydraulic Throughput	56
  4.4    Phases I-IVData Summary and Discussion	60
       4.4.1   Installation and Operation & Maintenance Findings	61
  4.5    Summary of Findings	63
Chapter 5 Quality Assurance/Quality Control	65
  5.1    Audits	65
  5.2    Precision	65
       5.2.1   Field and Laboratory Precision Measurements	65
  5.3    Accuracy	67
  5.4    Representativeness	67
  5.5    Completeness	68
Chapter 6 Vendor Supplemental Testing	69
  6.1    Up-Flo® Filter Modifications	69
  6.2    Test Procedure Modifications	70
       6.2.1   Synthetic Challenge Water	70
       6.2.2   Analytical Methods	71
  6.3    Synthetic Challenge Water Laboratory Analytical Results	71
  6.4    Test Results	72
       6.4.1   Phase I - Performance under Intermittent Flow Conditions	72
       6.4.2   Phase II - Determination of the Capacity of the Unit	77
  6.5    Sediment Retained in Sump	81
  6.6    Test Summary and Discussion	83
Appendices	87
  A   Test Plan	87
  B   UpFlo™ Filter O&M Manual	87
  C   Analytical Data	87


                                       Figures

Figure 2-1. Up-Flo™ Filter components	5
Figure 2-2. Filter module components	6
Figure 2-3. Flow path during normal operating conditions	7
Figure 2-4. Flow path during bypass flow conditions	7
Figure 2-5. Flow path during drain down conditions	8
                                           VI

-------
Figure 2-6. Bypass water levels for standard Up-Flo™ Filter (left) and shallow Up-Flo™ Filter.
     	9
Figure 2-7. Up-Flo™ Filter test unit isometric view	10
Figure 2-8. Up-Flo™ Filter test unit plan view	10
Figure 2-9. Section view of Up-Flo™ Filter test unit	11
Figure 3-1. Test rig process flow diagram	16
Figure 3-2. Sediment particle size distribution graph	18
Figure 4-1. Phase I TSS influent and effluent results	33
Figure 4-2. Phase I SSC influent and effluent results	34
Figure 4-3. Phase I total phosphorus influent and effluent results	34
Figure 4-4. Phase I COD influent and effluent results	35
Figure 4-5. Phase I particle size distribution summary	35
Figure 4-6. Phase II TSS influent and effluent results	37
Figure 4-7. Phase II SSC influent and effluent results	37
Figure 4-8. Phase II total phosphorus influent and effluent results	38
Figure 4-9. Phase II COD influent and effluent results	38
Figure 4-10. Phase II PSD summary	39
Figure 4-11. Phase I and II TSS cumulative loading results	40
Figure 4-12. Phase I and II SSC cumulative loading results	40
Figure 4-13. Phase I and II total phosphorus cumulative loading results	41
Figure 4-14. Phase I and II COD cumulative loading results	41
Figure 4-15. Phase I and II PSD summary	42
Figure 4-16.  Phase III Part 1  relationship between influent and effluent flow rates using clean
    water	43
Figure 4-17. Phase III Part 1 tank water depth as a function of influent flow rate	44
Figure 4-18. Phase III Part 1 drawdown flow rates	44
Figure 4-19. Phase III Part 2 relationship between influent and effluent flow rates	45
Figure 4-20. Phase III Part 2 tank water depth as a function of influent flow rate	46
Figure 4-21. Phase III Part 3 relationship between influent and effluent flow rate	46
Figure 4-22. Phase III Part 3 tank water depth as a function of influent flow rate	47
Figure 4-23. Comparison of influent versus effluent flow rates for Phase III hydraulics testing.48
Figure 4-24. Phase III Part 2 TSS influent and effluent results	51
Figure 4-25. Phase III Part 2 SSC influent and effluent results	51
Figure 4-26. Phase III Part 2 total phosphorus influent and effluent results	52
Figure 4-27. Phase III Part 2 COD influent and effluent results	52
Figure 4-28. Phase III Part 3 TSS influent and effluent results	53
Figure 4-29. Phase III Part 3 SSC influent and effluent results	53
Figure 4-30. Phase III Part 3 total phosphorus influent and effluent results	54
Figure 4-31. Phase III Part 3 COD influent and effluent results	54
Figure 4-32. Phase III Part 2 PSD summary	55
Figure 4-33. Phase III Part 3 PSD summary	56
Figure 4-34. Phase IV TSS influent and effluent cumulative loading results	58
Figure 4-35. Phase IV SSC influent and effluent cumulative loading results	58
Figure 4-36. Phase IV total phosphorus influent and effluent cumulative loading results	59
Figure 4-37. Phase IV COD influent and  effluent cumulative loading results	59
Figure 4-38. Phase IV particle size distribution analysis	60
                                           vn

-------
Figure 6-1. Modifications to Up-Flo® Filter module	69
Figure 6-2. Modifications to Up-Flo® Filter module showing improved support details	70
Figure 6-3. Phase I TSS influent and effluent results	74
Figure 6-4. Phase I SSC influent and effluent results	74
Figure 6-5. Phase I TP influent and effluent results	75
Figure 6-6. Phase IRP influent and effluent results	75
Figure 6-7. Phase I tank water level	76
Figure 6-8. Phase I influent and effluent PSD summary	77
Figure 6-9. Phase II TSS influent and effluent results	79
Figure 6-10. Phase II SSC influent and effluent results	79
Figure 6-11. Phase II TP influent and effluent results	80
Figure 6-12. Phase IIRP influent and effluent results	80
Figure 6-13. Phase II tank water level	80
Figure 6-14. Phase II influent and effluent particle size distribution summary	81
Figure 6-15. Depth of sedimentation in sump	82
Figure 6-16. Sump particle size distribution analysis results	82


                                        Tables

Table 3-1.  Particle Size Distribution	17
Table 3-2.  Revised Synthetic Challenge Water Concentrations	23
Table 3-3.  Synthetic Challenge Water Mix Concentrations	24
Table 4-1. Desired Feed Rates at "Normal" Settings (matching the concentrations in the original
    challenge solution)	29
Table 4-2.  Desired Feed Rates at "4X Concentration" Settings	30
Table 4-3.  Synthetic  Wastewater Analytical Data Comparison Test Plan Concentration Mean
    Testing	31
Table 4-4.  Phase I Analytical Data Summary	32
Table 4-5.  Phase II Analytical Summary	36
Table 4-6.  Phase III Influent and Effluent Flow Summary	47
Table 4-7.  Phase III Part 2 Analytical Data	49
Table 4-8.  Phase III Part 3 Analytical Data	50
Table 4-9.  Phase IV Analytical Summary	57
Table 4-10. Characterization of Material Captured in Up-Flo™ Filter Sump	63
Table 5-1. Replicate Laboratory Sample RPD Summary	66
Table 5-2. Laboratory Control Sample Data Summary	67
Table 6-1.  Modified Synthetic Challenge Water Concentrations	70
Table  6-2.    Synthetic  Challenge  Water  Analytical  Data Comparison to  Desired Feed
    Concentration	72
Table 6-3.  Phase I Analytical Data Summary	73
Table 6-4.  Phase II Analytical Data Summary	78
                                          Vlll

-------
                           Abbreviations and Acronyms
cfs
COD
dso
EPA
ETV
ft2
ft3
g
gal
gpm
hr
in.
L
LAS

Ib
NRMRL
mg/L
min
mL
um
NIST
NSF
OBC
O&M
P
PI
PSH
QA
QAPP
QC
RPD
SAP
ssc
STPP
TCLP
TO
TP
TSS
USGS
VO
WQPC
WSC
Cubic feet per second
Chemical oxygen demand
Diameter of 50th percentile particle
U.S. Environmental Protection Agency
Environmental Technology Verification
Square feet
Cubic feet
Gram
Gallon
Gallon per minute
Hour
Inch
Liter
Linear alkylbenzene  sulfonate  (represented  by Dodecylbenzenesulfonic
acid)
Pound
National Risk Management Research Laboratory
Milligram per liter
Minute
Milliliter(s)
Micron
National Institute of Standards and Technology
NSF International
Oil-based constituents
Operations and maintenance
Phosphorus
Principal Investigator
Penn State Harrisburg
Quality assurance
Quality Assurance Project Plan
Quality control
Relative percent difference
Sampling and Analysis Plan
Suspended sediment concentration
Sodium tripolyphosphate
Toxicity Characteristic Leachate Procedure
Testing Organization (Penn State Harrisburg)
Total phosphorus
Total suspended solids
United States Geological Survey
Verification Organization (NSF)
Water Quality Protection Center
Water-soluble constituents
                                          IX

-------
                                 Acknowledgements

Penn  State Harrisburg was responsible for all elements in the testing sequence, including test
setup, calibration and verification of instruments, data collection and analysis, data management,
data interpretation, and the preparation of this report.

       Penn State Harrisburg
       777 W. Harrisburg Pike
       Middletown, Pennsylvania 17057
       Contact Person:  Shirley Clark

The vendor of the equipment is:

       Hydro International
       94 Hutchins Dr.
       Portland, Maine 04102-1930
       Contact Person:  Kwabena Osei

The Testing Organization thanks  J. Bradley Mikula for his planning of the testing apparatus,
James Elligson, Julia Hafera  and David Spyker for  their assistance in assembling the test
apparatus and Christopher  Roenning, Kelly Franklin,  Christine Siu and Brett Long  for their
many hours testing the Up-Flo™ Filter and analyzing the resulting samples. The TO also thanks
the Environmental Engineering Program for its support and patience during the testing period as
we occupied a large portion of the wastewater laboratory.

-------
                                      Chapter 1
                                     Introduction

1.1    ETV Purpose and Program Operation

The U.S. Environmental Protection  Agency (EPA) has created the Environmental  Technology
Verification  (ETV)  Program  to  facilitate  the  deployment  of  innovative  or  improved
environmental technologies through  performance verification and dissemination of information.
The ETV Program's goal is to further environmental protection by substantially accelerating the
acceptance and use of improved and  more cost-effective technologies. ETV seeks to achieve this
goal by providing high-quality, peer-reviewed data on technology performance to those involved
in the design, distribution, permitting, purchase, and use of environmental technologies.

ETV  works  in  partnership  with  recognized  standards  and  testing  organizations  (TOs);
stakeholders groups that consist of  buyers, vendor organizations, and permitters; and the full
participation of individual technology developers. The program evaluates the performance of
innovative technologies by developing test plans that are responsive to the needs of stakeholders,
conducting field or laboratory tests (as appropriate), collecting and analyzing data, and preparing
peer-reviewed reports. All evaluations are conducted  in  accordance with rigorous  quality
assurance/quality  control (QA/QC) protocols to ensure that data of known and adequate quality
are generated and  that the results are  defensible.

NSF International (NSF) operates the Water Quality Protection Center (WQPC) in cooperation
with EPA.  The Source Water Protection Area of the WQPC evaluated the performance of the
Hydro International's  Up-Flo™  Filter,  which  is  an in-drain device  designed to remove
hydrocarbons, organically bound metals, sediments, and other organic chemical compounds from
commercial or industrial runoff and  wet weather flow. This document provides the verification
test results for the Hydro International Up-Flo™ Filter.

It is important to  note that verification of the equipment does not mean that the equipment is
"certified"  by NSF or "accepted" by EPA. Rather, it recognizes that the performance  of the
equipment has been determined and verified by these organizations for those conditions tested by
the TO.

1.2    Testing Participants and Responsibilities

The  ETV  testing of the  Up-Flo™ Filter was  a cooperative  effort between the  following
participants: EPA, NSF, PSH, and Hydro International.

The following is a brief description of each ETV participant and their roles and responsibilities.

1.2.1   U.S. Environmental Protection Agency

The EPA Office of Research and Development, through the Urban Watershed Branch,  Water
Supply and Water Resources Division, NRMRL, provides administrative, technical, and QA

-------
guidance and oversight on all ETV WQPC activities. This peer-reviewed document has been
reviewed by NSF and EPA and recommended for public release.

The key EPA contact for this program is:

       Mr. Ray Frederick, Project Officer, ETV Source Water Protection Program
       (732) 321-6627  e-mail: Frederick.Ray@epamail.epa.gov
       USEPA, NRMRL
       Urban Watershed Management Research Laboratory
       2890 Woodbridge Ave. (MS-104)
       Edison, NJ 08837-3679

1.2.2   NSF International - Verification  Organization (VO)

NSF is EPA's verification partner organization for administering the WQPC. NSF is a not-for-
profit testing and certification organization dedicated to public health safety and the protection of
the environment.  Founded  in  1946  and located in  Ann  Arbor,  Michigan, NSF has  been
instrumental in the development of consensus  standards for the protection of public health and
the environment. NSF also provides testing and  certification services to ensure that products
bearing the NSF Name, Logo, or Mark meet those standards.

NSF's responsibilities as the VO include:
•  Review and comment on the test plan;
•  Review the quality systems of all parties involved with the TO and subsequently, qualify the
   TO;
•  Oversee the TO activities related to the technology evaluation and associated laboratory
   testing;
•  Carry out an on-site audit of test procedures;
•  Oversee the development of a Verification Report and Verification Statement;
•  Coordinate with EPA to approve the Verification Report and Verification Statement;
•  Provide QA/QC review and support for the TO.

Key contacts at NSF for the test plan and program are:

       Mr. Thomas Stevens, Program Manager    Mr. Patrick Davison, Project Coordinator
       (734) 769-5347                          (734) 913-5719
       e-mail:  Stevenst@NSF.org                davison@nsf.org

       NSF International
       789 Dixboro Road
       Ann Arbor, Michigan 48105

-------
1.2.3   Testing Organization - Penn State Harrisburg

Penn  State  Harrisburg (PSH)  acted  as the  TO for the  verification  testing.  The  PSH
Environmental Engineering Wastewater Laboratory had the space and large-scale  equipment
(tanks, pumps,  etc.)  to perform the testing  on the Up-Flo™ unit, and the PSH Stormwater
Management Research Group Laboratory has the  equipment and  experience to perform the
analytical work for this test plan.

The TO  provided  all needed logistical support, established a communications network, and
scheduled and coordinated activities of all participants. The TO was responsible for ensuring that
the testing location and feed water conditions were  such that the verification testing could meet
its stated objectives.  The TO prepared  the test plan; oversaw the testing; managed,  evaluated,
interpreted, and reported on the data generated by the testing; and reported on the performance of
the technology.

TO employees manufactured and prepared the testing rig,  assured the required test  conditions
were  met, and  measured and recorded data during the testing. The TO's Project Manager
provided oversight of the daily tests.

The key personnel and contacts for the TO are:

       Shirley E. Clark, Ph.D., P.E.
       Assistant Professor of Environmental Engineering
       Penn State Harrisburg Environmental Engineering Program
       777 W. Harrisburg Pike TL-105
       Middletown, PA 17057

1.2.4   Vendor — Hydro International

Hydro International  is the  vendor of  the Up-Flo™ Filter.  The vendor was responsible for
supplying a  field-ready Up-Flo™ unit  and filter media,  and was  available during all tests to
provide technical assistance  as needed.

The primary contact for the vendor is:

       Kwabena Osei, Research & Development Manager
       (207) 756-6200
       e-mail: kosei@hil-tech.com

       Hydro International
       94 Hutchins Dr.
       Portland, Maine 04102-1930

-------
1.3    Verification Testing Site

The verification testing was performed at PSH's  campus in Middletown, Pennsylvania. The
testing rig was set up in the PSH Environmental Engineering Wastewater High-Bay Laboratory,
which is capable of performing a wide array of research programs. The laboratory was equipped
with the necessary storage tanks and equipment to  provide flows up to 50 gpm with storage of
1,700 gal in the clean-water tank.

Samples of the synthetic wastewater mixture used  for testing were  created and analyzed in the
Environmental Engineering Program's Stormwater Research Laboratory, which is located in the
same building as the Wastewater High-Bay Laboratory.

-------
                                     Chapter 2
       Up-Flo™ Filter Equipment Description and Operating Processes

2.1    Equipment Description

The Up-Flo™ Filter is a passive, modular filtration system that incorporates multiple elements of
a treatment train into a single, small-footprint device. The Up-Flo™ Filter uses a sedimentation
sump and screening system to pretreat runoff before it flows up through the filter media where
final polishing occurs. A high-capacity, siphonic bypass safeguards against upstream ponding
during high-flow events. The siphon also serves as a floatables baffle to prevent the  escape of
floatable trash and debris from the Up-Flo™ Filter chamber.

2.1.1   Up-Flo™ Filter Components

The Up-Flo™ Filter has no moving parts and no external power requirements. It consists of a
cylindrical concrete vessel with plastic internal components  and a stainless steel support frame.
The concrete vessel is a standard cylindrical manhole with an inlet pipe or a grate opening. An
inspection port at ground  level provides access to the sump  for sediment removal. The internal
components consist of angled stainless steel screens, wedge-shaped filter modules,  a  bypass
siphon with a floatables baffle, and an outlet module. The base of the outlet module is equipped
with a drain-down port design  that enables standing water to drain out  of the filter media
between  storm  events, preventing the re-release of captured pollutants. The Up-Flo™ Filter
components are shown in Figure 2-1.
Bypass Siphon/
Floatables Baffle
                                                            Inlet Grate/
                                                            Maintenance Access
Outlet Module
                                                            Filter Module
                                                            Angled Screen

                                                            •Drain-down port
                                                            (not seen from this
                                                            view)
Figure 2-1. Up-Flo™ Filter components.

