September 2005
                           NSF05/14b/EPADWCTR
                              EPA600/R-05/122
Environmental Technology
Verification Report

Removal of Chemical Contaminants in
Drinking Water

EcoWater Systems Incorporated
ERO-R450E Drinking Water Treatment
System
                Prepared by
             NSF International


          Under a Cooperative Agreement with
         U.S. Environmental Protection Agency

-------

-------
         THE ENVIRONMENTAL TECHNOLOGY VERIFICATION
                                      PROGRAM
  U.S. Environmental Protection Agency
                                                                     NSF International
                    ETV Joint Verification Statement
TECHNOLOGY TYPE:

APPLICATION:


PRODUCT NAME:

COMPANY:

ADDRESS:


PHONE:

EMAIL:
                            POINT-OF-USE DRINKING WATER TREATMENT SYSTEM

                            REMOVAL OF CHEMICAL CONTAMINANTS IN DRINKING
                            WATER

                            ECOWATER SYSTEMS ERO-R450E

                            ECOWATER SYSTEMS, INC.

                            1890 WOODLANE DRIVE

                            WOODBURY,MN 55125

                            800-808-9899

                            INFO(%ECOWATERCOM
NSF International (NSF) manages the Drinking Water Systems (DWS) Center under the U.S.
Environmental Protection Agency's (EPA) Environmental Technology Verification (ETV) Program.  The
DWS Center recently evaluated the performance of the EcoWater Systems ERO-R450E point-of-use
(POU) drinking water treatment system.  NSF performed all of the testing activities, and also authored the
verification report and this verification statement.  The verification report contains a comprehensive
description of the test.

EPA created the ETV Program to facilitate the deployment of innovative or improved environmental
technologies through performance verification and dissemination of information.  The goal of the ETV
Program is to further environmental protection by accelerating the  acceptance and use of improved and
more cost-effective technologies.  ETV seeks to achieve this goal by providing high-quality, peer-
reviewed data on technology performance to those involved in the  design, distribution, permitting,
purchase, and use of environmental technologies.

ETV works in partnership with recognized standards and testing organizations, stakeholder groups
(consisting of buyers, vendor organizations, and permitters), and with the full participation of individual
technology developers. The program evaluates the performance of innovative technologies by developing
test plans that are responsive to the needs of stakeholders, conducting field or laboratory tests (as
appropriate), collecting and analyzing data, and preparing peer reviewed reports.  All evaluations are
conducted in accordance with rigorous quality assurance protocols to ensure that data of known and
adequate quality are generated and that the results are defensible.
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.       September 2005
                                            VS-i

-------
ABSTRACT

The EcoWater Systems ERO-R450E POU drinking water treatment system was tested for removal of
aldicarb, benzene, cadmium, carbofuran, cesium, chloroform, dichlorvos, dicrotophos, fenamiphos,
mercury, mevinphos, oxamyl, strontium, and strychnine.  The ERO-R450E employs a reverse osmosis
(RO) membrane and activated carbon filters to treat drinking water. Treated water is stored in a 3.1-
gallon capacity storage tank. The system was first tested with only the RO membrane component in
place. The target challenge concentration for each chemical for the RO membrane tests was 1 mg/L.
Following the RO membrane challenges, the post-membrane carbon filter component was challenged
alone with each organic chemical the RO membrane did not remove to below 30 |o,g/L. The carbon filter
was also challenged with cesium and mercury because the membranes did not remove these two
substances as well as total dissolved solids (TDS) in general. The target challenge concentration for the
carbon filter tests was the maximum effluent level measured during the RO membrane tests.

A total of 20 RO membrane components were tested, divided into ten pairs. Each pair of membranes was
tested with only one of the ten organic chemicals because of concern that a chemical could compromise
the integrity of the membrane or membrane seals. One pair of RO membrane components was also
challenged with the inorganic chemicals. Each RO membrane chemical challenge was conducted over a
one-day period.  Influent and effluent samples were collected during the operation period, and also the
next morning. The post-membrane carbon filter challenges were conducted over a 15-hour duration.
Two filters were tested for each chemical challenge, and each pair was only used for one challenge.
Influent and effluent samples were collected at the beginning, middle, and end of the challenge period.

The ERO-R450E as a whole, considering both the RO membrane challenge and post-membrane carbon
filter challenge results combined, reduced all of the challenge chemicals but cesium by 94% or more.

TECHNOLOGY DESCRIPTION

The following technology description was provided by the manufacturer, and has not been verified.

The ERO-R450E is a three-stage POU drinking water treatment system, employing an RO membrane,
and activated carbon filters both upstream and downstream of the membrane.  The system includes a 3.1-
gallon maximum capacity pressurized bladder tank for storing the treated water, and a faucet to mount on
the kitchen sink. The  influent water first passes through a carbon filter designed to remove chlorine and
particulate matter, such as rust and silt. The second stage of treatment is the reverse osmosis membrane,
which reduces a wide  variety of contaminants.  The permeate water is sent to the storage tank. When the
user opens the faucet,  the partially treated water leaves the storage tank, passes through a second carbon
filter to remove organic chemicals and any taste and odor chemicals, and then exits the faucet.

When the flow of water into the system is started, treated water will be continually produced until the
storage tank is nearly full. At that time, the water pressure in the tank activates an automatic shut-off
device, stopping the flow of water through the system.  After a portion of the water is dispensed from the
storage tank, the shut-off device deactivates, allowing water to again flow into the system until the storage
tank is nearly full.
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.      September 2005
                                             VS-ii

-------
VERIFICATION TESTING DESCRIPTION

Test Site

The testing site was the Drinking Water Treatment Systems Laboratory at NSF in Ann Arbor, Michigan.
A description of the test apparatus can be found in the test/QA plan and verification report. The testing
was conducted November 2004 through March 2005.

Methods and Procedures

Verification testing followed the procedures and methods detailed in the Test/QA Plan for Verification
Testing of the EcoWater Systems ERO-R450E Point-of-Use Drinking Water Treatment System for
Removal of Chemical Contamination Agents. Because any contamination event would likely be short-
lived, the challenge period for each chemical lasted only one day. Long-term performance over the life of
the membrane was not evaluated.

The system was first tested with only the RO membrane component in place.  The complete ERO-R450E
system, including the storage tank, was used for the RO membrane challenges, but the carbon filters were
removed, leaving empty housings. A total of 20 RO membranes were challenged with the chemicals in
Table 1. The target challenge concentration for each chemical was 1 mg/L. The 20 membrane test units
were divided into ten pairs. Each pair was tested with only one of the ten organic chemicals because of
concern that a chemical, especially benzene or chloroform, could compromise the integrity of the
membrane or membrane seals. One pair of RO membrane components was also challenged with the
inorganic chemicals.  The inorganic chemical challenges were conducted prior to the organic  chemical
challenges to eliminate the possibility of damage to the membranes that could bias the inorganic chemical
test results. The reduction of TDS was also measured during the challenges to evaluate whether any
organic chemicals damaged the membrane material or membrane seals.
                               Table 1. Challenge Chemicals

                   Organic Chemicals	Inorganic Chemicals	
                       Aldicarb                   Cadmium Chloride
                       Benzene          Cesium Chloride (nonradioactive isotope)
                      Carbofuran                  Mercuric Chloride
                      Chloroform        Strontium Chloride (nonradioactive isotope)
                      Dicrotophos
                      Dichlorvos
                      Fenamiphos
                      Mevinphos
                       Oxamyl
                      Strychnine	
Prior to challenge testing, the RO membrane components were service-conditioned for seven days by
feeding the systems the test water without any chemical spikes. After completion of the conditioning
period, the membranes were subjected to a TDS reduction test using sodium chloride to verify that they
were operating properly.

Each RO membrane chemical challenge was conducted over a one-day period. The systems were
operated for six tank-fill periods, and then were allowed to rest overnight. Influent and effluent samples
were collected at start-up, after the 3rd tank fill, after the 5th tank fill, and the next morning after the
membranes rested under pressure overnight.
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.       September 2005
                                             VS-iii

-------
Following the RO membrane challenges, the post-membrane carbon filters were challenged with the
chemicals that the RO membranes did not remove to below 30 |o,g/L. The carbon filter was also
challenged with cesium and mercury because the membranes did not remove these two substances as well
as total dissolved solids (TDS) in general. The filters were attached to a separate manifold that was of the
same design as the manifold in the full RO system.  The pre-membrane carbon filter was not tested
because it is only designed to remove chlorine to protect the RO membrane.  Two carbon filters were
tested for each chemical challenge, and each filter was only used for one challenge. The target challenge
concentrations were the maximum effluent levels measured during the RO membrane tests.

Prior to testing, each carbon filter was service-conditioned by feeding water containing chloroform to
simulate the possible contaminant loading on the carbon halfway through the filter's effective lifespan.
The target chloroform concentration was 300 ± 90 |o,g/L, which is the influent challenge concentration for
the VOC reduction test in NSF/ANSI Standard 53 (chloroform is the surrogate challenge chemical for the
test).  The filters were operated at a flow rate of 0.5 gallons per minute (gpm) for 375  gallons (EcoWater
System's design capacity for the filter is 750 gallons).

The post-membrane carbon filter challenges were 15 hours in duration. Influent and effluent samples
were collected at the beginning, middle, and end of the challenge period.  The carbon  filters were
operated on an "on/off operation cycle where the "on" portion was the time required to empty the system
storage tank when full, and the "off portion was the time required to fill the storage tank.

VERIFICATION OF PERFORMANCE

The results of the RO membrane challenges are presented in Table 2. The RO membrane treatment
process removed 94% or more of all challenge chemicals except cesium and mercury.  The membrane
removed 82% of cesium, and only 9% of the mercury challenge.
                          Table 2. RO Membrane Challenge Data

                                  Mean Influent  Mean Effluent     Percent
                       Chemical	Qg/L)	(|ag/L)     Reduction (%)
Cadmium
Cesium
Mercury
Strontium
Aldicarb
Benzene
Carbofuran
Chloroform
Dichlorvos
Dicrotophos
Fenamiphos
Mevinphos
Oxamyl
Strychnine
960
930
1100
960
1000
980
1100
1100
1300
1100
930
1200
980
1100
33
170
1000
33
20
7.1
19
61
69
57
4
46
10
10
97
82
9
97
98
>99
98
94
95
95
>99
96
99
>99
The TDS reduction by each membrane component for all challenge tests was 87% or higher. The effluent
TDS levels for some of the chemical challenges rose from one sample point to the next over the challenge
period, but no TDS levels were significantly higher than the maximum TDS levels measured during TDS
reduction tests conducted on each unit after conditioning.  Thus, the rising TDS levels likely do not
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.       September 2005
                                            VS-iv

-------
indicate that the membrane components were becoming significantly compromised due to exposure to the
chemicals.  The increase may have been due to the challenge protocol design. The challenges began with
empty storage tanks, so there was no back-pressure on the membranes when the start-up samples, which
all had the lowest observed TDS levels, were collected. Most of the challenge chemical levels were also
lowest in the start-up samples.  The rest of the samples were collected after the membranes had been
operating facing back-pressure from the storage tanks.  RO membranes perform better without back-
pressure, so the higher TDS levels are likely more indicative of the performance of the RO system under
normal operating conditions.

The post-membrane carbon filter components were challenged with chloroform, dichlorvos, dicrotophos,
and mevinphos based on the criteria that the RO membrane  challenge effluents were above 30 |og/L.  The
carbon filters were also challenged with cesium and mercury.  The target challenge levels were the
maximum effluent levels measured during the RO membrane challenges. The carbon filters were
operated at 1.15 gpm on an operating cycle  where the "on" portion was five minutes and eleven seconds,
and the "off portion was one hour and ten minutes.

The carbon challenge results are shown below in Table 3. Note that the percent reduction of dicrotophos
was limited by the detection limit for the chemical.  The carbon filter removed 89% or more of all of the
challenge chemicals but cesium, which was effectively not removed at all by the carbon.
                  Table 3. Post-Membrane Carbon Filter Challenge Data
                                  Mean Influent  Mean Effluent     Percent
                      Chemical	(|ag/L)	(|ag/L)     Reduction (%)
Cesium
Mercury
Chloroform
Dichlorvos
Dicrotophos
Mevinphos
230
760
100
100
90
40
220
35
0.7
3.9
ND(10)
2.1
4.3
95
>99
96
89
95
The RO membrane and carbon challenge data combined shows that the two treatment technologies
working in concert within the ERO-R450E system removed 97% or more of all challenge chemicals but
cesium.

Complete descriptions of the verification testing results are included in the verification report.

QUALITY ASSURANCE/QUALITY CONTROL (QA/QC)

NSF ETV and QA staff monitored the testing activities to ensure that the testing was in compliance with
the test plan. NSF also conducted a data quality audit of 100% of the data.  Please see the verification
report referenced below for more QA/QC information.
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.       September 2005
                                             VS-v

-------
    Original signed by Andrew Avel, 10/25/05	   Original signed by Robert Ferguson,  11/07/05
    Andrew P. Avel                       Date        Robert Ferguson                     Date
    Acting Director                                   Vice President
    National Homeland Security Research Center       Water Systems
    United States Environmental Protection             NSF International
    Agency
    NOTICE:  Verifications  are based  on  an evaluation  of  technology  performance under  specific,
    predetermined criteria and the appropriate quality assurance procedures. EPA and NSF make no expressed
    or implied warranties as to the performance of the technology and do not certify that a technology will
    always operate as verified.  The end-user is solely responsible for complying with any and all applicable
    federal, state, and local requirements. Mention of corporate names, trade names, or commercial products
    does not constitute endorsement or recommendation for use of specific products. This report is not an NSF
    Certification of the specific product mentioned herein.	
     Availability of Supporting Documents
     Copies of the test protocol, the verification statement, and the verification report (NSF report # NSF
     04/14b/EPADWCTR) are available from the following sources:
     (NOTE: Not all of the appendices are included in the verification report. The appendices are available
     from NSF upon request.)

     1.   ETV Drinking Water Systems Center Manager (order hard copy)
         NSF International
         P.O. Box 130140
         Ann Arbor, Michigan 48113-0140
     2.   NSF web site: http://www.nsforg/etv/dws/dws_reports.html, and from
         http://www.nsforg/etv/dws/dws_project_documents.html (electronic copy)
         EPA web site: https://www.epa.gov/etv (electronic copy)
NSF 05/14b/EPADWCTR   The accompanying notice is an integral part of this verification statement.        September 2005
                                                VS-vi

-------
                                                    September 2005
    Environmental Technology Verification Report
Removal of Chemical Contaminants in Drinking Water

            EcoWater Systems Incorporated
    ERO-R450E Drinking Water Treatment System
                        Prepared by:

                      NSF International
                  Ann Arbor, Michigan 48105
Under a cooperative agreement with the U.S. Environmental Protection Agency

                Jeffrey Q. Adams, Project Officer
           National Risk Management Research Laboratory
              U.S. Environmental Protection Agency
                    Cincinnati, Ohio 45268

-------
                                       Notice

The  U.S.  Environmental  Protection  Agency  (USEPA) through its Office  of Research and
Development has financially supported and collaborated with NSF International (NSF) under
Cooperative Assistance Agreement No. R-82833301.  This verification effort was supported by
the Drinking  Water Systems (DWS) Center,  operating under the Environmental Technology
Verification  (ETV) Program. This document  has been peer-reviewed, reviewed by NSF and
USEPA, and recommended for public release.
                                         11

-------
                                       Foreword

The U.S. Environmental Protection Agency (USEPA) is charged by Congress with protecting the
Nation's land, air, and water resources. Under a mandate of national environmental laws, the
Agency strives to formulate and implement actions leading to a  compatible balance between
human activities  and the ability of natural systems to  support and nurture life. To meet this
mandate, USEPA's research program is providing  data  and technical  support  for  solving
environmental problems today and building a science knowledge base necessary to manage our
ecological resources wisely, understand how pollutants affect our health, and prevent or reduce
environmental risks in the future.

The National  Risk Management Research Laboratory  (NRMRL) is  the  Agency's center for
investigation of technological and management approaches for preventing and reducing risks
from pollution that threaten human health and the environment. The focus of the Laboratory's
research program is on methods and their cost-effectiveness for prevention and control  of
pollution to air, land, water, and subsurface resources;  protection of water quality in public water
systems; remediation of contaminated sites, sediments and ground water; prevention and control
of indoor air pollution; and restoration of ecosystems.  NRMRL  collaborates with both public
and private  sector partners to foster technologies that  reduce the cost of compliance and to
anticipate emerging problems. NRMRL's research provides solutions to environmental problems
by: developing and promoting technologies that protect and improve the environment; advancing
scientific and engineering information  to support regulatory and policy decisions; and providing
the technical  support  and information transfer  to  ensure  implementation of environmental
regulations and strategies at the national, state, and community levels.