-------
  The filter module houses the media pack. The media pack consists of two filter media bags and
  two layers of flow distributing media. The internal components of the filter module are shown in
  Figure 2-2.
Filter Module Lid
                               P     - L.           LXf^^^i   "Media Restraint
Conveyance channel-
                                                            ^^^     Media Pack
Filter Module
Support Brackets	                            •—	Angled Screen
 Figure 2-2. Filter module components.

 2.2    Hydraulic Flow Path

 The Up-Flo™ Filter is self-activating and operates on simple fluid hydraulics. The configuration
 of the internal components directs the flow in a pre-determined path through the vessel as
 described below.

 2.3    Flow Conditions

 2.3.1   Operating Flow Conditions

 Challenge water enters the chamber from an inlet pipe or an overhead grate and flows into the
 sump region where gross debris and coarse grit are removed by settling. Runoff continues to fill
 the chamber until there is enough driving head to initiate flow through the filter media. At this
 point, the water flows up through the angled screen into the filter module. In the filter module,
 water passes up through the filter media and is  conveyed to the outlet module via the flow
 conveyance channel.  The flow  path  through  the  Up-Flo™ Filter during normal operating
 conditions is illustrated in Figure 2-3.

-------
Figure 2-3.  Flow path during normal operating conditions.

2.3.2   Bypass Flow Conditions

Flows in excess of the filtration capacity are discharged  directly to the outlet module by the
siphonic bypass. The siphon also serves as a floatables baffle to prevent the escape of buoyant
litter and debris. The flow path through the Up-Flo™ Filter during bypass flow conditions  is
shown below in Figure 2-4.
Figure 2-4.  Flow path during bypass flow conditions.

-------
2.3.3  Drain Down

Filter media continuously submerged in water can become anoxic, producing an environment
that promotes bacterial growth and the release of other harmful leachates. The Up-Flo™ Filter is
equipped with  a drain-down mechanism to ensure that the filter media sits above the standing
water level during no-flow conditions. As flows subside, water slowly drains out of the chamber
through  drain-down ports located at the base of the outlet module. The drain-down ports are
covered  with filter fabric to provide treatment to the  drain-down flows. The flow path for the
drain down mechanism is shown in Figure 2-5.
Figure 2-5. Flow path during drain down conditions.

2.4    Sizing and Hydraulic Capacity

The Up-Flo™ Filter is sized to treat the peak treatment flow of a water quality design storm. The
peak flow is determined from calculations based on the contributing watershed hydrology and
from a design storm magnitude  set by the local challenge water management agency.  The
number of filter modules included in an Up-Flo™ Filter is  determined by the peak treatment
flow.

The flow rate through each filter module depends on the nature and type of media within the
module and the water level in the Up-Flo™ Filter chamber. By adjusting media blends and the
height  of the water column in  the chamber, each filter module can be engineered to have a
treatment flow rate  of 10 to 25 gpm. The flow rate through each filter module will determine the
number of modules needed to treat the peak treatment flow of the storm event.

The Up-Flo™ Filter is equipped with a bypass  siphon designed to discharge flows in excess of
the treatment flow. When influent flows  exceed the filtration capacity, the water level in the

-------
Up-Flo™ Filter chamber rises until it reaches the height of the internal weir of the bypass. Once
water starts to flow over the weir, the bypass siphon begins drawing water out of the chamber
discharging the excess flows through the outlet module to the outlet pipe.

The  height  of the  bypass can be  adjusted to  accommodate shallow retrofits  or restrictive
hydraulic profiles. The standard Up-Flo™ Filter bypasses up to 7 cfs with 2.5 feet of hydraulic
drop. A  shallow unit, depicted in Figure 2-6, has a bypass capacity of 4 cfs with 1.7 feet of
hydraulic drop.
Figure 2-6. Bypass water levels for standard Up-Flo™ Filter (left) and shallow Up-Flo™
Filter.
2.5    Test Unit Specifications and Test Setup Description

The unit to be tested is a full scale, commercially available catch basin system. For the standard
catch basin configuration, the Up-Flo™ Filter is comprised of one to six filter modules. In
normal  business practice, the number  of  filter modules included in an Up-Flo™ Filter is
dependent upon the required peak treatment flow rate. Because the Up-Flo™ Filter is sized on a
per-module basis, it is important for modular systems to be characterized on a per-module basis.
TSS, phosphorous  and hydraulic capacity performance claims will be verified on a one-module
Up-Flo™ Filter setup. The two-module Catch Basin Up-Flo™ Filter set up is shown in Figure 2-
7, Figure 2-8, and Figure 2-9.

-------
Up-Flo™ Filter Test Tank
Viewing/Clean Out Port          •

Sump	

                                                                _-...
   Bypass Siphon/
   Floatables Baffle

   Outlet Module

   Outlet Pipe

   Filter Module

   Support Brackets
   with Legs
Figure 2-7.  Up-Flo™ Filter test unit isometric view.

The test unit has a 24-in. sump depth, a 12-in. outlet, and an 18-in. acrylic viewing port. The
height of the bypass is set so that there can be 21 in. of driving head acting on the Up-Flo™
Filter before bypass levels are reached.  The test tank will be set up such that inflows pour into
the chamber through the open top, replicating a grated-inlet field installation.
Up-Flo™
Filter test tank
Viewing/Clean
Out port
  Sump
Filter Module
                                                                   Bypass Siphon/
                                                                   Floatables Baffle
 Outlet Pipe
   Support
   Bracket Legs
Figure 2-8.  Up-Flo™ Filter test unit plan view.
                                          10

-------
Up-Flo™ Filter Test
Tank
Filter Module


Viewing/Clean Out Port


Sump
Bypass Siphon/
Floatables Baffle
Outlet Module


Outlet Pipe

Support/Legs

Angled Screen
Figure 2-9.  Section view of Up-Flo™ Filter test unit.

The tests will be performed at PSH's Environmental Engineering Program's Wastewater High-
Bay  Laboratory. The PSH laboratory is set up to handle testing of this type with  physical
facilities that includes a water supply up to 50 gpm, tanks, mixers, and pumps to store and feed
the synthetic water,  and all  other associated  piping,  controls and  related equipment. The
Up Flo™  Filter is  a  passive  unit that  does not require any utility  connections to  operate.
Therefore,  there will be no electrical  requirements  needed for operation  of the unit. The
laboratory is equipped with water and electrical needs to supply the synthetic challenge water to
the unit,  operate  pumps,  mixers,  and sampling  equipment,  etc.  However, none of these
requirements would be needed in a field application.

The  synthetic challenge  water described later in this test plan contained simulated challenge
water solids and a source of particulate phosphorus.  The contaminant concentrations in the
synthetic water were similar to those found in challenge water runoff, based  on data generated
both during the Nationwide Urban  Runoff Program (NURP) and the more-recent analysis of
outfall data. The solids that accumulated as part of testing were solid waste that required disposal
after testing. The solids were tested prior to  disposal to ensure they are not regulated materials
that require special disposal. In addition, a carbon filter was used to treat the discharge water
after the effluent settling  tank to ensure that  the organic pollutants were removed to acceptable
levels prior to discharge.
                                           11

-------
2.6    Up-Flo™ Filter Capabilities and Claims

2.6.1   System Capability

The  Up-Flo™  Filter is  a compact treatment-train device that targets the wide range  of
contaminants typically found in water  runoff.  Each Up-Flo™ Filter includes a sedimentation
sump,  coarse screens and polishing filter media. Coarse grit and gross  debris is removed by
settling in the sump, neutrally  buoyant debris is removed by screening, and fine suspended
sediment is  removed by  filtration.  The filter media may be customized to target other  site-
specific pollutants such as metals and organics.

A single filter module was used in this verification program. The filter  media installed in the
module was Hydro International's  CPZ  Mix™,  which is made up  of activated  carbon,
manganese-coated zeolite and peat. Granular activated carbon is a traditional filter media for
targeting organic chemicals,  pesticides  and  herbicides.  The manganese-coated zeolite targets
TSS, iron, manganese and ammonium in challenge water runoff. The small fraction of peat is
highly  efficient at removing organics and metals.

Each filter module filled  with the CPZ Mix™ has  a design flow rate of 20-25 gpm when the
water level in the chamber provides 20  in. of driving head. Water is filtered through the filter
media until the water level in the chamber falls to zero inches of driving head. When  the inflows
exceed the filtration capacity, the excess flows discharge through the bypass siphon directly to
the outlet module. The bypass is designed to accommodate  7  cfs of excess flows.  This high-
capacity bypass siphon ensures that head-loss and flow-restrictions  due to the filter media will
not cause collection system backups and ponding on the surface during  events with high flow
rates.

Maintenance of the sump and replacement of the filter bags is important for the successful long-
term operation of the Up-Flo™ Filter. The flow capacity of the Up-Flo™ Filter will  decrease as
it accumulates sediments. The filter bags should be replaced once a year (or as needed) to ensure
that fine sediment build-up is  not allowed to accumulate such that the flow rate of the filter will
be significantly reduced. Sediment and gross debris must also be periodically removed from the
sump to ensure that accumulated sediment does not block the intake of the filter module.

This test plan was designed to meet the basic protocol requirements and focused on the treatment
capability of the unit to remove sediment and particulate phosphorous from synthetic challenge
water.  The  experimental  design and sampling  and analysis plan presented in  the following
sections provide details on the test protocol and the constituents targeted for this verification.

2.6.2   Vendor Claims

The Up-Flo™ Filter is designed to incorporate multiple elements  of a  treatment train into a
single,  small-footprint device. The  Up-Flo™ Filter utilizes settling,  screening and filtration to
remove gross  debris and suspended sediment from  challenge water runoff. Specifically,  the
Up-Flo™ Filter will remove over 80% of fine total suspended solids (TSS) from challenge water
runoff, and  it will also remove a portion of metals, organics  and  other pollutants commonly
                                           12

-------
found sorbed to the surface of suspended sediment particles.  Verification of the removals of
metals, organics (except that measured as chemical oxygen demand [COD]), and other pollutants
was not included as part of the test plan.

Regular maintenance events are necessary to ensure optimal performance of the Up-Flo™ Filter
over time. In-field maintenance includes removing floatables, sediment and other pollutants from
the sump and changing out the media packs. In-field inspection should occur regularly. In-field
media pack replacement should occur once a year or as needed. The in-field maintenance of each
Catch Basin Up-Flo™ Filter unit should take a half-hour or less. Maintenance on the Up-Flo™
Filter test unit will  occur after each phase of performance testing. The side of the Up-Flo™ Filter
test tank is equipped with an 18-in.  access port to facilitate sump cleanout (see Figure 3-7). To
replace media packs, entry into the test tank is necessary. The tank is spacious enough to provide
comfortable access for one maintenance  person. Confined space issues did  not  need to be
addressed during this testing since the test tank was open to the atmosphere.

To properly maintain the Up-Flo™ Filter, the steps detailed in the Up-Flo™ Filter Operation &
Maintenance (O&M) Manual were followed.

2.7    Performance Measures for the Verification Test

The  performance  capabilities  of the Up-Flo™  Filter were assessed both quantitatively and
qualitatively. Sampling and analysis of the influent,  effluent, and  residues provided data to
determine the treatment efficiency  of the  unit with  quantitative data.  Recording  of visual
observations, operational issues and  maintenance requirements provided a basis for qualitatively
assessing the unit's performance. The test plan,  including the Experimental  Design,  Sampling
and Analysis Plan (SAP), and Quality Assurance Project Plan (QAPP), focused on obtaining
performance-based  data that  served as the foundation  of  the  verification  report and the
verification statement.

2.7.1   Contaminant Selection and Monitoring for Performance

The Up-Flo™ Filter unit is designed to remove solids and solids-associated pollutants, such as
particulate-bound phosphorus  in  runoff. Based on the unit's capabilities  a  list  of targeted
contaminants that will be monitored for removal by the unit has been selected. The targeted list
is as follows:

Targeted Contaminant List

       •  Suspended sediment concentration (SSC)
       •  Total suspended solids (TSS)
       •  Total phosphorus (TP)

These constituents, in addition COD [as a surrogate for the added organics], were measured in
influent and effluent samples in accordance with the  experimental  design and the SAP.  The
results provided data for determining the performance capability of the unit to remove targeted
contaminants and provide data on the additional and secondary contaminants as well. All of
                                           13

-------
these data are reported  in  the verification  report as part of the quantitative performance
measurements.

2.7.2  System Component Operation and Maintenance Performance

The overall system performance was measured both quantitatively and qualitatively. Quantitative
measurements included determination of the range of hydraulic flow conditions that can  be
handled by  the unit.  The hydraulic capacity  of the  unit was determined by measuring the
hydraulic flow rate in volume of water treated and flow rate handled. The experimental design
included both hydraulic loading tests and loading of contaminants to the unit. The filter media
and containment bag combination was stressed to exhaustion and spike loads were charged to the
unit at high flow rates. The mass removal of contaminants was determined.

Qualitative measures were assessed by observations of and experience with the unit during the
setup and testing phases. Records were maintained on the ease and time of installation, the time
and ease of maintenance for cleanout and absorption medium replacement, and other operating
observations. The  unit is a simple design with no controls, instrumentation, alarms, or other
mechanical or electrical devices that will require operation. The unit was monitored for solids or
debris buildup, clogging of entry paths, and other related operational issues. The O&M Manual
provided by  Hydro International was  reviewed for its specificity and completeness. These
observations, experiences, records and review will  be the basis for evaluating the system
performance in terms of operation and maintenance.

2.7.3  Quantification of Residuals

Testing the Up-Flo™ Filter created residual material, such as removed contaminants, sediments,
and  spent filter media. The  quantity of residual materials  requiring disposal was  a factor in
performance measurements.
                                           14

-------
                                      Chapter 3
                          Verification Testing Procedures
3.1    Testing Objectives
The objective of in-drain treatment  system verification testing under the ETV Source  Water
Protection Protocol for In-Drain Treatment Technologies is to evaluate the contaminant removal
performance and operational and maintenance performance of commercially available systems.

The objective  of this  testing  was to  determine  the performance  attained by the Hydro
International's Up-Flo™ Filter when used to treat synthetic challenge water containing a variety
of contaminants,  including sediments,  hydrocarbons,  water-soluble organics and fertilizer. In
order to estimate the "life" of the device  before maintenance in  a rapid period of time, the
concentrations of all contaminants except sediment tested were higher than those typically seen
in urban stormwater, but lower  than those anticipated to be seen in mixes of stormwater and
washwater.

The objective was achieved by implementing testing procedures presented in the  protocol and
test  plan (Appendix A).  A  synthesized  challenge  water  containing  sediments,  petroleum
hydrocarbons, and surfactants was prepared to simulate contaminants at concentrations typically
found in a mixture of surface water runoff and other wet-weather flows at a commercial or
industrial setting. The  treatment system  was challenged  under a variety of hydraulic loading
conditions using the  synthetic wastewater. Influent and effluent samples collected from the unit
were measured for various contaminants as  determined by indicator tests (e.g., COD,  TSS, SSC,
Particle Size Distribution, and TP). The results were used to calculate  removal efficiencies and
system  capacities, and to determine  the system treatment effectiveness. The treatment system
was also monitored for operation and maintenance characteristics, including the performance and
reliability of the equipment and the level of operator maintenance required.

The experimental  design followed the methods and procedures defined in  the protocol. The
design incorporated all  of the elements described in the protocol and included all of the phases of
testing prescribed. There were two anticipated deviations or exceptions from the protocol as
understood by the TO. These deviations were as follows:

    1.  The measurement of head loss  was not directly applicable due to  the design of the
       Up-Flo™ Filter; and
    2.  The synthetic challenge water concentrations set to reflect the requested challenge water
       concentrations,  and, since no  description of the  sediment was provided, the particle size
       distribution  of  the  sediment was selected  based on  those required by  New Jersey
       Department of Environmental Protection challenge water device evaluation protocols.

The verification test was  a controlled  test. The testing was performed on a full-scale unit
(containing one filter cartridge) and was set up in the PSH Wastewater Research laboratory. The
PSH Wastewater Research laboratory is a physical testing laboratory with space, tanks, piping,
utilities, etc., to  perform medium scale (10 -  50 gpm) testing of this type. The synthetic
challenge used for the testing was made as described later in this section and dosed to the unit as
                                           15

-------
prescribed in the protocol, with the exceptions noted in this report due to the low concentrations
required.

3.2    Test Equipment

The Up-Flo™ Filter unit was placed in a specially designed (vendor-supplied) testing tank that
simulated a typical catch basin used in stormwater runoff conveyance systems. The testing rig
designed and constructed by PSH personnel controlled influent and effluent flow and constituent
feed rates. The rig  also provided for collection of influent and effluent liquid  samples for
laboratory analysis, and observation of performance conditions, such as bypass, in a simple and
effective manner.