This publication has been produced as part of the Laboratory's strategic long-term research plan.
It is published and made available by  USEPA's Office  of Research and Development to assist
the user community and to link researchers with their clients.
                                                                 Sally Gutierrez, Director
                                           National Risk Management Research Laboratory
                                           in

-------
                                   Table of Contents

Verification Statement [[[ VS-i
Title Page [[[ i
Notice [[[ ii
Foreword [[[ iii
Table of Contents [[[ iv
List of Tables [[[ vi
List of Figures [[[ vi
Abbreviations and Acronyms [[[ vii
Acknowlegements [[[ viii
Chapter 1 Introduction 	
1 . 1 Environmental Technology Verification (ET V) Program Purpose and Operation
12 Purpose of Verification
1 3 Development of Test/Quality Assurance (QA) Plan
1 . 4 Challenge Chemical s 	
1 . 5 Testing Participants and Responsibilities 	
1 5 1 NSF International
152 EcoWater Systems Inc
1.5.3 U.S. Environmental Protection Asencv 	
1
.... 1
1
1
7
7
9
3
3
Chapter 2 Equipment Description [[[ 4
  2.1    Principals of Operation [[[ 4
     2.1.1    Activated Carbon [[[ 4
     2.1.2    RO Membrane [[[ 4
  2.2    Equipment Capabilities [[[ 4
  2.3    System Components [[[ 4
  2.4    System Operation [[[ 5
  2.5    Rate of Waste Production [[[ 6

-------
      3.2.4.2   Post-Membrane Carbon Filter Test Units	13
    3.2.5     Challenge Protocols and Sampling Plans	13
      3.2.5.1   TDS Reduction System Performance Check	13
      3.2.5.2   RO Membrane Challenge Testing	13
      3.2.5.3   Post-Membrane Carbon Filter Challenge Testing	15
  3.3    Analytical Methods	17
    3.3.1     Water Quality Analytical Methods	17
    3.3.2     Challenge Chemical Analytical Methods	18
Chapter 4 Results and Discussion	20
  4.1    RO membrane Conditioning	20
    4.1.1     RO Membrane System Operation Data	20
  4.2    Post-Membrane Carbon Filter Conditioning	20
  4.3    TDS Reduction System Performance Check	21
  4.4    RO Membrane Chemical Challenges	21
    4.4.1     Inorganic Chemicals Challenges	21
    4.4.2     Organic Chemical Challenges	23
  4.5    Post-Membrane Carbon Filter Challenges	25
  4.6    Conclusions	26
Chapters QA/QC	27
  5.1    Introduction	27
  5.2    Test Procedure QA/QC	27
  5.3    Sample Handling	27
  5.4    Analytical Methods QA/QC	27
  5.5    Documentation	28
  5.6    Data Review	28
  5.7    Data Quality Indicators	28
    5.7.1     Representativeness	28
    5.7.2     Accuracy	28
    5.7.3     Precision	29
    5.7.4     Completeness	30
      5.7.4.1   Number of Systems Tested	30
      5.7.4.2   Water Chemistry Measurements	30
      5.7.4.3   Challenge Chemicals	31
Chapter 6	32

-------
                                     Appendix

Appendix A   Conditioning and Chemical Challenges Data Tables



                                   List of Tables

Table 1-1.  Challenge Chemicals	2
Table 3-1.  Challenge Chemicals	9
Table 3-2.  Summary of Sampling Plan for RO Membrane Challenges	16
Table 3-3.  Summary of Sampling Plan for Post-Membrane Carbon Filter Challenges	17
Table 3-4.  QC Limits and Method Reporting Limits for Analyses	18
Table 4-1.  RO Membrane System Operation Data	20
Table 4-2.  Post-Membrane Carbon Filter Conditioning Influent Water Chemistry	21
Table 4-3.  RO Membrane Inorganic Chemical Reduction Data	22
Table 4-4.  Inorganic Chemical Challenge Reject Water Data	23
Table 4-5.  RO Membrane Organic Chemical Challenge Data	23
Table 4-6.  TDS Reduction Data for Organic Chemical Challenges	24
Table 4-7.  Organic Chemical Challenge Reject Water Data	24
Table 4-8.  Post-Membrane Carbon Filter Challenge Data	25
Table 4-9.  Combined Performance of RO Membrane and Post-Membrane Carbon Filter	26
Table 5-1.  Completeness Requirements	30



                                   List of Figures

Figure 2-1. Photograph of the ERO-R45 OE	5
Figure 2-2. Schematic Diagram of the ERO-R450E	6
Figure 3-1. RO Membrane Systems Installed at Test Station	14
Figure 3-2. Post-Membrane Carbon Filters Installed at Test Station	16
                                         VI

-------
                            Abbreviations and Acronyms
ANSI
°C
DWS
DWTS
ETV
°F
GC/MS
gpd
gpm
HC1
HPLC
ICP/MS
L
LFB
LFM
mg
mL
NaOH
ND
NRMRL
NSF
NTU
POE
POU
psi
QA
QC
QA/QC
RO
RPD
RSD
SOP
IDS
TOC
Hg
USEPA
VOC
American National Standards Institute
Degrees Celsius
Drinking Water Systems
Drinking Water Treatment Systems
Environmental Technology Verification
Degrees Fahrenheit
Gas Chromatography/Mass Spectrometry
Gallons Per Day
Gallons Per Minute
Hydrochloric Acid
High Pressure Liquid Chromatography
Inductively Coupled Plasma - Mass Spectrometry
Liter
Laboratory Fortified Blank
Laboratory Fortified Matrix
Milligram
Milliliter
Sodium Hydroxide
Non-detect
National Risk Management Research Laboratory
NSF International (formerly known as National Sanitation Foundation)
Nephelometric Turbidity Unit
Point-of-Entry
Point-of-Use
Pounds per Square Inch
Quality Assurance
Quality Control
Quality Assurance/Quality Control
Reverse Osmosis
Relative Percent Difference
Relative Standard Deviation
Standard Operating Procedure
Total Dissolved Solids
Total Organic Carbon
Microgram
U. S. Environmental Protection Agency
Volatile Organic Chemical
                                         vn

-------
                                   Acknowledgments

NSF was responsible for all elements in the testing sequence, including collection of samples,
calibration and verification of instruments, data collection and analysis, data management, data
interpretation and the preparation of this report.

The manufacturer of the equipment was:

       EcoWater Systems Incorporated
       1890 Woodlane Drive
       Woodbury, MN 55125

NSF wishes to thank the members of the expert technical panel for their assistance with
development of the test plan.
                                          Vlll

-------
                                       Chapter 1
                                     Introduction
1.1    Environmental Technology Verification (ETV) Program Purpose and Operation
The U.S. Environmental Protection Agency (USEPA) has created the ETV Program to facilitate
the deployment of innovative or improved environmental technologies through performance
verification and dissemination of information. The goal of the ETV Program is to further
environmental protection by accelerating the acceptance and use of improved and more cost-
effective technologies. ETV seeks to achieve this goal by providing high-quality, peer-reviewed
data on technology performance to those involved in the design, distribution, permitting,
purchase, and use of environmental technologies.

ETV works in partnership with recognized standards and testing organizations; with stakeholder
groups consisting of buyers, vendor organizations, and permitters; and with the full participation
of individual technology developers.  The program evaluates the performance of innovative
technologies by developing test plans that are responsive to the needs of stakeholders, by
conducting field or laboratory testing, collecting and analyzing data, and by preparing peer-
reviewed reports. All evaluations are conducted in accordance with rigorous quality assurance
protocols to ensure that data of known and adequate quality are generated and that the results are
defensible.

The USEPA has partnered with NSF International (NSF) under the ETV Drinking Water
Systems (DWS) Center to verify performance of drinking water treatment systems that benefit
the public and small communities. It is important to note that verification of the equipment does
not mean the equipment is "certified" by NSF or "accepted" by USEPA. Rather, it recognizes
that the performance of the equipment has been determined and verified by these organizations
under conditions  specified in ETV protocols and test plans.


1.2    Purpose of Verification

The purpose of this verification was to evaluate treatment system performance under a simulated
intentional or non-intentional chemical contamination event. Because any contamination event
would likely be short-lived, the challenge period for each chemical lasted only one day.  Long-
term performance over the life of the membrane was not investigated.


1.3    Development of Test/Quality Assurance (QA) Plan
USEPA's "Water Security Research and Technical Support Action Plan" (USEPA, 2004)
identifies the need to evaluate point-of-use (POU) and point-of-entry (POE) treatment system
capabilities for removing likely contaminants from drinking water.  As part of the ETV program,
NSF developed a test/QA plan for evaluating POU reverse osmosis (RO) drinking water
treatment systems for removal of chemical contaminants. To assist in this endeavor, NSF

-------
assembled an expert technical panel, which gave suggestions on a protocol design prior to
development of the test/QA plan.

The product-specific test/QA plan for evaluating the ERO-R450E was entitled Test/QA Plan for
Verification Testing of the EcoWater Systems ERO-R450E Point-of-Use Drinking Water
Treatment System for Removal of Chemical Contamination Agents.

By participating in this ETV evaluation, the vendor obtains USEPA and NSF verified
independent test data indicating potential user protection against intentional or non-intentional
chemical contamination of drinking water. Verifications following an approved test/QA plan
serve to notify the public  of the possible level of protection against chemical contamination
agents afforded to them by the use of a verified system.


1.4    Challenge Chemicals

The challenge chemicals for this verification are listed in Table 1-1.
                             Table 1-1.  Challenge Chemicals

                  Organic Chemicals	Inorganic chemicals	
                      Aldicarb                 Cadmium Chloride
                      Benzene         Cesium Chloride (nonradioactive isotope)
                     Carbofuran                Mercuric Chloride
                     Chloroform       Strontium Chloride (nonradioactive isotope)
                     Dicrotophos
                     Dichlorvos
                     Fenamiphos
                     Mevinphos
                      Oxamyl
                     Strychnine	
1.5    Testing Participants and Responsibilities

The ETV testing of the ERO-R450E was a cooperative effort between the following participants:

       NSF
       EcoWater Systems Inc.
       USEPA

The following is a brief description of each of the ETV participants and their roles and
responsibilities.


1.5.1   NSF International

NSF is a not-for-profit organization dedicated to public health and safety, and to protection of the
environment. Founded in  1946 and located in Ann Arbor, Michigan, NSF has been instrumental

-------
in the development of consensus standards for the protection of public health and the
environment.  The USEPA partnered with NSF to verify the performance of drinking water
treatment systems through the USEPA's ETV Program.

NSF performed all verification testing activities at its Ann Arbor location.  NSF prepared the
test/QA plan, performed all testing, managed, evaluated, interpreted, and reported on the data
generated by the testing, and reported on the performance of the technology.

Contact Information:

       NSF International
       789 N. Dixboro Road
       Ann Arbor, MI 48105
       Phone: 734-769-8010
       Fax: 734-769-0109
       Contact: Bruce Bartley, ETV Program Manager
       Email: bartley@nsf.org


1.5.2   EcoWater Systems Inc.

The ERO-R450E is manufactured by EcoWater Systems Inc., a manufacturer of residential and
commercial water treatment products.

The manufacturer was responsible for supplying the RO systems in accordance with Section
3.1.1, and for providing logistical and technical support as needed.

Contact Information:

       EcoWater Systems Inc.
       1890 Woodland Drive
       Woodbury, MN  55125
       Phone: 1-800-808-9899
       Contact Person: Ms. Ann Baumann


1.5.3   U.S. Environmental Protection Agency

The USEPA, through its Office of Research and Development, has financially supported and
collaborated with NSF under Cooperative Agreement No. R-82833301. This verification effort
was supported by the DWS Center operating under the ETV Program. This document has been
peer-reviewed, reviewed by the USEPA, and recommended for public release.

-------
                                      Chapter 2
                                Equipment Description
2.1    Principals of Operation

2.1.1   Activated Carbon

Activated carbon removes organic chemicals from water through the process of adsorption.  The
chemicals are attracted to and attach to the surface of the carbon through electrostatic
interactions. The adsorbent properties of activated carbon are a function of the raw material used
and the activation process. Once the carbon is saturated with adsorbed molecules, it must be
replaced.

2.1.2   RO Membrane

Membrane technologies are among the most versatile water treatment processes because of their
ability to effectively remove a wide variety of contaminants. RO membranes operate by the
principal of cross-flow filtration. In this process, the influent water flows over and parallel to the
filter medium and exits the system as reject water. Under pressure, a portion of the water
diffuses through the membrane becoming "permeate".  The membrane allows water molecules to
pass through its pores, but not most dissolved inorganic chemical molecules and larger molecular
weight organic chemical molecules. These molecules are concentrated in and washed away with
the reject water stream.

Unlike activated carbon,  which reaches and exhaustion  point and needs to be replaced, the
reduction capabilities of RO membranes remain in effect until the membrane is compromised.
Monitoring of membrane performance can be conducted by measuring the TDS of the permeate
water with a TDS monitor.


2.2    Equipment Capabilities
The ERO-R450E is certified by NSF to NSF/ANSI Standard 58 - Reverse Osmosis Drinking
Water Treatment Systems. The  system has a certified production rate of 22.2 gallons per day.
This measurement is based on system operation at 50 pounds per square inch (psi) inlet pressure,
a water temperature of 77 °F, and a total dissolved solids (TDS) level of 750 + 40 mg/L. The
amount and quality of treated water produced varies depending on the inlet pressure, water
temperature, and level of TDS.  These measurements were  not subject to verification during this
study.


2.3    System Components
The ERO-R450E is a three-stage POU treatment system, employing an RO membrane, and
activated carbon filtration both upstream and downstream of the membrane. The system
includes a 3.1-gallon maximum capacity pressurized bladder tank for storing the treated water,

-------
and a faucet to mount on the kitchen sink.  A photograph of the system is shown in Figure 2-1.
Please note that the information given in this section, and Section 2.4 is for informational
purposes only, and is not subject to verification.
                       Figure 2-1.  Photograph of the ERO-R450E
2.4    System Operation

Incoming water first passes through a carbon filter designed to remove chlorine and particulate
matter, such as rust and silt. The second stage of treatment is the reverse osmosis membrane,
which reduces a wide variety of inorganic and larger molecular weight organic contaminants,
and also protozoan cysts such as Cryptosporidium and Giardia. The permeate water is sent to the
storage tank.  When the user opens the faucet, the partially treated water leaves the storage tank,
passes through a second carbon filter to remove organic chemicals, mercury, and any taste and
odor chemicals, and then exits the faucet. Figure 2-2 shows a schematic diagram of the ERO-
R450E, with the path of water through the system illustrated.

-------
When the flow of water into the system is started, treated water will be continually produced
until the storage tank is nearly full. At that time, the water pressure in the tank causes an
automatic shut-off device to activate, stopping the flow of water through the system. After a
portion of the water is dispensed from the storage tank, the shut-off device deactivates, allowing
water to again flow into the system until the storage tank is nearly full. The operational storage
tank capacity will vary slightly from system to system, and may also be affected by the inlet
water pressure.  The capacity was measured to be approximately 2.5 gallons when the system
was tested for NSF/ANSI Standard 58 certification.
                                 BLUE
                                            PRODUCT WATER



PRODUCT
WATER
FAl ICFT //

ir gap ^
vn"
//
•t- /
//
J
* 4
t/







gravity
drain

t

X^



f


4

RED •»












drain flow

control
f AUTOMATIC \
SHUTOFF y \

WATER GREEN
IN " ^


f




**



t










»

\1


check
valve
j



YELLOW -41 i*>

1
\ 0 *
Jfi





—




4









t

IS
o«.