Figure 3-1  shows the process flow diagram and equipment configuration for the test setup. City
water stored in a 1,700 gal holding tank served as the main water feed. Oil-based constituents
(OBC) (gasoline, diesel fuel, motor oil, and brake fluid) and water-soluble constituents (WSC)
(windshield washer fluid, antifreeze,  and surfactants) were stored in two-liter bottles and fed by
variable-speed peristaltic pumps into the inlet pipe  containing the water. The inlet pipe was a
12-in. PVC plastic pipe that received water from the feed tank and dispensed the water mixture
into the Up-Flo™ device. A dry feeder above the channel dispensed the solids mixture into the
water stream at controlled rates.
      Synthesized
      Contaminants
     Two (2) Tanks
Soil Dry Feeder
                                              Open Channel
<
L
Influent ^L
7 1
i T
Influent
Sampling Point
Clean
Water

Up-Flo™
Filter and
test catch
basin





( FE J Effluent
Effluent
X
Effluent Sampling
Point
Figure 3-1.  Test rig process flow diagram.
                                           16

-------
The  test site was the PSH  Environmental Engineering  Wastewater Research laboratory in
Middletown, Pennsylvania. The physical laboratory was set up to handle medium-range flow
testing and full-scale unit testing. The facility had space to set up several large tanks and piping
to convey the challenge wastewater to the full-scale test unit. The laboratory setup designed for
this verification activity could  supply up to 50  gpm of city  water as a main feed during  the
testing.  Ample electrical  service was available  to run  all pumps, controllers, samplers, and
associated equipment.

The Up-Flo™ Filter unit  used  for the verification test was that of a full  scale commercially
available one-module catch basin configuration which would be used in catch basin applications.
Influent to the unit was pumped into the  same elevation as the grate inlet (relative to the unit) so
that flow could move through the system by gravity and the driving head in a manner similar to a
field application.  Effluent from the unit flowed by siphon out of the side of the test unit in the
same manner that the flow would exit the unit in the field.

Figure 3-1 shows the process flow diagram and equipment configuration  for the test setup. City
water served as the main water feed with a maximum flow rate of up to 50 gpm.  A flow control
valve controlled the flow.   The flow rate of the  water was measured using a standard "paddle
wheel" style flow meter that showed flow rate (gpm) and totalized the volume processed (gal).

Synthetic challenge water was  made by adding pre-mixed and sized solids, with a specific
amount of a particulate phosphorus source (ground slow-release fertilizer) to the city water.  The
solids were mixed in the appropriate ratio using a cement mixer and stored in a bucket near the
test device. Periodic samples were collected from the solids dry-feeder (hopper) of the device to
ensure that the mixture had not separated during storage. The original intention was to add the
solids by slurry, but initial tests in the lab found that the sand could not be kept in suspension
even in a stirred sample bottle.  Therefore, the  hopper was used to feed the solids into the pipe
with sufficient mixing area available in the pipe between the solids-addition point and the entry
to the device. The sieve size analysis of the selected solids mix, as specified by a New Jersey
testing plan, is provided in Table 3-1,  and is displayed graphically in Figure 3-1.

Table 3-1.  Particle Size Distribution
Description
Coarse sand
Medium sand
Fine sand
Very fine sand
Silt
Fine Silt
Clay
Particle Size
Gun)
500-1,000
250-500
100-250
50-100
8-50
2-8
1-2
Sandy loam
(% by mass)
5
5
30
15
25
15
5
This distribution  can be approximated by mixing a pre-sieved concrete  plant sand with the
Sil-Co-Sil 250 to be purchased from U.S. Silica, Inc.  (or one  of its distributors). The mix  is
42.5% sand and 57.5% Sil-Co-Sil 250.
                                           17

-------
            100
                                             100
                                      Particle Size (jam)
1000
10000
Figure 3-2.  Sediment particle size distribution graph.

The original intention was to use Miracle-Gro™ topsoil as the source of particulate phosphorus
to generate the required additional phosphorus (above that supplied by the STPP in the organic
mixture). Testing at PSH on this topsoil showed that the phosphorus content measured as TP is
approximately 0.04 mg TP/g  Miracle-Gro™.  However, the  calculation of the solids  mixture
requirement was that  the topsoil did not have sufficient total phosphorus to be used (the sand
would have been eliminated from the mixture entirely). A search for a source of particulate
phosphorus resulted in the use of Scott's Starter Slow-Release Lawn Fertilizer. This fertilizer is
granular with a coating designed for slow release. The intact particles were too large to use in the
solids feed so the fertilizer was ground using a coffee grinder and the phosphorus concentration
measured. The testing showed the approximate TP  concentration of the Scott's Starter to be
0.3 mg TP/g fertilizer.

All sampling was performed manually for all test sequences. This eliminated the  concern
regarding the collection of representative solids when using automatic sampling equipment.

The synthetic challenge water entered the treatment unit through the open top of the device
grating, flowed  through the sump/sediment  collection section, and passed over/through  the
adsorbent materials. The treated water exited through the outlet pipe along the side of the unit.
Flow  rates were  measured both at the beginning and outlet of the system. A sampling port was
located in the effluent pipe for collection of manual grab samples. All sampling was performed
manually for all test sequences.
                                           18

-------
Attempts were made to use an automatic flow measuring device to confirm the readings from the
flow meter. However, the low flow levels in the effluent pipe that accompanied the unit made the
use of the meter impossible. In addition, the TO was concerned about  the trapping of solids
around the flow meter installation. To compensate for the lack of automatic flow readings in the
effluent pipe, manual  flow measurements (bucket  and  stopwatch) were  made  periodically
throughout the testing - typically  with  every sample collection or every  two hours, whichever
came first. Head  measurements in the tank were taken at every sample collection and flow
measurement time.

3.3    Test Phases - Hydraulic Loading

The unit was  tested under varying  hydraulic load conditions to simulate typical conditions found
in wash water applications  (i.e., catch basins and drain inlets in streets,  parking lots, etc., that
contain substantial dry-weather flows or truck-washing facilities) and during challenge water
flows. The primary operational characteristics tested included the following:

       •  Performance under intermittent flow conditions;
       •  Performance under different hydraulic loadings, including peak flow;
       •  Performance at different contaminant loadings; and
       •  Capacity of the unit to contain contaminants.

The  testing was done in four phases  that included conditions  designed to test  all of these
operating scenarios. The phases described below followed the same phases that are discussed in
the protocol.

3.3.1   Phase I — Performance under Intermittent Flow Conditions

In Phase  I  the system  was  operated intermittently to  simulate  actual  in-drain  treatment
applications during intermittent loadings at flow rates that are typical average flow rates over a
period of time. The Up-Flo™ Filter catch basin unit, with one to six  filter modules, is designed
to treat flow rates of up to approximately 20 gpm per filter module before any water is bypassed
through the  overflows. A more typical average flow rate at a catch basin or drain inlet is
expected to be in the 10-15 gpm range. A flow rate of approximately 11  gpm was used for the
Phase I four-to-five day test. The  intermittent tests were run for  a 40-hr period. During the ON
cycle, the unit received flow for 15 min, followed by a 15-min period with no flow.  The result
was  16  flow  periods during eight-hour  ON cycle (two 15 min flow periods  per hour for 8 hr).
The flow was constant during the  dosing periods  at a flow rate of approximately  11 gpm. Flow
rates were recorded throughout the ON-cycle  period and the effluent flow rate was recorded
periodically during the OFF cycle to determine drain down flows.

Samples of both the influent and  the effluent were collected by manual  grabs.   Samples were
only collected when flow is being sent  to the unit. Samples for both the  solids and phosphorus
analysis were collected manually with 500 mL of sample collected every 500  gal (approximately
once every 2 hr). Table 5-1 in the Sampling and Analysis Plan Section of the test plan provides a
summary of all sampling and analysis schedules for verification test.
                                           19

-------
Observations included  a physical description of the effluent water with  respect to color, oil
sheen,  etc.   The unit was observed for any evidence of clogging, change  in operating head or
head loss, flow patterns, or any evidence of bypass  or short-circuiting. These observations are
described in Chapter 4. The protocol called for the measurement of head loss  as part of the
monitoring of flow conditions in the unit.  The Up-Flo™ Filter unit, however,  is designed to
bypass any flow that does not pass through the absorption media.  Given that the unit is fed by
gravity, is open at the top, and has an overflow capacity greater than the inlet, it is  not possible to
measure  head  loss on the influent stream to the unit. An approximation of the depth of water
over the  filter media in the treatment  chamber was monitored by noting whether water was
bypassing the treatment media, and reported as an estimate of the head loss through the  media.
This head loss, however, would only impact the capacity of the unit to treat water  and would not
impact the  concern regarding flooded conditions. Water depth measurements, therefore, were
recorded  whenever samples and/or flow rates were measured.

The  unit has a relatively large capacity  (approximately 40  ft3) for holding sediment  (settled
solids). The challenge water had a target sediment concentration of approximately 300 mg/L.
Assuming 100% removal from a flow of 12,000 gal and a 90 lb/ft3 bulk  density, the retained
sediment would occupy 0.2 ft3.  Therefore, sediment cleanout was not anticipated until  the
Phase I test was completed. At the end of the Phase I period, the unit was inspected to determine
the condition of the sediment chamber and the absorbents. Observation of an increase in water
depth in  the test tank during the test run would indicate whether the media was beginning to
blind or plug.  If the media and sediment chamber were in good operating  condition, the media
would be used for the capacity study. If the sediment chamber appeared to be filling quicker than
expected or the media was beginning to plug as indicated by  water draining through the bypass
holes during the low-flow testing, the unit would be cleaned and the media pack will be replaced
as described in the O&M Manual.

3.3.2  Phase II - Determination of the Capacity of the Unit

The  objective  of the Phase II  testing was to  run the unit to "exhaustion" with  respect to the
capacity  of the absorbent material to remove  suspended  solids and/or phosphorus. During this
phase of testing, the unit was operated under continuous flow conditions for 12 hr/day until the
unit plugged with solids or the absorption capacity was exceeded. This was not a continuous test
sequence since it would be highly unusual for an in-drain unit to flow at  near maximum flow
continuously until exhaustion occurred.  Therefore, operating on a 12-hr basis was selected since
it would most resemble real-world conditions.

The test plan allowed for using the loadings from the Phase I test to contribute to the loadings in
Phase II.  The total loading from Phase  I would then be added to Phase II data to calculate total
capacity.  The flow rate for this test was  set at approximately 16 gpm, which is  approximately
80% of the maximum rated flow capacity of 20 gpm.

If the unit capacity had not been exceeded in the first 12 hr run (about 11,500 gal of water), the
test plan  called for the unit to be operated for  a  second 12 hr period or until the solids capacity
was reached. If after the second 12-hr  period indicates exhaustion has not been  achieved, then
                                           20

-------
the unit would be started again and would continue to be dosed on a 12 hr run schedule until the
maximum absorption capacity was reached.

Samples were collected on a grab sample  basis.  Samples from the influent and effluent were
collected at the start of the test and after approximately each  10,000 gal of influent flow, and
analyzed for  the primary constituents (TSS, SSC, TP). Samples were  collected on  the  same
schedule until the capacity was achieved.

Flow rates were monitored  throughout the  test period on a minimum of a once per hour basis.
The water depth over the filter media was monitored and recorded. Increasing water elevation in
the test tank was an indication that plugging was  occurring. At the end of the Phase II test, the
unit was cleaned and the media pack was replaced  as described in the vendor's O&M Manual.

3.3.3  Phase III - Performance Under Varied Hydraulic and Concentration Conditions

This phase of testing focused on determining the unit's  hydraulic capacity  and how well  it
handled spike loads of constituents. Phase III had three distinct parts.

3.3.3.1 Part 1: Hydraulic Capacity with Clean Water

The vendor stated that one filter module has a rated capacity of 20 gpm for treating water. Flows
above 20 gpm would be bypassed through the bypass openings in the top of the unit. In order to
confirm the rated treatment capacity the unit was challenged  with increasing flow rates using
clean water in the Part I test.

The test started with a clean unit containing fresh  media. Only  the clean water line was used for
this test. The drain-down ports on the base of the outlet module were plugged prior to  testing.
Flow started  at 10 gpm of fresh  water for a period  of 15 min.  After  15  min, the flow was
increased to  15 gpm for a period  of 15 min. Flow continued  to be increased by an additional
5 gpm (20 gpm, 25  gpm, 30 gpm,  etc.) in 15-min increments  until  flow began through the
bypass. The maximum flow rate achieved, before  bypass and after bypass occurs, was recorded.
Flow increases continued until the maximum available fresh water rate was reached. All flow
rates and operating observations were recorded.

Observations  of the water elevation at various flows were made so that estimates of media head
loss can be made. The overflow was monitored and water height at various bypass flow rates was
recorded.

3.3.3.2 Part 2: Hydraulic Throughput with Synthetic Challenge Water

The  Part 2 testing  followed the same approach as the Part 1  testing except that the synthetic
challenge water was used as the influent water. In  this part, the  chemical feed pumps and hopper
were used to  add the stock solutions  to the fresh water. At each increase in flow rate, the pumps
and  feeder were increased in rate  in ratio to the fresh  water feed to maintain a constant
concentration of constituents in the synthetic challenge water.
                                          21

-------
The test was conducted after the Part 1 test and used the same filter media that was used for the
Part 1 test.  Flow started at 10 gpm for a period of 15 min. After 15 min, the flow was increased
to 15  gpm for a period of 15 min. Flow continued to be increased by  an  additional  5  gpm
(20 gpm, 25 gpm, 30 gpm, etc.) in 15-min increments until flow began through the bypass holes.
The maximum flow rate achieved before bypass and after bypass begins was recorded in the
logbook. After  achieving the maximum treated rate,  the flow continued to be increased to
challenge the bypass system.  All flow rates and operating observations were  recorded in the
logbook along with any physical observations regarding the unit response during the test.

Grab samples of the influent and effluent were collected at each flow rate condition. All samples
will be analyzed for the complete list of constituents (solids and phosphorus).

3.3.3.3 Part 3: Impacts of Spike Concentration Loadings

Part 3 was a test series designed to evaluate the impact that spike loadings may have on the unit's
ability to remove key constituents. The key constituents for the Up-Flo™ Filter are TSS, SSC,
PSD, and TP. The hydraulic loadings were increased following the same protocol as for Part 2.

Using the same unit (no cleanout or media pack) as for Part 2, the test procedure started at a flow
rate of approximately 10 gpm. The chemical feed pump rates of the stock  solutions and dry
feeder were set at a factor of four times higher than used in the previous tests.  This increased the
concentration of constituents approximately by a  factor of four. Grab samples of the influent and
effluent were collected  at  each  flow  rate condition until  the unit flooded  or the maximum
available feed water capacity was reached. All samples will be analyzed for  all constituents of
interest. At the end of the Phase  III tests, the unit was  cleaned and the media pack replaced as
described in the vendor's O&M Manual.

3.3.4   Phase IV — Contaminant Capacities at High Hydraulic Throughput

The influence on treatment efficiency  of  high hydraulic loads  on the unit were  tested in
Phase IV. The Phase IV test was a capacity or "exhaustion test" similar to Phase  II, except the
unit will be under higher hydraulic loads  typical of a very large flow event. The Up-Flo™ Filter
unit was somewhat unique  in that it treats all of the water that can pass through  the treatment
chambers and then bypass the remaining water. Thus, at higher flows (above treatment  capacity)
it will not backup  and flood  an area around  the inlet, but rather will  treat  a set flow,  about
20 gpm/ft2 of filter media, and the additional flow will be bypassed to the catch basin outlet and
enter the collection system.  Under this high flow rate test, the unit  was operated above the rated
treatment capacity with the bypass flowing and removing the extra flow. The flow rate was set at
approximately 32 gpm, which is  above the treatment  capacity. The test  was  designed to
demonstrate the system's treatment capability when it is operating in bypass mode. The test time
period was 12 hr continuous flow per 24-hr day. However, the unit  did not end up in bypass. The
results are described later in  the verification report.

Observation of the  flow rates through the treatment unit and the bypass were to be used as the
primary indicator that solids capacity has been reached.  When flow rates in the treatment section
decreased by 25% or more for  30 minutes,  capacity  was considered  to have been reached.
                                          22

-------
Samples were collected on a grab sample basis. Samples from the influent and effluent were
collected at the  start  of the test. It was anticipated that the flows would  be sampled every
10,000 gal of water treated and analyzed for the primary constituents. However, given the nature
of the breakthrough pattern and timing seen in Phase II testing, it was determined that higher
resolution sampling was required.  Samples were collected every 30 min for the first 2 hr of
testing and then once per hour after that. Flow rates were monitored throughout the test period on
a minimum of a once per hour basis.

3.4    Influent Characterization

3.4.1   Synthetic Challenge Water

The verification test will be performed using synthetic water (Table 3-2) made from a mixture of
solids - one  of which will provide the particulate phosphorus required  by  the test plan.  The
following products will be used to make the synthetic challenge water:

   •   Regular unleaded gasoline;
   •   Diesel fuel;
   •   10W-30 motor oil;
   •   Brake fluid;
   •   Antifreeze (glycol based);
   •   Vehicle washing detergent (specific chemical addition - see below);
   •   Windshield washer fluid;
   •   Sil-Co-Sil 250;
   •   Slow release phosphorus-supplying fertilizer; and
   •   Concrete plant sand sieved to a size of all passing through 5,000 jim.

Table 3-2.  Revised Synthetic Challenge Water Concentrations


                                                     Concentration
                  	Parameter	(mg/L)
                   SSC                                     300
                   TSS                                     300
                   Total phosphorous (as P)                  5-10
                   COD                                  100-200
A formula using a mix of the above named products/materials has been made and tested in the
laboratory to determine the conformance to these  specifications.  The synthetic mix that was
prepared and tested  is shown in Table 3-3. The  results of testing  the ground fertilizer for
phosphorus content is 0.3 mg TP/g Scott's  Lawn  Starter Fertilizer. The addition of fertilizer
replaced approximately 10% of the sand in the mixture.
                                           23

-------
Table 3-3. Synthetic Challenge Water Mix Concentrations
 Product or Material
Concentration in Water (mg/L)
 Regular unleaded gasoline
 Truck diesel fuel
 10W-30 motor oil
 Brake fluid
 Antifreeze (glycol based)
 Dodecylbenzenesulfonic acid (LAS)
 Sodium tripolyphosphate (STPP)
 Windshield washer fluid
 Solids Mixture
             0.08
              3.9
              19
             0.97
              10
              10
              2
              10
              300
The product concentrations in Table 3-3 represent a deviation in the constituent concentrations
identified in the original protocol.  The hydrocarbon concentrations specified in the protocol
were not achievable in prior testing due to the insolubility of hydrocarbons with water. For this
test plan, the VO agreed that the hydrocarbon concentrations could be decreased further (to a
targeted  concentration range  of 10 to 20 mg/L) since the vendor makes no specific claims for
hydrocarbon treatment.  Since the  vendor did request an evaluation of particulate phosphorus
removal,  a  slow-release  fertilizer  was  used  to  increase phosphorus  concentrations to
approximately 5-10  mg/L (when  combined with the STPP required by the VO).  The VO, TO,
and vendor agreed that the materials that comprise the synthetic challenge water should provide a
condition suitable to  adequately verify the performance of the Up-Flo™ Filter against  the
protocol  requirements. This mixture was designed to represent a mixture of stormwater runoff
and a dry-weather flow/washwater  that contains a  substantially higher load of detergents and un-
emulsified hydrocarbons than is typically seen in urban runoff. The use of this mixture at the
higher loadings shortened the  testing time required  for the Up-Flo™ compared to using a
simulated solids  mixture and increased the blinding of the media by the OBC and WSC
constituents. The concerns raised by this mixture would be likely to be seen in applications with
heavy influences of detergents and/or locations with visible free-floating hydrocarbon products.

3.4.2   Stock Solutions

The standard mix determined above (Table 3-3) was used for all of the verification  tests.  The
Sil-Co-Sil,  fertilizer, and sand was supplied by the hopper and set to meet the concentration
targets in the  established mix. The solids were  premixed prior  to  filling the hopper to
homogenize the solids feed. The hopper had to be  refilled frequently to ensure that the solids did
not separate during the test. In addition, the humidity in the laboratory testing required regular
maintenance on the hopper to  prevent solids "cementing" in the influent line.

The remaining products  were mixed into two separate solutions.   One solution  included  the
hydrocarbon-based products (gasoline, diesel fuel, motor oil, and brake  fluid), while the other
solution  included the  water-soluble products (antifreeze, LAS, STPP, and windshield washer
fluid).  The two solutions were prepared using the following specifications:
                                           24

-------
   •   Hydrocarbon mixture (fed into the water at a rate of 0.03 mL per L of water):
          o   10 grams (g) motor oil
          o   2 g diesel fuel
          o   0.05 g gasoline
          o   0.5 g brake fluid

   •   Water-soluble mixture (fed into the water at a rate of 0.1 mL per L of water):
          o   10 g windshield washer fluid
          o   10 g antifreeze
          o   10 g LAS
          o   2 g STPP
          o   Mixture diluted to 100 mL with tap water

3.4.3   Influent Characterization during the Verification Testing

The influent synthetic challenge water was sampled and analyzed during all  of the various test
conditions described in Phases I - IV. While the protocol allowed for single daily samples of the
influent in several test cases, the approach used in the test plan was to match influent and effluent
samples as often as  possible for all sampling periods. This was to ensure that the actual influent
concentrations would be known for all test conditions.

Because of the large water volumes needed for these tests, it was not practical to make a single
large daily batch of synthetic  water to supply the entire  day's flow.   Instead,  the system used
more  concentrated  stock solutions  that  were  injected into the fresh water flow in the open
channel section.

3.4.4   Solids Characterization during the Verification Testing

Influent and effluent solids were characterized using the Coulter Counter Particle Size Analyzer
for particles in the range of 0.6 |j,m up to 240 |j,m.  Particles above 250 |j,m were characterized by
sieving the samples  through a stainless steel sieve  with a mesh size of 250 |j,m. The combination
of the Coulter Counter results  and the sieve analysis for the  large particles allowed for  a
complete characterization of the influent and effluent particle distribution between 0.6 |j,m and
5,000 |j,m. The results for the solids analysis  were subdivided into removal for the following
particle size ranges:

   •   0.6 - 3 |j,m
   •   3 - 12 urn
   •   12-30 urn
   •   30-60 urn
   •   60 - 120
   •   120 - 240
   •   > 240
                                           25

-------
3.5    Effluent Characterization

The effluent quality was monitored during all phases of testing except during the fresh water
hydraulic test in Phase III, Part 1.  The sampling and analysis approach focused frequent sample
collection and analysis on the key parameters for evaluating the UpFlo™ Filter unit as described
previously.  Specific  details  on the sampling and  analysis  frequency  and parameter list are
provided in the SAP section of the test plan and in the previous sections describing the test
phases.

3.6    Residue Management

Residues, including sediment in the settling chamber and the  absorbent media, were removed
from the unit  at the end of some Phases of testing as described in Section 4.3. This task included
recording  the volume  of residues/media  collected and the wet  weight of  residues/media
collected. These data were used to provide information on typical cleanout volume and weights
that can be expected from normal operation.

Solid residues were collected from the sedimentation chamber in the unit after the majority of the
water in the unit had been removed using a sump  pump. The  sediment was  removed using a
vacuum system (wet/dry shop vacuum) to simulate the typical removal system used in the field
(vacuum truck). The content  of the shop vacuum reservoir was removed using scoops, spatulas,
scrapers, etc. to remove as much material as possible. These solids were measured for wet weight
and volume in order to evaluate the amount of solids that can be  expected to be generated and
cleaned out of the unit on a  volume throughput/loading basis.  Samples of the solids were also
measured for solids content  so that a  dry weight of solids produced could also be calculated.
Three sub samples of the sediment were collected and percent solids measured. The weight of
solids collected was used to relate the accumulation rate of solids to total water treated.

One representative sample of the spent filter media and retained sediments was  analyzed for
COD  and TP and for leachate  testing  following the TCLP procedure. Attempts were made to
weigh the filters and obtain masses of residue gathered on the media. However, because of the
differences  in weights due to  moisture content between the new bags (which were not completely
dry) and the used bags, this measurement could not be taken accurately.

3.7    Operation and Maintenance Observations

The Up-Flo™ Filter unit was operated by PSH during the test period. The vendor-supplied O&M
Manual is  presented in Appendix B.  Hydro International will also provide consultation on
installation  and operation of the unit.

Installation of the unit was straight forward as the unit arrived at the PSH lab  pre-assembled.
Support brackets with legs sit on the base of the test tank. The filter modules were secured onto
the support brackets.  The outlet module had a  pipe  stub that fits up to the tank outlet via
standard Fernco® coupling. The test tank had an open top.
                                          26

-------
Laboratory personnel maintained a detailed logbook describing all observations made during the
tests.  Any unit  cleaning, clearing of debris,  unclogging of the screens or media, etc. were
recorded.  Observations  were  also  recorded  on  the  ease  of installation,  operation, and
maintenance. These observations included a qualitative assessment of the degree  of difficulty
encountered during the cleaning of the unit at the end of each phase and on the ease of replacing
the media pack.

Flow  rates, volume of water processed,  amount of stock solutions pumped from the stock feed
tanks, and related  operational data for each test run were  recorded in the operational log. Any
deviations or changes  from  the prescribed test  plan  were  thoroughly documented. The
measurements of residue volumes and weights were recorded after cleaning periods.

Any other observations on the operating condition of the unit or the test system as a whole were
recorded  for  future  reference.  Observations of changes  in  effluent  quality based  visual
observations, such as color change, oil sheen, obvious sediment load, etc., were recorded for use
during the verification report preparation.
                                           27

-------
                                       Chapter 4
                    Verification Testing Results and Discussion

4.1    Synthetic Wastewater Composition

The protocol and test plan set forth a requirement that the TO maintain constituent feed rates in
the synthetic wastewater of ±50 percent of the target feed during the course of testing so that the
system would be properly challenged. Prior to beginning the testing, the TO created calibration
curves for each pump (water, OBC, WSC) using the appropriate feed mixture. Then the flow
rates were set based on the calibration curves. The flow meter calibrations are shown in Figures
4-1, 4-2 and 4-3 for the feed water, WSC and  OBC, respectively.
                        M -
                        2D •
                                    Water Flow Meter Calibration
                           Mnlrr Rising {GPM} = 0 fiSlAcjiial Flow Bain) - 4 9H?
                           Ft' - 0JW
                                               ,-*
                          n        10       711       in       40
                                       Actual Flow Rate I (3PM;

Figure 4-1. Calibration of the flow meter for the feed water.
                                                             i- 6.0
                                 Hydrocarbon Peristallsc Pump CaliSMIion
                              y Rail i;inL''s; = o.i2:Puirp Srt-rg: * 0 OT
                        0.6 -
                                           Pump
Figure 4-2. Calibration of the hydrocarbon feed peristaltic pump.
                                            28

-------
                         Water-Soluble Constituents Peristaltic Pump Calibration
                      0,2 •
                                         Pump Setting'

Figure 4-3. Calibration of the WSC peristaltic pump.

Based on the  calibration equations,  the desired flow readings for the water and the peristaltic
pump settings were selected for each flow rate-concentration combination. The following tables
for settings were established (Tables 4-1 and 4-2). These were then corresponded to settings on
the hopper and the peristaltic pumps.

Table 4-1. Desired  Feed Rates at  "Normal" Settings (matching the concentrations in the
original challenge solution)
Water Flow Rate
(gpm)
10
15
20
25
30
35
40
45
50
Solids Feed Rate
(mg/sec)
189
284
379
473
570
662
757
852
947
OBC Feed Rate
(mL/sec)
0.019
0.028
0.038
0.047
0.057
0.066
0.076
0.085
0.095
WSC Feed Rate
(mL/sec)
0.063
0.095
0.13
0.16
0.19
0.22
0.25
0.28
0.32
                                            29

-------
Table 4-2.  Desired Feed Rates at "4X Concentration" Settings.

  Water Flow Rate       Solids Feed Rate       OBC Feed Rate       WSC Feed Rate
       (gpm)	(mg/sec)	(mL/sec)	(mL/sec)
10
15
20
25
30
35
40
45
757
1,140
1,510
1,890
2,270
2,650
3,030
3,410
0.076
0.114
0.151
0.189
0.227
0.265
0.303
0.341
0.252
0.379
0.505
0.631
0.757
0.883
1.01
1.14
Generally, the OBC and WSC  feed rate was  higher than targeted because of the inherent
difficulties posed by the low flows required of the testing. Two different sizes of pump tubing
were tried for each measure to better accurately target the desired flow rate range. However, the
desired range, especially for the OBC mixture, fell between the two pump tube sizes. The WSC
settings were in  range but all at the lowest end of the range. For both OBC  and  WSC, it was
decided to proceed with the larger tubing, based on the belief that over-challenging  the filter was
better than under-challenging  it. Part of the desire of the protocol is to evaluate the impact that
hydrocarbons and other constituents of washwater (similar to that found in service station and
maintenance yard drains) have on blinding of the filter media.  Therefore, the use of the larger
tubing was warranted in order to not undercut the concentration of the two "fouling" agents.

Two general problems were encountered with the dosing of the solids. The humidity generated in
the laboratory due  to the water flow created a clogging problem  in  the solids hopper and
removed the option of using the lowest motor settings. The calibration of the hopper therefore
was inconsistent  and had to be maintained regularly. Physical measurements of the hopper solids
being dispensed  into the water stream indicated that when the hopper was fully functional, the
dispensing was in the desired range. However, the partial clogging was an issue throughout the
tests. The second general problem was encountered in all sample collection procedures where the
solids mixture contains comparatively large particles and is the question of where to sample in
the influent flow stream. For this device, based on initial observations of the  flow, the influent
was sampled in the stream as the stream "united" entering the device. However, the solids results
showed that, although they were not observed un-entrained in the system, the sand particles were
falling out of the inlet pipe and were not evenly dispersed in the influent.  At the end of the
Phase III testing, the sampling location was moved up  to the edge of the influent dispensing pipe
and near the center bottom of the flow stream.  This also has been documented to cause errors of
measurement, with a potential bias toward higher solids measurements than actually occurring.
This is because the sample is collected along the center flow path which is deemed to be where
the larger particles  flow. The testing rig,  in agreement with  prior testing  performed under a
different verification protocol with a different device, is not equipped to provide adequate mixing
of large solids into the water column. The addition of baffles or mixers was considered but was
rejected because  of the concerns of forming a solids settling location, ensuring that the solids did
not end up in the Up-Flo™ Filter.


                                           30

-------
 4.2     Synthetic Wastewater Laboratory Analytical Results

 During testing, 60 influent samples were collected during the normal constituent feed conditions
 (Phase I, Phase II, Phase III Part 2, Phase IV) and analyzed for the various constituents specified
 in the test plan. Table 4-3  provides a comparison of the mean analytical results for these influent
 samples versus the analytical results for the synthetic wastewater mix specified in the test plan.

 Table  4-3.   Synthetic Wastewater Analytical Data Comparison Test Plan Concentration
 Mean Testing
                               Measured Mean                    Desired Feed
	Constituent	Concentration (mg/L)	Concentration (mg/L)	
         TSS                        132                              300
         SSC                        130                              300
          TP                          44                             5 -10
	COD	121	70-100	

 The mean synthetic wastewater data for the primary constituents were measured to be greater
 than desired for TP, and less than desired for TSS and SSC. They were within the ±50% of the
 desired concentration for COD. This supports the observations that the test mixture was difficult
 to dose correctly  in a humid  environment and when very little of the OBC and WSC were
 required. The decision was made by the TO to supply a concentration of the OBC and WSC that
 could be regulated correctly  by the pumps.  This meant that  the  flow rate was set  for
 approximately 20  drops per minute at the lower flow rates of testing - not a steady stream,  but
 sufficient to provide a measurable concentration.  A review of the data shows that the  COVs for
 all parameters ranged between 0.5 and 1.0. In  addition,  as discussed earlier in the report,
 collecting of samples in the "correct location" in the influent stream caused difficulties. A review
 of the data by phases showed that the influent concentration of TSS and SSC  for Phase II (the
 last phase run) was over 230 mg/L and was within the ±50 percent guideline of the test plan.

 The hopper dosage measurements were within the guideline for the test plan. Therefore, although
 the mean analytical TSS and SSC concentrations were lower than  the 300 mg/L concentration
 specified  in the test plan, the hopper  dose measurements suggest that the theoretical test plan
 concentration was close to the  300 mg/L goal.   This also suggests that the analytical samples
 were biased toward underreporting  the actual solids concentration.  On the basis of the hopper
 dosage measurements, the overall objective for sediment loading was met.

 The  variances between the  test  plan  and mean  testing concentrations for the secondary
 parameters exceeded the ±50% guideline for most parameters, but the  vendor makes  no claims
 for the secondary parameters. Therefore, the variation  from the targeted concentrations is
 deemed to have no impact on meeting the testing objectives. However, the potential effects of
 the increased secondary parameter concentrations on the sediment removal performance is  not
 known.

-------
4.3    Test Phases in the Test Plan

This section summarizes the analytical and flow data for the test phases specified in the test plan
(Phases I through IV). The efficiency values reported in this section are a function of the total
influent and total  effluent  concentrations and do not take into  account  the  effects of water
bypassing the filter media.

4.3.1   Phase I - Performance under Intermittent Flow Conditions

As described in Section 3.5.1, the Phase I test took place over 40 hr, 8 hr per test day on days 1
and 4 and 12 hr per test day on days 2 and 3, with the flow alternating on and off for 15-min time
periods. The influent flow rate was set at 12 gpm throughout the test.

4.3.1.1 Analytical Data

The effect of blinding or clogging of filter media should be evident in the results comparing flow
rate through the  media to the effluent concentrations.  The TSS,  SSC, TP and  COD analytical
data as related to cumulative volumetric loading on the media are summarized in Table 4-4. The
test plan required that a minimum  of one  set of samples be collected  each test day.  The
verification organization  collected a  total of 26 sets of samples.  The increase was to verify
whether filter media breakthough was occurring.  Three sets of these samples encountered very
low or non-detectable sediment concentrations due to the issues outlined in Section 4.1.  For the
purposes of verification,  these three  sample sets were considered testing anomalies and were
removed from statistical evaluations.  These data  are  reported in the data  set enclosed in
Appendix C.

Removal efficiencies for TSS and SSC ranged from 73% to 77%, depending on the analyte and
the statistical  evaluation, which is slightly below the vendor's 80% performance claim. The VO
observed dark particles in the effluent at  the beginning of the test phase.  These dark particles
were likely the result of washing of fine sediments in the media bags.  Large negative removal
efficiencies were observed, primarily  at the beginning of the test phase, which is likely the result
of media bags washing out fine particles or bridging in the test rig's sediment dispenser, resulting
in  low or non-detectable influent sediment concentrations.  The  TP data showed a mean  and
median removal efficiency of 13%. The COD analytical data  showed a  mean  and  median
removal efficiency of 62% and 53%, respectively.