4
t





4









t









^-J-^


PRODUCT
WATER
STORAGE
s^ ^X
RO
                                          PREFILTER MEMBRANE  POSTFILTER

                   Figure 2-2. Schematic Diagram of the ERO-R450E
The ERO-R450E has a volume meter and TDS level meters that measure the volume of treated
water produced, and the level of TDS in the influent and effluent water. The faucet has a three
colored indicator light to tell the user when to replace the carbon filters and RO membrane.
Under normal operation, the indicator light is green. After six months have passed, or 750
gallons of treated water have been produced, the light changes to amber, indicating that the
carbon filters need to be replaced.  The light turns red when the RO membrane's TDS rejection
falls below 75%, as measured by comparing the influent and effluent TDS levels. When the red
light comes on, the RO membrane should be replaced. The user must reset the meters each time
any treatment elements are replaced.
2.5    Rate of Waste Production
The rate of reject water production was measured during the certification process for NSF/ANSI
Standard 58 certification. The efficiency rating, as defined by Standard 58 is the percentage

-------
measure of the amount of influent water delivered as permeate under a closed permeate
discharge set of actual use conditions.  The efficiency rating of the ERO-R450E is 9.7%, which
means the system produces approximately nine gallons of reject water for each gallon of product
water produced.  The efficiency rating was not verified as part of this evaluation.

2.6    Equipment Operation Limitations
EcoWater Systems gives the following operation limitations:
   •   feed water temperature of 40-100°F;
   •   feed water pressure of 40-100 psi;
   •   feed water pH 4-10;
   •   non-detectable iron, manganese, or hydrogen sulfide in the feed water supply;
   •   maximum inlet water TDS level of 2,000 mg/L;
   •   inlet water hardness of less than 10 grains per gallon (1 grain per gallon equals 17.1
       mg/L, expressed as calcium carbonate equivalent); and
   •   maximum inlet water chlorine level of 2 mg/L.

2.7    Operation and Maintenance Requirements
The following are the operation and maintenance requirements specified in the product owner's
manual:
   •   Replacement of the carbon filters when indicated by the meter (every six months or 750
       gallons);
   •   Replacement of the RO membrane cartridge when indicated  by the meter;  and
   •   Sanitization of the system when the carbon filters or RO membrane are replaced
       (instructions included in the owner's manual.)

-------
                                       Chapter 3
                               Methods and Procedures
3.1    Introduction

The challenge tests followed the procedures described in the Test/QA Plan for Verification
Testing of the EcoWater Systems ERO-R450E Point-of-Use Drinking Water Treatment System
for Removal of Chemical Contamination Agents.

As described in Section 2.3, the ERO-R450E employs an RO membrane and carbon filters to
treat drinking water. The system was first tested with only the RO membrane component in
place.  After the RO membrane challenges were complete, the post-membrane carbon filter was
challenged alone. This approach allowed an evaluation of the individual performance of each
component, and also served to simulate a worst-case scenario where the carbon filters are at or
past the end of their useful life. This approach also allowed each treatment component to be
challenged using a test water that presented more of a worse-case scenario for that component.
The pre-membrane carbon filter was not tested, because it is only designed to remove chlorine
and particulate matter to protect the RO membrane.


3.1.1   RO Membrane Challenges
The RO  membranes were challenged with each chemical in Table 3-1.  The target challenge
concentration for each chemical was 1 mg/L, which is much higher than most challenge levels in
the NSF/ANSI  Standards for POU devices.  Of the chemicals in Table 3-1  included in the POU
device standards, the highest challenge is chloroform at 450 (ig/L for the  total trihalomethanes
reduction test.

Only two membranes were challenged with each chemical. The organic chemical challenges and
mercury  challenge were conducted individually, but cadmium, cesium, and strontium were
combined into one challenge. Each membrane was only tested with one of the ten organic
chemicals, because of concern that some of them, especially benzene and chloroform, could
damage the membranes or membrane seals at the high challenge levels. This approach
eliminated the possibility that membrane performance against subsequent chemicals was
negatively biased. TDS reduction was also measured during the challenges, to serve as a
membrane performance benchmark, and also to evaluate whether any organic chemicals
damaged the membrane or integrity of the membrane seals.

A total of twenty RO membranes were tested, divided into ten pairs.  The inorganic chemical
challenges were conducted first. The systems tested for the inorganic chemical challenges were
used again for an organic chemical challenge. As discussed in Section 1.2, each challenge period
was only one day. The systems were operated for six tank-fill periods, and then were allowed to
rest overnight. Influent and effluent samples were collected during the operation period, and also
the next morning after the rest period.  In addition to influent and  effluent samples, reject water
samples were also collected and analyzed in an attempt to determine whether any of the

-------
chemicals adsorbed onto or absorbed into the membrane material in significant amounts.  See
Section 3.2.5.2 for RO membrane challenge protocol details.
                             Table 3-1.  Challenge Chemicals

                  Organic Chemicals	Inorganic Chemicals	
                      Aldicarb                 Cadmium Chloride
                      Benzene         Cesium Chloride (nonradioactive isotope)
                     Carbofuran                Mercuric Chloride
                     Chloroform       Strontium Chloride (nonradioactive isotope)
                     Dicrotophos
                     Dichlorvos
                     Fenamiphos
                     Mevinphos
                      Oxamyl
                     Strychnine
3.1.2   Post-Membrane Carbon Filter Challenges

The post-membrane carbon filter was tested alone for reduction of some of the chemicals.  The
carbon filter was challenged with the organic chemicals the RO membrane did not remove to a
level of 30 |j,g/L or less. The inorganic chemicals were considered on a case-by-case basis, since
USEPA does not consider carbon to be the best available technology for removing cadmium,
cesium, or strontium. As with the membranes, the carbon filters were challenged in pairs, and
each pair was only tested once. Each challenge was 15 hours.  The target challenge
concentrations for the carbon filter tests were the maximum effluent levels measured during the
RO tests.  See Section 3.2.5.3  for the post-membrane carbon filter test protocol details.


3.1.3   System  Operation Scenarios

The challenge protocol was designed to evaluate system performance under two  different
operation  scenarios. The first is operation with the product water storage tank over half full,
giving high back-pressure.  This is how the system is likely to operate in the home, as the user
will usually dispense small volumes of water until the shut-off valve deactivates, allowing the
storage tank to fill again.  RO  membrane performance is affected by the net driving pressure on
the membrane.  The net driving pressure is the feed water pressure minus the osmotic pressure
minus the back-pressure from the storage tank.  As the storage tank fills up and the tank bladder
expands, the back-pressure increases, reducing the net driving pressure. As the net driving
pressure drops,  the ion rejection performance of the membrane can also drop (Slovak, 2000).

This test protocol was designed so that the membranes operate for multiple tank  fills under
conditions where the net driving pressure was as low as possible. After the first  tank fill, the lab
technician dispensed the product water to the drain until the shut-off valve deactivated, allowing
the RO membrane to again produce treated water. This cycle was repeated for a total  of five
storage tank fill periods.

-------
The second operation scenario is continued contaminant rejection while the system is at rest.
The NSF/ANSI Standard 58 testing protocols call for a two-day stagnation period to check
whether the membrane can maintain rejection of the contaminants.  NSF has observed that RO
systems can give higher contaminant concentrations after the rest period than before.  This
phenomenon is due to the membrane's difficulty maintaining the osmotic differential across the
membrane, and perhaps also imperfections in the membrane material. At the end of each
challenge, the membranes were allowed to rest under pressure overnight, and product water
samples were collected for analysis the next morning.


3.2    Verification Test Procedure

3.2.1   Challenge Protocol Tasks

The following are the tasks in the challenge protocol, and the order in which they were
conducted:
       1.  Installation of the RO membrane devices  on the test rig, and seven days of
          conditioning (Section 3.2.4.1);
       2.  One-day TDS challenge test to evaluate system integrity (Section 3.2.5.1);
       3.  Conditioning of the post-membrane carbon filters while the RO membrane tests are
          being conducted (Section 3.2.4.2); and
       4.  Chemical challenge tests
          a.  RO inorganic chemical challenges (Section 3.2.5.2)
          b.  RO organic chemical challenges (Section 3.2.5.2)
          c.  Post-membrane carbon filter challenges (Section 3.2.5.3).


3.2.2   Test Rig

All test units were plumbed to "injection rig" test stations in the NSF Drinking Water Treatment
Systems Testing Laboratory.  The injection rigs have a common 90-gallon tank to hold the test
water without the challenge chemicals.  Fresh water is periodically  added to the tank as it is
being used. Online monitors and a computer system automatically  control the water level and
water chemistry. Downstream of the feedwater tank, a precisely controlled pump is used to
inject the challenge chemical(s) at the proper concentrations. Immediately downstream of the
pump lies a motionless in-line mixer to assure complete mixing of the challenge water.  An
influent sample port is downstream of the in-line mixer. No schematic diagram of the injection
rig is available, due to the proprietary nature of the design.