Table 4-4.  Phase I Analytical Data Summary

           Influent Concentration       Effluent Concentration
                   (mg/L)                     (mg/L)             Removal Efficiency (%)*
Analyte  Mean Median   Max   Min   Mean  Median Max   Min   Mean  Median  Max  Min
TSS
SSC
TP
COD
123
132
40
168
107
125
40
139
435
480
126
523
5
5
0.6
77
32
34
35
63
29
29
35
65
83
106
64
89
9
5
0.6
33
74
74
13
62
73
77
13
53
92 -1280
99 -480
91 -533
88 5.1
                                           32

-------
1. Mean and median removal efficiency is a function of mean and median influent and effluent concentrations, and
  maximum and minimum removal efficiencies are a function of individual paired data points.
A graphical examination of the data was also conducted to illustrate the results discussed above.
Figures 4-1, 4-2, 4-3, and 4-4 compare the influent and effluent concentrations for TSS, SSC,
TP, and COD, respectively.
                           Total Suspended Solids -  Phase I
          500
          400 -
          300 -
       CO
       CO
          200 -
          100 -
                                                              —•—  Influent
                                                              —-O—  Effluent
              0      2000     4000     6000     8000     10000    12000
                             Cumulative Volumetric Loading (gal)

Figure 4-1.  Phase I TSS influent and effluent results.
14000
The Up-Flo™ Filter did not exhibit signs of clogging or blinding during the test run.  A review
of the water depth measurements at each sample time showed that the tank water level remained
consistent between 40 and 42 in. No buildup of head was noted in the unit, further indicating that
the media capacity had not been exhausted in the Phase I testing.

Particle size distribution analysis was also performed on representative influent samples and on
all the effluent samples. Since Phase I was  not the chronologically  first phase performed,  many
influent  samples had been analyzed prior to this and it  was determined  that  the  influent
distribution  was relatively consistent. Figure  4-5 shows the results  of the PSD  analysis for
Phase I.

Figure 4-5 shows that the influent sample had the largest d50, indicating a reduction  in the media
particle  size in  the solution  as  it  passed through the Up-Flo™ Filter.  This confirms the
predictions of the manufacturer that the Up-Flo™ Filter would be capable of removing the larger
particles in the solution. The data show the mean  influent dso was 57 um and the mean effluent
d50 was 24 um.
                                           33

-------
         500
                   Suspended Sediment Concentration - Phase I
         400 -
         300 -
       E,
       o
         200
         100 -
                                                          —•— Influent
                                                          — O—  Effluent
             0      2000     4000     6000     8000     10000    12000    14000
                           Cumulative Volumetric Loading (gal)

Figure 4-2. Phase I SSC influent and effluent results.

                            Total Phosphorus - Phase I
         140
         120 -
         100 -
      en
      E
          80 -
          60 -
          40 -
          20 -
                                                                Influent
                                                          —-O— Effluent
            0      2000     4000     6000     8000    10000    12000
                          Cumulative Volumetric Loading (gal)

Figure 4-3. Phase I total phosphorus influent and effluent results.
14000
                                        34

-------
         600
                        Chemical Oxygen Demand - Phase I
         500 -
         400 -
       O)


       Q
       O
       O
300 -
         200 -
         100 -
              —•— Influent
              —-O—  Effluent
                                                              _O.-O--OO
             0      2000    4000     6000     8000    10000    12000    14000
                           Cumulative Volumetric Loading (gal)

Figure 4-4. Phase I COD influent and effluent results.

                         Phase I  Influent & Effluent
     100
          —•——  Influent
          —-o—  Effluent
          	  Dry solids mix
     80 -
                           10                 100
                                Diameter (Mm)

Figure 4-5. Phase I particle size distribution summary.
                                                        1000
                                         35

-------
4.3.2   Phase II - Determination of the Capacity of the Unit

As described in Section 3.5.2, in Phase II the system was run to "exhaustion" with respect to the
capacity of the filter media to remove suspended solids or petroleum hydrocarbons. The unit was
operated  under continuous flow conditions at a  constant flow rate  of 15 gpm until the unit
plugged with solids or the contaminant absorption capacity was exceeded. The test plan specified
a flow rate of 16 gpm for this test, based on the vendor's claims that the system could treat water
at a maximum flow rate of approximately 20 gpm.

4.3.2.1 Analytical Data

As specified in the test plan, samples were collected approximately every 10,000 gal  and the
system was run until breakthrough was  noted. Breakthrough was noted by the failure of the
media bags to remain in place  in the system.  The data are summarized in Table 4-5  and are
expressed graphically in Figures 4-6 through 4-9.

Table 4-5. Phase II Analytical Summary
          Influent Concentration
              Results (mg/L)
       Mean  Median  Max.  Min.
   Effluent Concentration
       Results (mg/L)
Mean  Median  Max.  Min.
   Removal Efficiency ("/o)1
Mean  Median   Max.  Min.
TSS
ssc
TP
COD
215
237
89
82
164
171
75
67
492
555
183
134
84
96
47
60
60
71
56
60
50
64
50
62
100
108
81
80
30
<5
30
43
72
70
36
27
70
63
33
7.5
82
81
59
53
40
47
7.1
-3.3
1. Mean and median removal efficiency is a function of mean and median influent and effluent concentrations, and
  maximum and minimum removal efficiencies are a function of individual paired data points.
                                           36

-------
                             Phase II - Total Suspended Solids
             600
             500
             400 -
             300 -
           CO
           05
             200 -
              100 -
                  —•—  Influent
                  --O-  Effluent
                 0       10000     20000     30000      40000     50000

                          Cumulative Volumetric Loading in Phase II (gal)

Figure 4-6. Phase II TSS influent and effluent results.

                      Phase II - Suspended Sediment Concentration
  60000
            600
            500
            400 -
                  -*— Influent
                  • -O-  Effluent
            300 -
         o
         GO
         oj
            200 J
            100 -
                        10000     20000     30000     40000     50000

                         Cumulative Volumetric Loading in Phase II (gal)
60000
Figure 4-7. Phase II SSC influent and effluent results.
                                          37

-------
                                Phase II - Total Phosphorus
200



180 -



160 -


140
           O. 100
           I-

              80 H


              60


              40 -\


              20
                  — -o—
Influent
Effluent
                 0       10000     20000     30000     40000     50000

                          Cumulative Volumetric Loading in Phase II (gal)


Figure 4-8. Phase II total phosphorus influent and effluent results.


                          Phase II - Chemical Oxygen Demand
                                                60000
            140
            120 -
            100 -
         Q
         O
         O
             60
             40 -
             20
                 —•— Influent
                 - O— Effluent
                0       10000     20000     30000     40000     50000


                         Cumulative Volumetric Loading in Phase II (gal)



Figure 4-9. Phase II COD influent and effluent results.
                                              60000
                                          38

-------
In general, the Up-Flo™ Filter was 40% to 82% effective in removing TSS and 47% to 81%
efficient in removing SSC from the influent. The TSS and SSC removal efficiencies actually
increased over the life of the test. The TP removal efficiencies ranged from 7% to 60% and the
COD removals ranged from <0% to 53%, with COD removal efficiencies increasing across the
test.

PSD analysis was also performed on the Phase II samples, as shown in Figure 4-10. The mean
d50 for the influent was 60 um and the mean effluent d50 was 26 um.
           100
                               Phase II Influent & Effluent
                       Influent
                       Effluent
                       Dry solids mi>:
                                  10                 100
                                      Diameter
1000
Figure 4-10. Phase II PSD summary.

The Phase II test was stopped when the TO noticed that the Up-Flo™ filter bags had been moved
out of place and that substantial solids were appearing the effluent samples compared to previous
samples. The mesh retaining the filter bags below the cartridge lid was displaced, allowing water
to bypass  the filter bags. This breakthrough was noted prior to  the water level reaching the
designed bypass level.

Because the media bags were  not changed between Phases I and II, a full evaluation of the
Up-Flo™ Filter requires an evaluation of performance across the entire testing sequence on these
bags. Figures 4-11 through 4-14 summarize  the media bag behavior across the entire range of
testing for TSS, SSC, TP and COD, respectively. Figure 4-15 summarizes the PSD analysis for
Phase I and Phase II combined. The mean dso for the influent was 59 um and the mean effluent
dso was 24 um.
                                          39

-------
          600
          500 -
          400 -
                         Phase l+ll - Total Suspended Solids
        O)
        E,

        to
        CO
300 -
                                                                  Influent
                                                           — O—  Effluent
          200 -
          100 -
                     10000    20000    30000    40000    50000    60000    70000

                            Cumulative Volumetric Loading (gal)

Figure 4-11. Phase I and II TSS cumulative loading results.

                    Phase l+ll - Suspended Sediment Concentration
          600
          500 -
          400 -
        O)


        O
        CO
        co
300 -
          200 -
           100 -
            0
                                                    —•— Influent
                                                    —-O— Effluent
                                Q = 15gpm
                                                                   .-O
              0      10000    20000    30000    40000    50000    60000    70000

                            Cumulative Volumetric Loading (gal)

Figure 4-12. Phase I and II SSC cumulative loading results.
                                         40

-------
          200
                            Phase l+ll -Total Phosphorus
                Q = 10gpm
          150 -
        0.
                                                    —•— Influent
                                                    —-O— Effluent
                        Q = 15gpm
              0     10000    20000    30000    40000    50000    60000    70000
                            Cumulative Volumetric Loading (gal)
Figure 4-13. Phase I and II total phosphorus cumulative loading results.
                        Phase l+ll - Chemical Oxygen Demand
          600
          500 -
          400 -
        O)
        E,
        Q
        O
        O
300 -
          200 -
          100
              0     10000    20000    30000    40000    50000   60000    70000
                            Cumulative Volumetric Loading (gal)
Figure 4-14. Phase I and II COD cumulative loading results.
                                        41

-------
                               Phase l+ll Influent & Effluent
          100
                 —•	 Influent
                 •-o—  Effluent
                 ^—^— Dry solids mix
           80 -
                                   10                   100                 1000
                                       Diameter (pm)

Figure 4-15. Phase I and II PSD summary.
4.3.3   Phase III - Performance under Varied Hydraulic and Concentration Conditions

As described in Section 3.5.3, Phase III testing focused on determining the unit's hydraulic flow
capacity and how well it handles spike loads of constituents. Phase III had three distinct parts:

   •   Part  1: Hydraulic capacity with clean water;
   •   Part 2: Hydraulic capacity with synthetic wastewater (regular constituent feed
       concentrations);
   •   Part 3: Hydraulic capacity with spiked constituents (four times constituent feed
       concentrations).

The Phase III tests were performed first because the information gathered in Phase III would
help set the flow rates in Phases II and IV.

4.3.3.1 Flow Data
In Phase III Part 1, clean water was used to determine the maximum hydraulic capacity of the
system before water bypassed  the unit and whether drain backup would occur, resulting in
potential flooding  of the catch basin. The test started at  10  gpm and ran for a minimum of
15 minutes. The flow rate was then increased at 5 gpm increments, and the test was rerun until
bypass occurred. Test Phases III Part 2 and III Part 3 were identical to Phase III Part 1, with the
exception that constituents were added to the clean water.
                                           42

-------
The Phase III-l  data are shown graphically in Figures 4-16,  4-17 and 4-18, representing the
relationship between influent and effluent flow rates, between influent flow rate and tank water
depth and the drawdown flow rate as a function of water depth.   The elevation of the bypass
siphon was 60 in. above the tank floor, and served to prevent water depths greater than 60 in. for
these flow conditions.
               50
              40
            CL
            CD
            £
            ffi)
            QC
30 -
            ; 20-
            E
            LLJ
               10-
                    Effluent Flow Rate as a Function of Influent Flow Rate
                    •  Effluent 1
                    O  Effluent 2
                    T  Effluent 3
                             10          20          30
                                    Influent Flow Rate (GPM)
                                                            50
Figure 4-16. Phase III Part 1 relationship between influent and effluent flow rates using
clean water.
                                          43

-------
                   Tank Water Depth as a Function of Influent Flow Rate
              60-
              40-
              20
•  Effluent 1

O  Effluent 2

T  Effluent 3
*  *
                           10
                                         40
                50
                                      20         30

                                  Influent Flow Rate (GPM)


Figure 4-17. Phase III Part 1 tank water depth as a function of influent flow rate.
                           Drawdown: Flow Rate vs  Water Level
              20
              15
            E
            Q.
            CD


            I 10
            DC
               5 -
                50      48      46      44      42      40

                                    Tank Water Level (in)
                                            38
               33
Figure 4-18. Phase III Part 1 drawdown flow rates.
                                        44

-------
The data show that the influent and effluent flow rates through the system are nearly identical
once the flow is greater than approximately 15 gpm. The data also show the Up-Flo™ Filter can
operate up to approximately 35 gpm before the bypass level is triggered. The drawdown data
snowed that the drawdown time for the device was less than one  hour and was linearly related
(visual assessment only) to the water level in the tank.

The same information was graphed for Phase III Part 2 and Phase  III Part 3 (Figures 4-19, 4-20,
4-21,  and 4-22, respectively for the relationship between flow rates and between influent flow
rate and water depth in the tank. Phase  III Part 2 and Phase III Part 3 used the same media bags
as in Phase III Part 1.

                    Effluent Flow Rate as a Function of Influent Flow Rate
               40
            B  30 -
            ra
               20 -
            u
            E
            LLJ
               10 -
                            10          20          30
                                    Influent Flow Rate (GPM)
40
SO
Figure 4-19. Phase III Part 2 relationship between influent and effluent flow rates.
                                          45

-------
                   Tank Water Depth as a Function of Influent Flow Rate
              70
              SO-
           '
              50 i
           jf.
            c
            ro


           ,E 40 -




           
-------
                    Tank Water Depth as a Function of Influent Flow Rate
               70
              60 -
               50 -
              40

               30 -
            Q
               10 -
                            10          20          30
                                    Influent Flow Rate (GPM)
50
Figure 4-22.  Phase III Part 3 tank water depth as a function of influent flow rate.

The results of the flow rates through the media as a function of influent flow rate were compared
in Table 4-7 and graphically in Figure 4-23. The results show that, in general, the effluent flow
rates were comparable to the influent for all flow rates tested (up to and past the point where the
bypass was activated). Hydraulic  performance  appears to decrease during the 40 gpm and
particularly the 45 gpm testing in Phase III Part 3.  When Figure 4-22 is evaluated with Table 4-7
and Figure 4-23, it appears that the bypass siphon (with an elevation of 60 in.) was preventing
the tank water level from exceeding 60 in., and at influent flows greater than 30 gpm, a portion
of the effluent was likely untreated bypass water.

Table 4-6. Phase III Influent and Effluent Flow Summary
Influent Flow
Rate (gpm)
10
15
20
25
30
35
40
45

Phase III Part 1
8.43
15.5
20.0
24.2
31.1
36.3
40.3
47.1
Effluent Flow Rate (gpm)
Phase III Part 2
7.39
15.0
20.0
22.1
34.9
36.4
40.7
48.1

Phase III Part 3
10.3
14.6
16.9
20.5
32.0
33.6
38.2
41.9
                                          47

-------
                                Flow Rate - Phase
              10      15       20      25       30      35
                                 Flow Conditions (GPM)
40
45
Figure 4-23.  Comparison of influent versus effluent flow rates  for Phase III hydraulics
testing.