3.2.3   Test Water

3.2.3.1    RO Membrane Conditioning and Challenge Test Water
The test water for the RO membrane conditioning and challenges was a synthetic water
constructed from deionized municipal drinking water. The municipal water was  first filtered
through activated carbon to remove chlorine, then deionized and treated with reverse osmosis.
Sodium chloride was added for TDS, and the pH was adjusted with hydrochloric acid (HC1) or
                                           10

-------
sodium hydroxide (NaOH), if necessary, to achieve the following characteristics prior to addition
of the challenge chemical(s):
   •   pH - 7.5 ± 0.5 for the IDS reduction test, conditioning, and organic chemical challenges,
       6.0-6.5 for the inorganic chemicals challenge;
   •   total chlorine - < 0.05 mg/L;
   •   temperature - 25 ±  1 °C;
   •   IDS - 750 ± 75 mg/L; and
   •   turbidity - < 1 Nephelometric Turbidity Unit (NTU).

TDS, pH, temperature, and turbidity were maintained within the appropriate range by a computer
system with on-line monitors.  In addition, grab samples were collected and analyzed for all
parameters according to the sampling plans described in Sections 3.2.4.1, 3.2.5.1, and 3.2.5.2.
Note that the pH specification for the inorganic chemicals challenges was 6.0 to 6.5, to ensure
that the metals were present as dissolved free ions in the challenge water. This ensured that the
inorganic chemicals challenges were testing the ability of the RO membrane to reject the ions
instead of physically removing suspended particles of the metals.


3.2.3.2    Post-Membrane Carbon Filter Conditioning and Test Water

The test water for post-membrane carbon filter conditioning and testing was the "general test
water" specified in NSF/ANSI Standard 53, Drinking water treatment units - health effects (NSF
International, 2002). This water is the Ann Arbor municipal drinking water that is adjusted, if
necessary, to have the following characteristics prior to addition of the challenge chemical:
   •   pH-7.5 ±0.5;
   •   TDS - 200-500 mg/L
   •   temperature - 20 ± 2.5 °C;
   •   total organic carbon (TOC) - > 1.0 mg/L; and
   •   turbidity - < 1 NTU.

Please note that the TOC parameter only has a minimum  level specified, since it is the natural
TOC in the municipal water supply. The natural TOC in the water supply ranged from 2.1 to 2.8
mg/L during testing. However, the TOC levels in the organic chemical challenge waters were
much higher due to the methanol used as the carrier solution for the chemicals.

TDS, pH, and temperature were maintained within the appropriate range by a computer system
with on-line monitors.  The pH of the Ann Arbor drinking water was above 7.5 during the test
period, so the pH was adjusted with HC1.  The TDS level was within the allowable range, so no
adjustments were needed. The water was not dechlorinated prior to use.

Grab samples were collected and analyzed for all parameters according to the sampling plans
described in Sections 3.2.4.2 and 3.2.5.3.  Total chlorine was also measured, although there is no
specification given for it as there is in Section 3.2.3.1 for the RO membrane test water.
                                           11

-------
3.2.3.3    Chemical Challenges

The appropriate chemical(s) were added to the base test waters given in Sections 3.2.3.1 and
3.2.3.2 to make the challenge waters.  The RO membrane challenge target concentration for each
chemical was 1 + 0.5 mg/L. The target challenge concentrations for the carbon filter tests were
the maximum effluent levels measured during the RO tests.  For each challenge, a concentrated
solution of the chemical(s) was made, and this mixture injected into the influent water stream at
an appropriate rate.  Due to analytical procedure lengths, the amount  of chemical to add to the
test water to achieve the proper challenge concentration was calculated based on the known
concentration in the feed solution.  The tests were conducted without waiting for confirmation of
the influent level from the chemistry laboratory.


3.2.4   Test System Installation and Conditioning

3.2.4.1    RO Membrane Test Units

The RO membranes were installed on the test rigs by an NSF DWTS Laboratory technician
according to the instructions in the ERO-R450E owner's manual.  The recommended
conditioning procedure of operation for six tank-fill periods was not conducted, instead the
membranes underwent a seven day, seven tank-fills conditioning period.  Previous POU RO
system ETV tests for microbial agents indicated that perhaps membrane performance does not
stabilize until after four or five days (four or five tank-fills) of conditioning.  A seven-day
conditioning period  ensured that the membranes were performing optimally prior to the chemical
challenges.

For the first six days, the membranes were operated at 60 + 3 psi inlet pressure for one storage
tank fill period per day using the water described in Section 3.2.3.1.  Influent water samples were
collected each day at the beginning of the operation period for analysis of pH, TDS, temperature,
total chlorine, and turbidity. The membranes  rested under pressure overnight, and the storage
tanks were emptied the next morning prior to beginning that day's operation period.

On the seventh day,  the membranes were instead operated at 80 + 3 psi inlet pressure. Influent
water samples were  collected at the beginning of the operation period for analysis of pH, TDS,
temperature, total chlorine, and turbidity. The times required to fill the storage tanks were
measured and recorded for the three test units whose tanks filled the fastest. On the morning of
the eighth day, the times to dispense the first liter of water and to empty the storage tanks with
the faucet fully open were measured and recorded for the three test units whose operation times
were recorded the previous day. The tank fill times, times to empty the storage tank, and first
liter flow rates were used to determine the operating parameters for the post-membrane carbon
filters during the carbon filter challenge tests.  The longest time to empty the storage tank was
used for the "on" time portion of the operating cycle. The shortest tank fill time was used for the
"off portion of the cycle.  The flow rates during the carbon filter challenges were set at the
fastest first liter flow rate.  Operation at 80 psi instead of 60 psi caused the tank fill time to be
shorter, which gave  a worse case testing scenario for the carbon filters. See Section 3.2.5.3 for
further discussion about the post-membrane carbon filter challenge tests.
                                           12

-------
3.2.4.2    Post-Membrane Carbon Filter Test Units

The carbon filters were plumbed to a test station and operated using the water described in
Section 3.2.3.2 amended with 300 + 90 |o,g/L of chloroform until 375 gallons passed through
each filter.  This is the volume equal to one-half of EcoWater System's stated capacity of 750
gallons for the filter.  The filters were operated at an inlet water pressure of 60 + 3 psi and a
maximum flow rate of 0.5 gallons per minute (gpm), on a ten minutes on, ten minutes off cycle.
Chloroform at 300 |o,g/L is the influent challenge concentration for the VOC (volatile organic
chemical) reduction test in NSF/ANSI Standard  53 (chloroform is the surrogate test chemical).
The chloroform served to load the carbon filters  to a degree that simulated contaminant loading
in the middle of their effective lifespan.  Influent samples were collected for analysis of
chloroform, pH, temperature, TOC, and turbidity at start-up,  approximately 25% of capacity, and
approximately 50% of capacity. Effluent samples were collected at the same three points for
chloroform analysis.

If the filters were not immediately used for a challenge test, they were stored with the
conditioning water still in them. The manifold inlets and outlets were closed off by valves to
ensure that the chloroform remained on the carbon.


3.2.5   Challenge Protocols and Sampling Plans

3.2.5.1    TDS Reduction System Performance Check

After the RO membrane conditioning period was complete, they underwent a short-term  TDS
reduction test to verify that they were operating properly. The challenge was conducted as
follows:
1.  The product water storage tanks were drained, and membrane operation was started at 50 ± 3
   psi inlet pressure using the water described in Section 3.2.3.1 without any challenge
   chemicals added.
2.  Immediately after the membranes began operation, influent samples were collected for
   analysis of pH, temperature, total chlorine, turbidity, and TDS.
3.  The systems were allowed to operate until the automatic  shut-off mechanisms  activated.
4.  The entire contents of the storage tanks were emptied into separate containers, and three 250
   mL samples were collected from each container for TDS  analysis.

Removal of 75% or more of the TDS was required for the use of each membrane for the
chemical challenges.


3.2.5.2    RO Membrane Challenge Testing
As discussed in  Section 3.1.1, the RO membrane test units were divided into ten pairs. The
inorganic chemical challenges were conducted first, followed by the organic chemicals. Figure
3-1 shows a pair of test devices plumbed to the test rig.