4.3.3.2 Analytical Data

Samples were collected during Phase III-2 and Phase III-3 testing at each flow rate condition (10,
15, 20, 25, 30, 35, 40, and 45 gpm). The analytical data are summarized in Tables 4-8 and 4-9.
For Phase III-2, the TSS and SSC analytical data showed a reduction starting above 90% and
decreasing to 0% at the two highest flow rates (40  and 45 gpm  settings, 45 and 50 gpm
measured). TP removals ranged from <0% to 65%, while  COD removals  ranged from <0% to
85%. At the higher challenge concentrations of Phase III-3, performance degradation was noted
much sooner for all parameters compared to Phase  III-2. The results are shown  graphically in
Figures 4-24 through 4-27 for Phase III-2 and 4-28  through 4-31 for Phase III-3. The graphics
illustrate the much more rapid loss of performance in Phase III-3. This would be expected, since
the device would be challenged beyond its design flow capabilities,  and a portion of the flows
would pass through the bypass mechanism without treatment.
                                         48

-------
Table 4-7. Phase III Part 2 Analytical Data
Influent Flow Rate
Analyte (gpm)
TSS 10.7
6.43
21.6
24.6
39.2
44.7
48.9
50.8
SSC 10.7
6.43
21.6
24.6
39.2
44.7
48.9
50.8
TP 10.7
6.43
21.6
24.6
39.2
44.7
48.9
50.8
COD 10.7
6.43
21.6
24.6
39.2
44.7
48.9
50.8
Influent Cone.
(mg/L)
140
110
209
125
49
283
45
45
120
215
242
184
71
391
71
49
14
32
19
20
13
46
36
45
35
30
41
43
286
105
168
130
Effluent Cone.
(mg/L)
5
6
<5
8
3.3
17
26
45
<5
8.3
3.6
13
7.1
20
32
49
79
54
61
13
11
16
33
32
71
60
34
43
44
164
367
48
Removal
Efficiency (%)
96
95
>99
94
93
94
42
0
>99
96
99
93
90
95
55
0
-464
-69
-221
35
15
65
8.3
29
-103
-101
18
1.4
85
-56
-118
63
                                        49

-------
Table 4-8. Phase III Part 3 Analytical Data
Influent Flow Rate
Analyte (gpm)
TSS 11.4
15.7
19.5
25.4
31.5
31.9
41.1
45.6
SSC 11.4
15.7
19.5
25.4
31.5
31.9
41.1
45.6
TP 11.4
15.7
19.5
25.4
31.5
31.9
41.1
45.6
COD 114
15.7
19.5
25.4
31.5
31.9
41.1
45.6
Influent Cone.
(mg/L)
331
253
430
624
314
370
511
575
NA
311
396
671
292
416
415
603
123
150
168
216
79
132
197
229
275
363
463
264
151
377
181
207
Effluent Cone.
(mg/L)
13
75
138
269
219
255
511
409
9.8
NA
142
273
340
320
824
399
60
59
107
162
138
187
237
242
27
89
152
190
186
188
222
198
Percent
Efficiency (%)
96
70
68
57
30
31
0
29
NA
NA
64
59
-16
23
-99
34
51
61
36
25
-75
-42
-20
-5.7
90
75
67
28
-23
50
-23
4.3
                                        50

-------
                           Total Suspended Solids: Phase 111-2
ouu

250 -
,§ 200 -
c
| 150-
<-> 100 -
50 -
n .
i i Influent
(=> Effluent




—





— I






P








— i
. — .
















i i

































LL D_
                  6,4     10.7    21.6    24.6    39.2    44.7

                                 Measured Flow Rate (gpm)


Figure 4-24. Phase III Part 2 TSS influent and effluent results.
48.9
50.8
                     Suspended Sediment Concentration: Phase III-2
            500
            400 -
          § 300
         '•+-»


         1

          8
          g 200

         o

         o
         03
         (f)
            100
                     Influent

                     Effluent
                  6.4     10.7    21.6    24.6    39.2    44.7

                                 Measured Flow Rate (gpm)


Figure 4-25. Phase III Part 2 SSC influent and effluent results.
48.9    50.8
                                         51

-------
                              Total Phosphorus: Phase 111-2
             80 -
          §> 60
            40 -
          o
          O
          £L
                  6.4     10.7    21.6    24.6    39.2    44.7    489     50.8

                                 Measured Flow Rate (gpm)


Figure 4-26. Phase III Part 2 total phosphorus influent and effluent results.


                         Chemical Oxygen Demand: Phase III-2
'-tuv

5* 300 -
O)
E.
c
0
£ 200 -
8
c
0
O
Q
g 100-
n .
i
i











3 Influent
3 Effluent










I — i










































f .|



















	






















1
                   6.4    10.7    21.6    24.6    39.2    447

                                 Measured Flow Rate {gpm)


Figure 4-27. Phase III Part 2 COD influent and effluent results.
48.9    50.8
                                        52

-------
                           Total Suspended Solids: Phase 111-3
/uu -
600 -
0) 500 -
c
•2 400 -
P
Concenti
CO
0
o
$ 200-
100 -
n .
i i Influent
i= Effluent
























]
—
























1 	
1 — 1





— 1
















— 1





1 —











—






1 — 1




                  11,4    15.7    19.5    25.4    31.5     31.9

                                 Measured Flow Rate (gpm)


Figure 4-28. Phase III Part 3 TSS influent and effluent results.
41.1
45.6
                     Suspended Sediment Concentration: Phase III-3
           1000
            800 -
         §  600 -

         03
         g  400-

        O

        o
        (D
        CO
            200 J
                     Influent

                     Effluent
                  11.4    15.7    19.5    25.4    31.5     31.9

                                 Measured Flow Rate (gpm)


Figure 4-29. Phase III Part 3 SSC influent and effluent results.
41.1
45.6
                                         53

-------
                              Total Phosphorus: Phase 111-3
            300
            250 -
          £? 200 -
         £ 150 -
         c
         O 100 -

         Q.



             50 -
                      Influent
                      Effluent
                  11.4     15.7    19.5    25.4    31.5     31.9    41.1    45.6

                                 Measured Flow Rate (gpm)


Figure 4-30. Phase III Part 3 total phosphorus influent and effluent results.
                          Chemical Oxygen Demand: Phase III-3
            500
            400 -
          o 300
          Sfl
          00
          I
          §
          O
          Q
          O
200 -
            100 -
                      Influent
                      Effluent
                  11.4     15.7    19.5    25.4    31.5     31.9

                                 Measured Flow Rate (gpm)


Figure 4-31. Phase III Part 3 COD influent and effluent results.
                                                  41.1
45.6
                                         54

-------
PSD analysis was also performed for all samples in Phase III. The results are shown graphically
in Figures 4-32 and 4-33.  For Phase III Part 2, the influent mean dso was 60 um, while for Phase
III Part 3, the mean influent dso was 43 um.  The mean effluent dso for Phase III Part 2 was 11 um
and for Phase III Part 3 was 39 um. This poorer performance in reducing the d50 of the influent
was not unexpected given the higher loading entering the filter during Phase III Part 3.  This
indicates that the Up-Flo™ Filter was capable of removing particulates from the influent during
normal operations, and removals are reduced when the filter is challenged, and part of the flow is
bypassed, as would be expected.
                              Phase 111-2 Influent & Effluent
          100
                       Influent
                	o—  Effluent
                       Dry solids mix
       o
            0
                                  10                   100
                                       Diameter (|jm)

Figure 4-32.  Phase III Part 2 PSD summary.
1000
                                          55

-------
                               Phase 111-3 Influent & Effluent
           100
                       Influent
                       Effluent
                       Diy solids mix
                                   10                   100
                                       Diameter (IJITI)
1000
Figure 4-33.  Phase III Part 3 PSD summary.

4.3.4   Phase IV— Contaminant Capacities at High Hydraulic Throughput

As described in Section 3.5.4, in Phase IV the system was run to exhaustion (similar to Phase II),
except that the unit was under higher hydraulic loads and proportional contaminant loads.

The unit was  operated under continuous flow conditions at a constant flow rate of 32 gpm until
the unit plugged with solids, or the contaminant absorption capacity was exceeded. The test plan
specified a flow rate of 30 gpm, based on the vendor's claims that the system could treat water at
a maximum flow exceeding 20 gpm.

During the first day (approximately two hours  into the testing), the TO observed the media bags
"broke through" their mesh  retainer, causing visible  solids in  the  effluent. New  bags  were
installed and the test rerun the following two days. No samples were analyzed from the first day.
The testing under sustained contaminant and flow  loading conditions until failure highlighted a
failure mode  that  had  not been anticipated by the vendor.   Under these conditions, failure
occurred through what appeared to be inadequate support of the top flow distribution media,
allowing bypassing to occur within the filter module, as  opposed to bypassing through the bypass
mechanism. Because of the nature of this failure mode,  the protocol was modified and additional
samples were taken during the first two hours of the rerun.
                                          56

-------
 4.3.4.1 Analytical Data

 As described  above, samples were collected in accordance with the test plan, plus additional
 supplemental samples were collected to confirm test observations. A total of 15 sets of samples
 were collected and analyzed.  The results of the testing are summarized in Table 4-10.  Visual
 evidence of breakthrough was noted at 19,800 gallons. Two sets of confirmatory samples were
 collected  and  analyzed once failure was  observed.  As anticipated, the  Up-Flo™ Filter
 performance was more variable than during the earlier runs, even for TSS and SSC. The median
 removal efficiency for TSS  and  SSC during Phase IV  was  62%, the median TP removal
 efficiency was less than -8%, and the median COD removal was -42%.  Comparison  of this data
 to the Phase I and Phase II data shows that the ability of the Up-Flo™ Filter to remove dissolved
 and fine particulate pollutants may be compromised by this failure mode, particularly at flow
 rates 150% above the design flow rate.  The data is displayed graphically in Figures 4-34 through
 4-37.

 Table 4-9. Phase IV Analytical Summary

       Influent Concentration (mg/L) Effluent Concentration (mg/L)   Removal Efficiency ("/o)1
Analyte Mean
TSS 131
SSC 121
TP 42
COD 66
Median
95
102
36
59
Max
480
389
163
180
Min
<5
<5
0.9
18
Mean
45
46
39
107
Median
36
39
39
84
Max
113
129
80
370
Min
6.5
7.3
3
42
Mean
65
62
7
-63
Median
62
62
-8
-42
Max
95
93
81
41
Min
-1,640
-1,420
-4,680
-1,960
1. Mean and median removal efficiency is a function of mean and median influent and effluent concentrations, and
  maximum and minimum removal efficiencies are a function of individual paired data points.
                                            57

-------
          500
          400 -
                         Phase IV - Total Suspended Solids
          300 -
        O)
        CO
        CO
          200 -
          100 -
                          5000          10000          15000         20000
                      Cumulative Volumetric Loading in Phase IV (gal)
Figure 4-34. Phase IV TSS influent and effluent cumulative loading results.
                    Phase IV - Suspended Sediment Concentration
          500
               —••—  Influent
               —-O—  Effluent
          400 -
                          5000          10000         15000         20000
                      Cumulative Volumetric Loading in Phase IV (gal)
Figure 4-35. Phase IV SSC influent and effluent cumulative loading results.
                                        58

-------
          180
                             Phase IV - Total Phosphorus
       o>
       £
          160 -

          140 -

          120 -

          100 -
               —•—  Influent
               —-O—  Effluent
              0           5000          10000         15000         20000
                       Cumulative Volumetric Loading in Phase IV (gal)
Figure 4-36. Phase IV total phosphorus influent and effluent cumulative loading results
                        Phase IV - Chemical Oxygen Demand
          400
          350 -
          300 -
          250 -
        CO
          200 -
       Q
       O
       O
          150 -
          100 -
           50 -
            0
                                                          —•— Influent
                                                          — -O—  Effluent
              0           5000          10000          15000         20000
                       Cumulative Volumetric Loading in Phase IV (gal)
Figure 4-37. Phase IV COD influent and effluent cumulative loading results.
                                         59

-------
The PSD analysis for Phase IV (Figure 4-38) shows that the Up-Flo™ Filter was not as effective
at reducing the influent dso during its operation at high hydraulic loadings. This is likely due to
the breakthrough of the filter bags and holder seen during this phase. The operation of the filter
was halted when the bag breakthrough was noticed visually, but it likely occurred to a slight
extent prior to its being visible in the operation.
                                Phase IV Influent & Effluent
           100
                        Influent
                	1>—  Effluent
                        Dry solids mix
                                   10                  100                 1000
                                        Diameter (|jm)

Figure 4-38. Phase IV particle size distribution analysis.

4.4    Phases I-IV Data Summary and Discussion

The flow and analytical data in the four test phases provided the following general observations:

   •   The Up-Flo™ Filter was capable of removing sediments from the influent water. TSS
       and  SSC  removals   were  variable,  resulting  primarily   from  variable   influent
       concentrations  with effluent concentrations remaining fairly consistent.   The  mean
       removal efficiencies during typical  operating conditions were slightly less than 80%, and
       in some circumstances were as high as 90% to 95%. Performance was poorer when the
       hydraulic flows or pollutant loadings were higher.

   •   Particle size distribution analysis confirmed these results, with poorer removals (or no
       removal) occurring during the test phases with sustained high hydraulic flows or pollutant
       loadings.
                                           60

-------
   •   Total phosphorus removals ranged from negative to approximately 60%. COD removals
       also ranged from negative to greater than 85%. In general, filter performance improved as
       the filter aged, up to the point where failure began.

   •   The failure mechanism noted by the TO was not the one anticipated by the vendor. The
       vendor indicated that the Up-Flo™ Filter would fail by having the filter bags clog,
       forcing a build up of water in the tank, which would eventually reach the bypass and flow
       out through the bypass. Instead, the TO noticed (at the ends of Phases II and IV) that the
       water built up  in the tank to  a specific level,  indicating that the filter was clogging.
       However, prior to activation of the bypass, the pressure on the bags apparently built up to
       a level sufficient to move the bags and mesh supports in the filter module. This uplifting
       of the bags  provided an opening large  enough (at  one corner) to allow water to flow
       freely past the bags. This failure was noted in two ways: (1) the edges of the bags were
       noted above the  effluent  opening of the cartridge container, and (2) the water level
       suddenly dropped noticeably after the slow buildup to the bypass level.

In general, the Up-Flo™ Filter was capable of removing solids consistent with claims made by
the vendor, at the concentrations  used during testing.   It is anticipated that the results of this
series of tests could be adjusted  to calculate loadings throughout the filter's life and used to
develop design curves that can be used to predict  behavior when challenged by lower TP  and
hydrocarbon concentrations. What  is  unknown (from a  performance  prediction standpoint) is
what effect the higher hydrocarbon loadings had  on blinding the filter bags. This data is not
easily translated without additional  work at different hydrocarbon loadings, where the effect of
hydrocarbon loading on filter life can be evaluated.

4.4.1   Installation  and Operation & Maintenance Findings

The TO performed O&M on the system as outlined in the vendor's written O&M procedures
between test phases and as necessary during testing. O&M procedures  and observations focused
on:

   •   Ease of installation;
   •   Weight of filter media bags, before and after testing;
   •   Clarity of written O&M procedures;
   •   Ease and time needed to clean unit and replace filter media; and
   •   Characteristics of waste materials.

4.4.1.1 Installation

To evaluate the ease of installation of the Up-Flo™ Filter, the  TO installed the system in the test
rig supplied by the vendor in accordance with the vendor's  instructions for use in a catch basin.
In general, the TO found the installation instructions were clear and  the procedures were simple
to follow.
                                           61

-------
4.4.1.2 Filter Media Bags

The TO was unable to observe differences in the sizes and dry weights of the filter media bags
from phase to phase since the bags were shipped slightly damp. Therefore, obtaining a point of
comparison  was impossible. According to the vendor, the net weight of the carbon-based filter
bags is approximately 50 Ib. Two bags of the CPZ  media were installed in the unit between
phases (chronologically, new filter bags were installed after Phases III, II and IV). Because of the
height of the test unit compared to the  location of the filter cartridge, it was difficult to  lift the
heavy filter  bags in and out, especially one-to-two days after use when they were still nearly
soaked (although not  dripping to a measurable extent). The TO was concerned that the straps
used to lift  the bags  in and out of the cartridge  and the device would  not  hold up  during
installation and removal. These concerns were unfounded. The bags stayed intact until they were
sliced open to observe the depth of penetration of the pollutants into the filter media.

4.4.1.3 General O&M/Svstem Cleanout

System cleanout consisted of pumping  down the water to the sediment level, taking care not to
disturb the sediment. One person entered the device and one person remained outside to hand in
materials as  needed. The replacement of the bags consisted of opening the module lid, removing
the top layer of mesh, the two bags and the bottom layer of mesh. The interior of the filter
module was wiped down with a paper towel and tap water to remove grit trapped along the
edges. The sediment was cleaned out between phases using a wet/dry shop vacuum. Once the
filter module was visually clean, new mesh and filter bags were installed as outlined in the O&M
manual with care taken to fit the bags to the edges of the filter module and to fit the top mesh
below the mesh sill of the filter module. The typical O&M session took between 30 and  45 min
with approximately half of the time devoted to pumping down the water in the tank.

4.4.1.4 Waste Material Characterization

Waste material  characterization focused on two primary areas: physical and chemical. Physical
characterization determined the mass and volume of waste material generated during a cleanout
session, while chemical characterization determined hazardous characteristics important in waste
disposal considerations.

As waste materials were generated, representative composite samples of the recovered sediments
were submitted for analysis for sediment COD and sediment  phosphorus. Three samples from
different sections  of  the  sump were collected and  analyzed. The results were as  listed  in
Table 4-11. The hopper solids were also tested and the solids' concentration was  >0.0875  g TP/g
solid. The statistical analysis showed less than 20% deviation  among the hopper solids samples
indicating that the contaminants of concern were well-distributed across the hopper solids. While
there  are  no waste disposal regulations that  specifically address these pollutants, the  results
indicate that the sump  is capable of trapping particulate pollutants and that further testing may be
required if the influent water contains one or particular contaminants of concern, such as metals
(which were not included in the scope of this project).
                                           62

-------
 Table 4-10. Characterization of Material Captured in Up-Flo™ Filter Sump


       Sample Number	COD (g COD/g waste)	TP (g TP/g waste)
              1                          0.070                        0.016
              2                           0.10                        0.022
              3                          0.087                        0.017
           Average                       0.086                        0.018
      Standard Deviation                  0.015                        0.0034
	COV	0.18	0.19	

 4.5    Summary of Findings

 A newly maintained Up-Flo™  System, operating in the design range, is  capable of reducing
 sediment concentrations in this test wastewater in a range of 50% to 90%,  as measured by TSS
 and SSC.  Hydrocarbon removals, as measured  by COD analyses, were  highly variable  and
 ranged from negative to >85%. TP removals were in the same range as the COD removals.  The
 TO observed the following regarding the removals of TP and COD. The filter performance  was
 optimum during the middle of the filter run (after the filter had 'aged' and before breakthrough
 began). Filtration performance was best when the filter was operating on an intermittent schedule
 and at the design flow rates or below.  This is in agreement with filter treatment theory.

 An Up-Flo™ with new filter media can accept a hydraulic flow of up to  approximately 35 to
 40 gpm, without bypassing, depending  on the concentration of contaminants in the wastewater.
 The maximum treated flow  decreases  as the  filter media trap  contaminants, preventing water
 from flowing through the filter bags.  The activation of the bypass was only observed during the
 testing across the operational flow rates (Phase III) testing. A different failure mechanism (where
 the pressure on the bags was sufficient to dislodge the bags and open a flow path through the
 cartridge) was observed in Phases II and IV. This failure mechanism was new to the vendor, who
 indicated that this failure mechanism  had not been noted before in the vendor's laboratory.  The
 TO supposes that this may be due to  the different test mixtures used in the vendor's laboratory
 compared to the TO, who was following the test plan. The test plan had a mixture that was much
 closer to washwater than stormwater.

 In addition to hydrocarbon and phosphorus treatment, the Up-Flo™ system was also capable of
 reducing suspended  solids concentrations in the  treated effluent. Sediment removal efficiency
 was measured three ways:

    1.  the TSS and SSC analytical methods;
    2.  theoretical methods (measuring the mass  of solids  fed into  the synthetic wastewater by
       the test rig); and
    3.  particle size distribution comparison of influent and effluent.

 An important  consideration  in  determining  overall system  efficiency is the propensity of
 contaminants  to plug the filter media,  resulting in untreated  wastewater bypassing the filter
 media. When the Up-Flo™ Filter failed in the method described by the vendor, it was simple to
                                           63

-------
verify visually. The water in the tank built up to the bypass level. This would be easy to observe
in the field also if the storm inlet is covered by a grate. The failure due to the shifting of the bags
and mesh will not be visible in normal  applications. It was visible here because the effluent
flowed directly into the treatment basin prior to discharge to the TO's sewer system.

Filter media blinding, which is a function of the influent flow rate and pollutant loading, did not
occur immediately, even at the  high flow  rate  and high influent concentration conditions.
However, as can be seen in the data for Phases  III (high concentration) and Phase IV (high
sustained flow rate) when compared to the Phase  I+II results, treatment efficiency is decreased
across the run and the run is shortened. Because of the elevated concentrations of detergents and
because of the behavior of the sediments as floes, the TO  can only predict that performance in
the field would  be  extended compared to that  in the laboratory.  The  length of that extended
performance is unknown because of the  manner in which the blinding occurred, with  an oily
slime appearing  on the media face and oil particles plus detergent creating rings around the test
tank. The results of these tests are more directly applicable to the performance of an Up-Flo™
Filter at hotspots where substantial vehicular maintenance and washing could be expected.

O&M procedures are relatively simple and can be completed in approximately 30-45 min.
                                           64

-------
                                      Chapter 5
                        Quality Assurance/Quality Control

The  test plan included a QAPP with critical  measurements  identified and several QA/QC
objectives established. The verification test procedures and data collection followed the QAPP,
and  summary results are reported  in this section. The full  laboratory  QA/QC results and
supporting documentation are presented in Appendix C.

5.1    Audits

The  VO conducted one audit of the PSH Environmental Engineering Laboratory at the start of
the verification test.  The audit  found that the field and laboratory procedures were generally
being followed, and that the  overall  approaches being used were in accordance with  the
established QAPP.  Recommendations for changes  or improvements were made,  and  the
responsible parties responded quickly to these recommendations.

5.2    Precision

Throughout the verification test, the laboratory performed laboratory duplicates or matrix
spike/matrix spike duplicates to monitor laboratory precision. Field duplicates were collected to
monitor the overall precision of the sample collection and laboratory analyses.  The test plan data
quality objectives for precision were based on laboratory precision for the analyses. The test plan
did not set field precision targets, as it was recognized that precision impacted by  sampling and
constituent mixtures would be highly constituent- and equipment-dependent.

The  relative percent difference (RPD) recorded from the sample  analyses was  calculated to
evaluate precision. RPD is calculated using the following formula:


                                    %RPD = ^=^ x 100%                        (5-1)
                                                x
where:
x\ =  Concentration of compound in sample
X2=  Concentration of compound in duplicate
x = Mean value of xi and X2

5.2.1  Field and Laboratory Precision Measurements

The  laboratory performed precision analyses in two methods: laboratory standard measurements
and analysis of field replicates.  Triplicate analyses for all samples collected during Phase III (the
first  phase chronologically) for TSS, SSC, COD, and TP were  performed. These  field samples
were individual bottles collected after the system had sufficient time to stabilize.

For the  laboratory, the required analytical tolerance limits are 10%  for all analytes used in this
test plan. The samples all fell within this tolerance, with the exception of TSS,  which was within
the 30% tolerance seen for prior TSS sampling. Several papers have been written addressing the


                                           65

-------
limitations and relationship between TSS and SSC, including one under review by Dr. Clark, the
principal investigator (PI) on this  project. The data from the PSH laboratory where the TSS
results are 70% to 80% of the SSC values for the same samples is in agreement with that seen by
other researchers working with stormwater samples. The statistical analysis of the data contained
in that paper (based on 215 sample  pairs) showed that there was no statistical difference between
the TSS and SSC results, indicating that the variability seen between samples is sufficiently large
to drown  out the differences between the analytical methods. This is particularly  true when
influent samples were analyzed (and not as true for effluent samples). These results are due to
the larger particles that are in the influent  samples (and not in the effluent). The TSS sampling
methods are not easily able to sample particles larger than 100 to 200 um.

For COD and TP, the field replicates are not in the 0% to 25% COV range deemed tolerable by
the test plan. The reason for this difference is the non-continuous distribution of TP and COD in
the influent. In order to obtain the dosing required by the test plan, only periodic dosing (adding
periodic drops of solution, rather than a continuous stream) was required of the OBC and WBC
solutions. The solids dosing was more consistent, although problems were noted with dosing due
to clogging of the solids hopper  and distribution  system occasionally. This resulted in the
installation of a technician at the solids' hopper to monitor the dosing of the system.

The  field precision results are summarized in Tables 5-1. All of the data  are presented in the
Appendices to this report. These  samples are  based on  triplicate influent samples collected
during Phase III Part 2.

Table 5-1. Replicate Laboratory Sample RPD Summary

Analyte
TSS
SSC
TP
COD
Number of
Samples
24
24
8
8
Mean
(mg/L)
109
168
56
71
Standard
Deviation
67
115
46
50

COV
0.61
0.69
0.82
0.71
All of the TOC laboratory data was within the established precision limits, although this analysis
may not have provided a true result for the samples, as discussed in this Section 5.5.

While the results were not always within the limits established by the test plan, the procedures
were reviewed regularly and standards analyzed. These standards' results showed that laboratory
procedures, calibrations, and data were found to be in accordance with the published methods
and good laboratory practice.

The design of the sampling program  anticipated that precision might be low for some  of the
constituents due to the nature of the water being tested. The sampling plan included collection of
several aliquots over time to make composite samples. The data evaluation also was based on
mean data collected over a large volume of flow and long time periods.  This approach was used
to help  mitigate minute-by-minute changes  that might occur in the water, particularly  in the
influent water. Also, the careful monitoring of the total volume of water used and the total mass
                                           66

-------
of constituents  fed to the system provided a basis for calculating influent concentration. The
sampling techniques  and laboratory procedures were carefully reviewed before and during the
test. The procedures  used were in accordance with best sampling practice, and the laboratory
methods and procedures were found to be performed in accordance with the published methods.

5.3    Accuracy

Method accuracy was determined and monitored using a combination  of matrix spikes and
laboratory control samples (known concentration in blank water)  depending on the method.
Recovery  of the  spiked  analytes was  calculated and monitored during  the verification test.
Accuracy  was in control throughout the verification test. Table 5-2 shows a summary of the
laboratory control sample recovery data.

Table 5-2. Laboratory Control Sample Data Summary


Analyte
TSS
ssc
TP (as P)
COD

Actual
(mg/L)
150
350
2.00
300

Measured
(mg/L)
159
344
2.25
294


cov
0.08
0.002
0.05
Deviation from
Standard
Concentration
6%
2%
13%
5%
All the samples were within the quality control limits, with the exception of one COD sample
(151 mg/L) which was much lower than the allowed limits. This  does  not raise a concern,
because all other COD standard samples were well within their limits. Samples associated with
the COD standard were spot-checked the next day to ensure that the problem was in the standard
only. This was confirmed when the sample analytical results were similar from Day 1 to Day 2
and the standard was measured at the desired level.

The balance used for TSS  and SSC analysis was calibrated routinely with weights that were
National  Institute of Standards  and Technology  (NIST) traceable. Calibration  records were
maintained by the laboratory and inspected during the on site audits. The temperature of the
drying oven was also monitored using a thermometer that was calibrated with a NIST-traceable
thermometer. Pipettes  and graduated  cylinders had their calibrations  confirmed  using  the
analytical balance and deionized water.

5.4   Representativeness

The testing procedures were designed to ensure that representative  samples  were collected of
both influent and effluent wastewater. Supervisor  oversight and audits provided assurance that
procedures were being followed. As discussed earlier, the challenge in sampling wastewater is
obtaining representative samples. The  data indicated that while  individual sample variability
might occur, the  long-term trend in the  data was representative of the concentrations in  the
wastewater, and  redundant methods of evaluating key constituent loadings in the wastewater
                                           67

-------
were used to compensate for the variability of the laboratory data. In addition, the results and
shape of the effluent curves were compared to known filter theory to evaluate abnormalities. For
example, while the models were not fitted to this data, it is well known that filter flow rate can be
modeled by a power equation with suspended solids loading or time as the independent variable.
This occurred in this case to the extent seen in prior laboratory work by the TO with up-flow
filters. In addition, the graphs of pollutant  behavior over  filter  life showed  the traditional
breakthrough curves, where  filter  performance was variable at the  start  of the run, optimal
performance was obtained after the filter aged slightly and the pollutant removals decreased as
the filter neared breakthrough.

The laboratories used standard analytical methods and written standard operating procedures for
each method to provide a consistent approach  to  all  analyses.  Sample handling, storage, and
analytical methodology were reviewed during the on-site  and  internal audits to  verify  that
standard procedures were being followed. The use of standard methodology, supported by proper
quality control information and audits, ensured that the analytical data were  representative of the
actual wastewater conditions.

5.5    Completeness

The test plan set a series of goals for completeness. During the startup and verification testing,
flow data were collected for each day at a minimum of once per two hours for Phases II, IV, and
V, and once per active flow setting for Phases I and III.  The flow records are 100% complete.

No scheduled analyses had to be omitted from the testing program. Less than seven TSS or SSC
samples were not sieved prior to analysis. In all cases but two, either the TSS or SSC sieved was
performed and while the protocol called for using the  TSS only data to adjust the particle size
distribution for the mass above 250 um, in those  cases where the TSS sieve data was missing, the
SSC unsieved and sieved comparison was used. For those two instances where no sieve data was
available, the samples were not included in the particle size distribution analysis presented here.
Given the number of samples collected (which exceeded the requirements of the test plan for all
phases but Phase II), these missing samples were not considered sufficiently important to rerun
the testing phase. Sufficient data was available to document the performance of the device. This
results in less than five omitted data points from  a more than 200 data points per analytical
parameter, resulting in greater than 99% completeness, which exceeds the 80% completeness
goal for this program.

While COD was used as a surrogate organic measurement in the protocol to measure the capture
of hydrocarbons, the free product (un-emulsified hydrocarbons) in the device and  in the flow
stream affected the repeatability of the tests even  from aliquots drawn from the same sample
bottle.  All samples collected for COD were analyzed, resulting in 100 percent completeness,
giving a reasonable indication of the bounds of performance  of the Up-Flo™ Filter. Similar
variability was seen with the TP measurements because of the  small additions of the WBC which
contained the bulk of the dissolved phosphorus. All samples  were analyzed, resulting in  100%
completeness and allowing for the bounds of performance to be evaluated.
                                           68

-------
                                      Chapter 6
                           Vendor Supplemental Testing

The vendor requested that supplemental testing be conducted on the Up-Flo® Filter after they
reviewed the test data and results derived from the ETV testing. They expressed concerns that
the filter media breakthrough in the filter module was something they had not seen in testing at
their facility or in field  applications. This test was conducted to examine  whether the  filter
module design  should be modified to reduce the ability of the filter media to move within the
module coupled with whether the synthetic challenge water created a challenge that was beyond
the design considerations of the device and not indicative of real-world situations.

6.1    Up-Flo® Filter Modifications

The filter modules were redesigned to improve support and restraint and prevent the media bags
from shifting and potentially displacing vertically, observed during the original phase of testing.
The  number of latches  attaching the filter module lid  was  increased from  one to  three.
Additionally, the media restraint was redesigned by increasing the width of each  structural side.
Figure 6-1 shows the Up-Flo® Filter module and Figure 6-2 shows the modifications made to the
module to improve the support on the filter media.
                                      Latches
                                      Media
                                     Restrain

                                    Conveyance
                                     Channel
                                    Media Pack
                                       Filter Module
                                      Angled Screen
Figure 6-1.  Modifications to Up-Flo Filter module.
                                           69

-------
                      Improved support across top of flow distribution media
               Old Module                               New Module

Figure 6-2. Modifications to Up-Flo® Filter module showing improved support details.

6.2    Test Procedure Modifications

The testing procedures were modified, including modifications to the synthetic challenge water,
elimination of COD as an analyte based on the changes to the synthetic challenge water, and
omission of the Phase III and Phase IV tests. These modifications are outlined in greater detail in
this section.

6.2.1   Synthetic Challenge Water

The verification test was performed  using synthetic water (Table  6-1) made from a mixture of
solids -  one of which provided the particulate  phosphorus required by the  test  plan.  The
following products were used to make the synthetic challenge water:

          Sil-Co-Sil® 250;
   •      Slow release phosphorus-supplying fertilizer; and
   •      Concrete plant sand sieved to a size of all passing through 5,000 jim.

Table 6-1.  Modified Synthetic Challenge Water Concentrations

                                                     Concentration
                  	Parameter	(mg/L)
                   SSC                                     300
                   TSS                                     300
                   Total phosphorous (as P)                   3
                   Reactive phosphorus (as P)	1
                                          70

-------
A formula using a mix  of the above named products/materials was made and  tested in the
laboratory to determine the conformance to these specifications. The result of testing the ground
fertilizer for phosphorus content is 0.3 mg TP/g Scott's Lawn  Starter Fertilizer. The amount of
fertilizer used was decreased from the amount used during the initial testing because phosphorus
recovery during initial testing was found to be greater than the  target concentration. This higher
concentration may have been from the combination of the slow-release property of the fertilizer
and the grinding of the pellets into smaller particles, thus releasing more phosphorus because of
the increased surface area that comes into contact with water.  For the supplemental testing, the
fertilizer replaced approximately  1% of the  sand in the mixture to decrease the phosphorus
concentration to the target concentration.

The  other constituents added to the synthetic challenge  water in the initial testing (gasoline,
diesel  fuel, motor oil,  brake fluid, antifreeze,  detergents, and windshield washer fluid) were
removed. Observations during  the  initial  testing indicated that the synthetic  challenge water
including the hydrocarbon constituents mixed with the solids to form a viscous substance that
was atypical of stormwater and could prematurely blind the filter media.

6.2.2  Analytical Methods

Constituent  analysis for  this testing  included reactive  and  total  phosphorus (RP  and TP,
respectively), and solids (PSD, TSS, and SSC). COD  was not analyzed because the hydrocarbon
mixture was removed from the synthetic challenge water.

Influent and effluent solids were characterized using wet sieve  analysis  on samples for particles
less than 20 |j,m to above 250 |j,m. Samples were sieved through stainless steel sieves with mesh
sizes of 20 |j,m, 38 |j,m, 63 |j,m, 106 |j,m, and 250 |j,m. This wet sieve analysis allowed a complete
characterization of the  influent and  effluent particle  distribution  from less  than  20 |j,m  to
5,000 |j,m. The results for the solids analysis were subdivided into removal for the following
particle size ranges:

   •  <20 urn
   •  20-38 urn
   •  38-63
   •  63-106
   •  106-250 urn
   •  >250
6.3    Synthetic Challenge Water Laboratory Analytical Results

During testing, 46 influent samples were collected during the normal constituent feed conditions
(Phase I, Phase II) and analyzed for the various constituents specified in the test plan. Table 6-2
provides a comparison of the  mean analytical results  for these influent  samples versus the
analytical results for the synthetic challenge water mix specified in the test plan.
                                           71

-------
 Table  6-2.   Synthetic Challenge Water Analytical  Data  Comparison  to Desired  Feed
 Concentration
                                Measured Mean                    Desired Feed
	Constituent	Concentration (mg/L)	Concentration (mg/L)	
          TSS                         101                              300
          SSC                         299                              300
          TP                          1.26                                3
	RP	0.73	1	

 The mean synthetic  challenge water  data for the primary constituents were measured to be
 approximately half of the desired target concentration for TP, approximately 75% of the targeted
 RP  concentration,  approximately one-third the concentration  for TSS,  and 99% for SSC.  A
 review of the  data shows that the COVs for all parameters ranged between 0 and 1.0. To confirm
 reliability of  the sampling and to  assess the repeatability  of the testing with new personnel,
 testing was performed  again to ensure that the sampling met the required criteria for efficient
 solids capture. The differences in solids analysis procedure resulted in capturing almost all solids
 by the SSC method but only approximately one-third by the TSS methodology1.

 The hopper dosage measurements are consistent with the biases reported for TSS concentrations,
 which  typically  underreport  the total sediment  concentration in the sample, especially  for
 sediment with a specific gravity greater than 1 and a dso  greater than approximately 75 jim.2
 Although the mean analytical  TSS  concentrations  were  lower than the  300 mg/L target
 concentration  goal,  the  hopper dose measurements  suggest  that the theoretical  test plan
 concentration was close to the 300 mg/L goal.