The challenge tests were conducted as follows:
1.  At the start of each challenge period, the test system storage tanks were emptied.
                                           13

-------
               Figure 3-1.  RO Membrane Systems Installed at Test Station
2.  The initial dynamic inlet water pressure was set at 50 + 3 psi, and test system operation was
   started using the test water described in Section 3.2.3.1 with the proper challenge chemical(s)
   added.
3.  Influent and effluent water samples were collected for analysis of the challenge chemical(s)
   and TDS immediately after the units began operation. Influent samples were also collected
   for analysis of pH, temperature, total chlorine, and turbidity.  The effluent samples were
   collected from the faucet that comes with the system. All influent and effluent samples for

   challenge chemical analysis were collected and analyzed in triplicate, except where
   indicated. To collect the triplicate samples, the volumes necessary to obtain the triplicate
   samples were  first collected into a polyethylene container, and then the triplicate samples
   were collected from that volume. Due to the volatility of benzene and chloroform, true
   triplicate samples were not collected for these chemicals. Instead, three consecutive replicate
   samples were  collected directly into the sample bottles that were delivered to the NSF
   Chemistry Laboratory. TDS samples were collected as single samples.
                                           14

-------
4.  While under operation for the first storage tank fill period, duplicate samples were collected
   from the reject water line of one of the systems for challenge chemical(s) analysis. Samples
   were collected at start-up, approximately halfway through, and approximately three-fourths
   of the way through the period.
5.  The units were operated continuously until the shut-off valves activated.  The faucets were
   then fully opened, and a minimum of one liter, the volume required for sample analysis, or
   the amount needed to fully deactivate the shut-off valve, was dispensed to drain from each
   system. Full deactivation was estimated by monitoring resumption of the flow of reject water
   as the product water is dispensed.  The shut-off valve was considered fully deactivated when
   the flow of reject water appeared to have fully resumed.
6.  Step 5 was repeated until five storage tank fill periods were complete. After the third storage
   tank fill period ended, influent and effluent samples were collected for analysis of the
   challenge chemical(s) and TDS.
7.  Approximately halfway through the last tank fill period, duplicate reject water samples were
   collected for challenge chemical(s) analysis.  The samples were collected from the same
   system from which the reject water samples were collected in step  4. This sample served to
   check whether any chemical adsorption/absorption observed during the first storage tank fill
   period was still occurring, or the membrane became saturated with the chemical.
8.  After the fifth storage tank fill, effluent samples were collected from each system for
   challenge chemical(s) and TDS analysis. Influent samples were collected for analysis of the
   challenge chemical(s), TDS, pH, temperature, total chlorine, and turbidity.  If a system did
   not resume operation after sample collection, the additional volume necessary to resume
   operation was dispensed from each system.
9.  The units were then allowed to operate until the shut-off valves activated, and then rest under
   pressure for at least eight hours. After the rest period, the faucets were fully opened, and the
   first draw out of each faucet was collected for single challenge chemical and TDS analysis.
   After collection of the first draw water, the rest of the contents of each storage tank were
   collected into  suitable containers, and three samples were collected from each volume for
   triplicate challenge chemical analysis.  Table 3-2 gives a summary of the sampling plan.

3.2.5.3    Post-Membrane Carbon Filter Challenge Testing

The post-membrane carbon filter in the ERO-R450E is downstream from the storage tank, so it
was tested at the flow rate measured at the faucet outlet during the RO membrane conditioning
step. Each challenge was 15 hours. The filters were operated on an "on/off operation cycle
where the "on" portion was the time required to empty the storage tank when full, and the "off
portion of the cycle was the time required to fill the storage tank at 80  psi inlet pressure,  as
measured during the RO membrane conditioning period.  Figure 3-2 shows a pair of carbon
filters being tested for dichlorvos removal.

The challenge tests were conducted as follows:
1.  The proper "on/off cycle parameters were entered into the test station computer.
                                           15

-------
          Table 3-2.  Summary of Sampling Plan for RO Membrane Challenges
                                     Influent Sample Numbers
        Sample Point
Water Chemistry
  Parameters
Challenge
Chemical
TDS
Effluent Sample Numbers
     (per system)
  Challenge
  Chemical       TDS
Start Up
  1 sample for
 each parameter
                                      1
1st Tank Reject Water Samples
   Startup
   Half Tank
   Three-fourths Tank
                                  2 (from one system)
                                  2 (from one system)
                                  2 (from one system)
3rd Tank Fill
5th Tank Fill
Reject Water - Halfway Through
5th Tank Fill
Post-Rest - First Draw
Post-Rest - Rest of Tank
3
1 sample for 3
each parameter



1 3
1 3
2 (from one system)
1
o
J
1
1

1

           Figure 3-2.  Post-Membrane Carbon Filters Installed at Test Station
                                            16

-------
2.  The initial dynamic inlet water pressure was set at 60 + 3 psi, and filter operation was started
   using the water described in Section 3.2.3.2 with the proper challenge chemical added.  The
   flow rate was adjusted as necessary using a valve downstream of each filter on the effluent
   line.
3.  Influent and effluent samples were collected for challenge chemical analysis immediately
   after operation began.  All effluent samples were collected during the last half of the "on"
   portion of the operation cycle, so that the dwell water was flushed out prior to sample
   collection.  All challenge chemical samples were collected and analyzed in triplicate. The
   sample volumes were those required to obtain the triplicate samples.
4.  Single influent samples were also collected for analysis of pH, TDS, temperature, TOC, total
   chlorine, and turbidity whenever challenge chemical samples were collected.
5.  After 7.5 and 15 hours of operation, second and third sets of influent and effluent samples
   were collected for challenge chemical analysis. The flow of challenge water through the
   filters was started manually if they were not in the "on" portion of the operation cycle.  Table
   3-3 gives a summary of the sampling schedule.
   Table 3-3.  Summary of Sampling Plan for Post-Membrane Carbon Filter Challenges

                             Influent Water    Challenge Chemical  Challenge Chemical
                           Chemistry Sample       Influent         Effluent Sample
              Sample Point	Numbers	SampleNumbers	Numbers
Startup
7.5 Hours
15 Hours
1 for each parameter
1 for each parameter
1 for each parameter
3
3
3
3
3
3
3.3    Analytical Methods

3.3.1   Water Quality Analytical Methods

The following are the analytical methods used during verification testing. All analyses followed
procedures detailed in NSF's Standard Operating Procedures (SOPs).  The reporting limits, and
the acceptable precision and accuracy for each parameter are shown in Table 3-4.
   •   pH - All pH measurements were made with an Orion Model SA 720 meter. The meter
       was operated according to the manufacturer's instructions, which are based on Standard
       Method 4500-H+.
   •   Temperature - Water temperature was measured using an Omega model HH11 digital
       thermometer.
   •   TDS (by  conductivity) -  TDS for the TDS reduction system check test was measured
       through  conductivity  according to Standard Method 2510 using a  Fisher Scientific
       Traceable™ Conductivity Meter.  This method has been validated for use with the test
       water; NSF uses this method for analysis of samples from  TDS reduction tests under
       Standard 58.
   •   TDS (gravimetrically) - The TDS in the carbon filter conditioning and challenge water
       was measured gravimetrically.  The method used was an adaptation of USEPA Methods


                                          17

-------
       160.3 and 160.4. An appropriate amount of sample was placed in a pre-weighed
       evaporating dish. The sample was evaporated and dried at 103-105 °C to a constant
       weight. The dish was then weighed again to determine the total solids weight.
       Total Chlorine - Total chlorine was measured according to Standard Method 4500-C1 G
       with a Hach Model DR/2010 spectrophotometer using AccuVac vials.
Table 3-4. QC Limits
Parameter Reporting Limit
pH NA
TDS (conductivity) 2 mg/L
TDS (gravimetric) 5 mg/L
TOC 0.1 mg/L
Total Chlorine 0.05 mg/L
Turbidity 0.1 NTU

Aldicarb 1.0 (o,g/L
Benzene 0.5 (o,g/L
Cadmium 0.3 (o,g/L
Carbofuran 1 (o,g/L
Cesium 1 (o,g/L
Chloroform 0.5 (o,g/L
Dicrotophos 10 (o,g/L
Dichlorvos 0.2 (o,g/L
Fenamiphos 4 (o,g/L
Mercury 0.2 (o,g/L
Mevinphos 0.2 (o,g/L
Oxamyl 1.0 (o,g/L
Strontium 2 (o,g/L
Strychnine 5 ^ig/L
LFB = Laboratory Fortified Blank
LFM = Laboratory Fortified Matrix
RPD = Relative Percent Deviation
RSD = Relative Standard Deviation
and Method Reporting
Acceptable Precision
(RPD or RSD)
RPD < 10%
RPD < 10%
RPD < 10%
RPD < 10%
RPD < 10%
RPD < 10%