 6.4     Test Results

 This section  summarizes the analytical data, flow  data, and observations for the test phases
 conducted during the supplemental testing.  The efficiency  values reported in  this section are a
 function of the total influent and total effluent concentrations.

 6.4.1   Phase I - Performance under Intermittent Flow Conditions

 The TSS, SSC, TP, and RP analytical data as related to cumulative volumetric loading on  the
 media are summarized in Table 6-3. The test plan required that a minimum of one set of samples
 be collected  each  test day, however, the  TO  collected samples  twice per  day.  The testing
 organization collected a total of 20 sets of samples. The increase was to  verify whether filter
 media breakthough was occurring.
 1 An in-depth discussion of solids recovery using the TSS and SSC analytical methods can be found in: Clark, S.E.
 and Siu, C.Y.S.  "Measuring Solids Concentration in Stormwater Runoff:  Comparison of Analytical Methods."
 Environmental Science & Technology. 2008, Vol. 42, No. 2, pp. 511-516.
 2 Ibid.
                                            72

-------
    Table 6-3. Phase I Analytical Data Summary
              Influent Concentration         Effluent Concentration
                     (mg/L)                       (mg/L)                Removal Efficiency (%)*
Analyte
TSS
ssc
TP (as P)
RP (as P)
Mean
85
288
1.32
0.73
Median
75
247
1.19
0.66
Max.
243
775
2.55
1.61
Min.
15
85
0.58
0.38
Mean
41
42
1.50
0.92
Median
37
37
1.42
0.86
Max.
68
79
2.27
1.37
Min.
24
20
1.12
0.60
Mean
52
86
-14
-25
Median
51
85
-19
-30
Max. Min.
81 -133
95 32
40 -291
37 -234
1. Mean and median removal efficiency is a function of mean and median influent and effluent concentrations, and maximum
  and minimum removal efficiencies are a function of individual paired data points.

    The median removal efficiency for TSS  was 51%, while the median removal efficiency for SSC
    was  85%.  The mean and median influent SSC concentration was approximately four times
    higher than the mean and median TSS  concentrations;  and  the median TSS and SSC effluent
    concentrations were nearly  identical. The  difference in sediment removal efficiencies can be
    explained by the particle size distribution of the synthetic challenge water and the differences in
    the analytical methods. The  TSS analytical method requires the analyst to shake the sample and
    collect an aliquot using a pipette, while the SSC analytical method utilizes the entire sample.
    Therefore, the SSC analytical method is perceived as a more effective method to quantify the full
    spectrum of solids including the coarser fractions of particles which may fall out of suspension
    and finer fractions of particles which will tend to stay in suspension, and as a result,  generally
    yields higher removal efficiencies than results based on TSS. The Up-Flo® Filter was  generally
    not effective in treating total phosphorus or reactive phosphorus as presented in the form utilized
    in the synthetic challenge water.

    A graphical examination of the data also was conducted to illustrate the results discussed above.
    Figures 6-3, 6-4, 6-5, and 6-6 compare the influent  and effluent  concentrations  for TSS, SSC,
    TP, and RP, respectively. Figure 6-7 shows the tank water levels for each test day.

    The Phase I testing was conducted with new filter media bags installed in the Up-Flo® Filter.  The
    Up-Flo® Filter did not exhibit signs of clogging or blinding during the test run. A review of the
    water depth  measurements  at each  sample time showed that the tank water level  remained
    consistent between 38 and 42 in. No buildup of head was noted in the unit, further indicating that
    the media capacity had not been exhausted in the Phase I testing.
                                               73

-------
        250
        200 -
        150 -
     C/D
     C/3
        100 -
         50 -
          0
               0--
                                                             —*— Influent
                                                             —-O—  Effluent
                                                                     O
            0       2000      4000     6000     8000    10000     12000
                           Cumulative Volumetric Loading (gal)

Figure 6-3. Phase I TSS influent and effluent results.
                                                                 14000
         800
         600 -
      o»
      •§
      O
      CO
      to
400 -
         200 -
                                                              —•— Influent
                                                              — O—  Effluent
                 .-O—O-Q-O--O—QS
             0       2000     4000     6000     8000     10000
                            Cumulative Volumetric Loading (gal)

Figure 6-4. Phase I SSC influent and effluent results.
                                                        12000     14000
                                         74

-------
         3.0
         2.5 -
         2.0 -
       o>
       E 1.5 4
         1.0 -
         0.5 -
         0.0
                                                               —•—  Influent
                                                               —-O—  Effluent
               0--0
             0      2000      4000     6000     8000     10000
                            Cumulative Volumetric Loading (gal)

Figure 6-5.  Phase I TP influent and effluent results.
12000    14000
          1.8
          1.6 -


          1.4 -


          1.2 -


          1.0 -
       Q_  0.8 -
       o:
          0.6 -
          0.4 -


          0.2 -


          0.0
                                                                —•— Influent
                                                                — O—  Effluent
             0        2000      4000      6000      8000     10000
                             Cumulative Volumetric Loading (gal)

Figure 6-6.  Phase I RP influent and effluent results.
     12000
                                          75

-------
           50
          40 -
           30 -
        5
        > 20 -
        c
        CO
           10 -
               Weir Height = 60 inches
                               i   i
                              CM  CO
                 Day 1         Day 2

Figure 6-7. Phase I tank water level.
                                            CM  CO
Day3
              I    I   I    I   I   I
              CM  CO  -
-------
         100
      o
          0
                                                       100
1000
                                      Diameter
Figure 6-8. Phase I influent and effluent PSD summary.
6.4.2   Phase II —Determination of the Capacity of the Unit

Upon inspection of the filter media bags after Phase I testing, the bags were found to be covered
with sediment. The TO shared this information with the vendor, who requested that the Up-Flo®
Filter be equipped with new filter media bags prior to the start of the next test phase. Since each
phase began with new filter media bags, with the exception noted previously, Phase I and II data
were not combined during the supplemental testing.

The data are summarized in Table 6-4 and are expressed graphically in Figures 6-9 through 6-12.
The median SSC  removal  efficiency was 77%, while the median TSS removal  efficiency was
41%.  Similar to Phase I, the median influent SSC concentration was approximately three times
higher than the median influent TSS concentration, yet  the median effluent  TSS and SSC
concentrations were nearly identical.  The Phase II data also show that the Up-Flo® Filter was
not effective at treating  total or reactive phosphorus as presented in the form  utilized in  the
synthetic challenge water.

Figure 6-13 shows the water levels during each day of testing. At the beginning of the test, the
water level in the sump would rise to around the elevation of the bypass weir (60  in.).  As the
testing progressed, the TO observed that the water level in the sump would take progressively
longer to reach the bypass weir elevation. On Day 14, after three consecutive days of the water
level in the tank failing to reach the bypass weir elevation, the TO concluded that  the Up-Flo®
                                          77

-------
Filter had reached a point where maintenance would be required to restore original  operating
conditions, so the Phase II test was considered finished.

Analytical  data results  for the final three days of testing did not demonstrate an increase in
contaminant concentrations in the effluent, which could be anticipated if the filter mechanism
was breached and flows were exiting the Up-Flo® Filter without filtration. Figures 6-9 through
6-12 do not show a dramatic change in the effluent contaminant concentrations at the end of the
test. The TO concluded that, there was a change in conditions in the filter modules sufficient to
relieve the pressure in the filter modules and to decrease the head in the tank, but this change did
not result in contaminant concentration increase in the effluent.
Table 6-4. Phase II Analytical Data Summary
         Influent Concentration
             Results (mg/L)
                               Effluent Concentration
                                   Results (mg/L)
Removal Efficiency (%}1
Analyte
TSS
ssc
TP (as P)
RP (as P)
Mean
110
307
1.26
0.73
Median
99
289
1.28
0.69
Max.
309
845
2.24
1.61
Min.
43
109
0.40
0.23
Mean
59
64
1.30
0.75
Median
58
65
1.25
0.71
Max.
87
101
2.53
1.38
Min.
30
33
0.51
0.27
Mean
47
79
-3.6
-3.5
Median
41
77
2.3
-2.2
Max.
83
93
46
67
Min.
-14
41
-78
-100
            1.  Mean and median removal efficiency is a function of mean and median influent
            and effluent concentrations, and maximum and minimum removal efficiencies are a
            function of individual paired data points.
         400
         300 -
      en
      E,
      CO
      co
200 -
         100 -
                                                                 —•—  Influent
                                                                 —-O—   Effluent
                        20000        40000        60000        80000
                        Cumulative Volumetric Loading in Phase II (gal)
                                                                    100000
                                            78

-------
Figure 6-9. Phase II TSS influent and effluent results.
        1000
      OJ
      E,

      O
      CO
         800 -
         600
         400 -
         200
                                                              —•—  Influent
                                                              —-O—  Effluent
                       20000        40000       60000        80000        100000

                       Cumulative Volumetric Loading In Phase II (gal)
Figure 6-10. Phase II SSC influent and effluent results.

          3.0
          2.5 -
          2.0 -
       O)
          1.5 -
       D_
       I-
          1.0
          0.5 -
          0.0
                                                              —•—  Influent
                                                              — O—  Effluent
                        20000        40000       60000        80000

                       Cumulative Volumetric Loading in Phase II (gal)
100000
                                          79

-------
Figure 6-11.  Phase II TP influent and effluent results.

         2,0
         1.5 -
      O)
         1.0 -
      Q_
      ec
         0.5 -
        0.0
                                                             —•—  Influent

                                                             —-O—  Effluent
            0          20000        40000        60000       80000

                      Cumulative Volumetric Loading in Phase II (gal)


Figure 6-12.  Phase II RP influent and effluent results.
100000
              70
              60 -
            •> 50 -
            c

            "S
              40 -
            
-------
PSD analysis also was performed on the Phase II samples, as shown in Figure 6-13. The mean
dso for the influent was  156 um and the mean effluent dso was 16  um. This confirmed the
manufacturer's claims that the Up-Flo® Filter would be capable of removing a high proportion of
the particulates in the solution.
         100
                       Influent
               —o —   Effluent
                       Dry solids mix
             1                     10                    100
                                        Diameter (|jm)

Figure 6-14. Phase II influent and effluent particle size distribution summary.
1000
6.5    Sediment Retained in Sump

Figure 6-15 shows the depth of sedimentation in different areas in the sump after running both
Phases I and II.  The letters on the figure correlate  to grab  sample locations.  The greatest
sediment depth occurred near the filter modules.  The water stream exited the influent pipe in this
general area. As a result, the larger particles most likely settled out of solution beneath the filter
modules.

Figure 6-16 presents  the sieve  analysis of the  three sampled  locations within the sump.  The
distribution of the hopper solids is given also for comparison.  The heavier solids in the mixture
tend to settle out near the inlet outflow area. The grade of the solids appears to become finer
(based on  these samples) the further away from initial point of entry into the tank (around
Location E).
                                           81

-------
         I
                    I
                         N
                         F
           G
Figure 6-15. Depth of sedimentation in sump.
Sample
Location
A
B
C
D
E
F
G
H
I
J
K
L
M
N
Depth
(in.)
4.9
4.0
2.5
4.4
2.8
2.0
1.1
1.3
0.8
1.0
1.4
1.3
1.5
1.5
                      Sample A
                      Sample G
                      Sample K
                      Hopper Solids
                                              100

                                       Particle Size ((.irn)
Figure 6-16. Sump particle size distribution analysis results.
1000
10000
                                             82

-------
Based on the data shown in Figure 6-14, the mass of solids in the  sump after the running of
Phases I and II was  estimated to be 85.3 kg.  The total  sum of loads for both phases was
approximately 104 kg. This indicates that the device retained approximately 82% of the total
solids loading in the sump. The concentration of phosphorus retained in the sump was estimated
to be 31.3  mg PC>43"  per gram of solids, or a total phosphorus mass of 3.5 kg PC>43", which
represents approximately 3% of the total  solids loading.  The increase of the phosphorus loading
from approximately 1% in the influent to 3% in the sump is likely attributable to the affinity of
phosphorus to be retained in sediments.

6.6    Test Summary and Discussion

The flow and analytical data result in the following general observations:

   •   The  Up-Flo® Filter was  capable of removing sediments from the  influent. Removal
       efficiencies for SSC were near 80% and were near 50% for TSS. The  difference between
       the TSS and SSC removal efficiencies are attributable to the TSS analytical procedure
       quantifying only the  finer fraction of sediment  as opposed to the SSC  analytical
       procedure which quantifies a full spectrum of coarse and fine sediment.  Most of the
       sediments removed from the flows were retained within the sump.

   •   Particle  size  distribution  analysis  showed that  the Up-Flo®  Filter removed a high
       proportion of  the particulate sediments.  The influent dso ranged from  approximately
       100 um to 300 um, and the effluent d50 was approximately 15 um.

   •   The Up-Flo® Filter was generally not effective at removing total or reactive phosphorus
       as presented in the form utilized in the  synthetic challenge water during this  phase of
       testing.

   •   The Up-Flo® Filter is designed so that flows exceeding the filtration capacity discharge to
       the bypass weir.  It is anticipated that clogging of the filter bags over time would decrease
       the filtration capacity, which would result in the water elevation and head increasing in
       the tank.  Flows reaching the bypass module elevation would pass through the weir in the
       bypass module without undergoing filtration.  Based on this supplemental testing and the
       original ETV study, the TO observed that as the filter media ripens, conditions within the
       filter modules  change,  resulting in an increase in the capacity  of the flow through the
       filter modules and a decrease in the driving head, instead of filter clogging decreasing the
       flow through  the  filter module.   This observation  is  demonstrated graphically  in
       Figure 6-12.

   •   The vendor's redesign of the media restraint and the  latching mechanisms of the lid of the
       filter module prior to the supplemental testing aimed to decrease the  ability of the filter
       media bags to  shift within the filter module and let flows pass between the filter media
       and the filter module walls. The latches were able to keep the filter bags encased within
       the filter  module. As the filter media ripens, it appears that conditions within  the filter
       modules change, allowing for an increase in the flow capacity through the filter module.
                                           83

-------
•  The decrease in the driving head due to the apparent increase in the flow capacity through
   the filter modules as the filter media ripened did not coincide with an increase in effluent
   analytical concentrations, as might  be expected if the flows were  bypassing  the  filter
   media.  Effluent  concentrations toward the end of the Phase II test, when the tank water
   level did not reach the weir elevation, were consistent with the effluent concentrations
   observed at the beginning of testing.
                                        84

-------
                                       Glossary

Accuracy - a measure of the closeness of an individual measurement or the mean of a number of
measurements to the true value and includes random error and systematic error.

Bias - the systematic or persistent distortion of a measurement process that causes errors in one
direction.

Commissioning - the  installation  of the in-drain removal technology and  start-up  of the
technology using test site wastewater.

Comparability - a qualitative term that expresses confidence that two data sets can contribute to
a common analysis and interpolation.

Completeness - a qualitative term that expresses  confidence that all  necessary data have been
included.

Precision - a measure of the agreement between replicate measurements of the same property
made under similar conditions.

Protocol - a written document that clearly  states the objectives, goals, scope, and procedures for
the study. A protocol  shall be used for reference during vendor participation in the verification
testing program.

Quality Assurance Project Plan - a written document  that describes the implementation of
quality assurance and quality control activities during the life cycle of the project.

Residuals - the waste streams, excluding final effluent, that are retained by or discharged from
the technology.

Representativeness - a measure of the degree to which data accurately and precisely represent a
characteristic of a  population  parameter  at  a   sampling point,   a  process  condition,  or
environmental condition.

Source Water  Protection Stakeholder Advisory Group -a group of individuals consisting of
any  or all  of the  following: buyers and users of in-drain removal and other technologies,
developers and  vendors, consulting  engineers, the  finance and  export communities, and permit
writers and regulators.

Standard Operating Procedure - a written  document containing  specific procedures and
protocols to ensure that quality assurance requirements are maintained.

Technology Panel -  a group of individuals with expertise and knowledge of in-drain treatment
technologies.
                                           85

-------
Testing Organization - an independent organization qualified by the Verification Organization
to conduct studies and testing of mercury  amalgam removal technologies in accordance with
protocols and Test Plans.

Vendor - a business that assembles or sells in-drain treatment equipment.

Verification - to establish evidence on the performance of in-drain treatment technologies under
specific conditions, following a predetermined study protocol(s) and test plan(s).

Verification  Organization -  an organization qualified  by EPA to verify  environmental
technologies and to issue verification statements and verification reports.

Verification  Report  - a  written document containing all  raw and analyzed data,  all quality
assurance/quality control  (QA/QC) data sheets, descriptions of all collected data,  a detailed
description of all procedures and methods used in the verification testing, and all QA/QC results.
The test plan(s) shall be included as part of this document.

Verification  Statement - a document that summarizes the Verification Report reviewed and
approved and signed by EPA and NSF.

Verification Test Plan - a written document prepared to describe the procedures for conducting
a test or study according to the verification  protocol requirements for the application  of in-drain
treatment technology.  At a minimum, the test plan shall include detailed instructions  for sample
and data collection, sample handling and preservation, precision, accuracy, goals, and QA/QC
requirements relevant  to the technology and  application.
                                           86

-------
                                 Appendices
A     Test Plan
B     UpFlo™ Filter O&M Manual
C     Analytical Data
                                      87

-------