RSD < 20%
RSD < 20%
RSD < 20%
RSD < 20%
RSD < 20%
RSD < 20%
RSD < 30%
RSD < 30%
RSD < 30%
RSD < 20%
RSD < 30%
RSD < 20%
RSD < 20%
RSD < 20%




Limits for Analyses
Acceptable Accuracy (% recovery)
90-110%
80-120%
90-110%
80-120%
90-110%
95-105%
LFB LFM
80-120% 65-135%
80-120% NA
85-115% 70-130%
80-120% 65-135%
85-115% 70-130%
80-120% NA
70-130% 70-130%
70-130% 70-130%
70-130% 70-130%
85-115% 70-130%
70-130% 70-130%
80-120% 65-135%
85-115% 70-130%
70-130%




3.3.2   Challenge Chemical Analytical Methods

The following are the analytical methods used during verification testing.  All analyses followed
procedures detailed in NSF SOPs.  The reporting limits, and the acceptable precision and
accuracy for each parameter are shown in Table 3-4.
   •   Aldicarb, Carbofuran, and Oxamyl were measured by high pressure liquid
       chromatography (HPLC) according to USEPA Method 531.1 or 531.2.
   •   Dichlorvos, Dicrotophos, Fenamiphos, and Mevinphos were measured by gas
       chromatography/mass spectrometry (GC/MS) according to USEPA Method 525.2.
   •   Cadmium, Chromium, Mercury, and Strontium were measured by Inductively Coupled
       Plasma - Mass Spectrometry (ICP-MS) according to USEPA Method 200.8.
                                         18

-------
•  Benzene and Chloroform were measured by purge and trap capillary gas chromatography
   according to USEPA Method 502.2.
•  There is no standard analytical method for strychnine. NSF developed a method to
   measure it using reverse phase HPLC with ultraviolet lamp detection.
                                      19

-------
                                       Chapter 4
                                 Results and Discussion
4.1    RO membrane Conditioning

As discussed in Section 3.2.4.1, the RO membranes were conditioned for seven days prior to the
chemical challenges.  All of the influent water quality parameters in Section 3.2.3.1 were
maintained within the allowable ranges.  The individual data values for these parameters can be
found in Table A-l of Appendix A


4.1.1   RO Membrane System Operation Data

As described in Section 3.2.4.1, the storage tank fill times, first liter dispense times, and times to
dispense the entire tanks were measured and recorded for the three systems whose tanks filled
the fastest.  The first liter flow rates were calculated for each system from the first liter dispense
times.  The results are given below in Table 4-1. This data was used to determine the operation
parameters for the carbon filter challenges.
Table 4-1. RO Membrane
Unit Tank Fill Time 1st Liter Time
Number (minutes) (seconds)
4
7
9
73
72
71
14.4
13.8
16.1
System Operation Data
1st Liter Flow
Rate (gpm) Tank Dispense Time
1.10
1.15
0.98
4 min.,
4 min.,
5 min.,
51 sec.
26 sec.
1 1 sec.
4.2    Post-Membrane Carbon Filter Conditioning

As described in Section 3.2.4.2, the post-membrane carbon filters were conditioned with water
containing 300 + 90 ug/L of chloroform until 375 gallons had passed through them.  Eight filters
were conditioned first, and then another seven were conditioned later. Influent and effluent
samples were collected for analysis at start-up, approximately 188 gallons, and approximately
375 gallons. The influent and effluent chloroform data are given below in Table 4-2. All water
chemistry parameters measured during carbon filter conditioning were within the limits specified
in Section 3.2.3.2.  The water chemistry data are presented in Table A-2 of Appendix A.

There appeared to be a quality problem with the post-membrane carbon filters submitted for the
tests.  The ERO-R450E is certified under NSF/ANSI Standard 58 for the VOC reduction claim,
which uses  chloroform as a surrogate challenge chemical,  and is solely based on the performance
of the post-membrane carbon filter. To obtain the VOC reduction claim, the filter must reduce a
300 + 30 |o,g/L challenge down to less than 15 |o,g/L at each sample point up to 120% of the 750
gallon design capacity.  Here, six of the fifteen carbon filters had effluents exceeding 15 |j,g/L at
or prior to 50% of capacity.  The influent and effluent chloroform data was not available to the
lab technicians when they were picking which carbon filters to test for the chemical challenges,
                                          20

-------
so four of the six filters with poor chloroform reduction performance were used. However, these
four filters were able to reduce the chemical challenges by 90% or more. See Section 4.5 for the
post-membrane carbon filter challenge data.
Table 4-2. Post-Membrane Carbon Filter Conditioning Chloroform Data
Chloroform (ng/L)
25% of 50% of
Sample Start-Up Capacity Capacity
Group 1 Influent
Unit 1 Effluent
Unit 2 Effluent
Unit 3 Effluent
Unit 4 Effluent
Unit 5 Effluent
Unit 6 Effluent
Unit 7 Effluent
Unit 8 Effluent
Group 2 Influent
Unit 9 Effluent
Unit 10 Effluent
Unit 11 Effluent
Unit 12 Effluent
Unit 13 Effluent
Unit 14 Effluent
Unit 15 Effluent
340
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
13
ND (0.5)
ND (0.5)
310
2.6
12
ND (0.5)
9.0
ND (0.5)
9.0
34
310
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
22
ND (0.5)
ND (0.5)
270
9.1
23
30
21
ND (0.5)
21
68
310
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
ND (0.5)
24
ND (0.5)
ND (0.5)
360
36
29
ND (0.5)
30
ND (0.5)
36
73
4.3    TDS Reduction System Performance Check

After the RO membranes were conditioned, all underwent the TDS reduction test described in
Section 3.2.5.1.  The maximum effluent TDS level measured was 100 mg/L, corresponding to a
minimum 87% reduction of TDS. The average TDS reduction was 91%. EcoWater Systems'
reported TDS reduction for the ERO-R450E is a minimum of 87%, and an average of 92.6%, so
test systems were representative of expected membrane performance. The TDS reduction data
for each RO membrane system can be found in Table A-3 of Appendix A.


4.4    RO Membrane Chemical Challenges
The RO membrane challenges were conducted according to the procedure in Section 3.2.5.2.
The tank-fill times were approximately 70 minutes, so the systems were in operation for
approximately seven hours per challenge.


4.4.1   Inorganic Chemicals Challenges

The inorganic chemicals challenge data are shown in Table 4-3. Each challenge chemical data
point is the arithmetic mean of the triplicate sample analyses, except for the post-rest first liter
draws, which were only single samples.  All individual sample values constituting the triplicate
                                         21

-------
analyses are presented in Table A-4 of Appendix A. The challenge water chemistry data are
presented in Table A-6 of Appendix A.

Unit l(unit 11) removed 99% of both cadmium and strontium, while unit 2 (unit 12) removed
95% of both metals. Cesium was removed by 80% and 84%.  The RO membrane did not remove
a significant portion of the mercury challenge, but this not a surprising result.  There are no POU
RO systems certified by NSF for mercury reduction because mercury is not well removed by RO
membranes using the test water specified in NSF/ANSI Standard 58.
Table 4-3. RO Membrane Inorganic Chemicals Reduction Data
Cd, Cs, Sr Mercury
Cadmium Cesium Mercury Strontium Challenge Challenge
Sample (ng/L) (ng/L) (nfi/L) (nfi/L) IDS (mg/L) TDS (mg/L)
Start-up Influent
Start-up Effluent, Unit 1
Start-up Effluent, Unit 2
3rd Tank Influent
3rd Tank Effluent, Unit 1
3rd Tank Effluent, Unit 2
_4 ____ j-g^-
5th Tank Effluent, Unit 1
5th Tank Effluent, Unit 2
Post-Rest 1st Liter Draw, Unit 1
Post-Rest 1st Liter Draw, Unit 2
Post-Rest 2nd Sample, Unit 1
Post-Rest 2nd Sample, Unit 2
Mean Influent
Mean Effluent, Unit 1
Mean Effluent, Unit 2
Percent Reduction, Unit 1
Percent Reduction, Unit 2
Overall Percent Reduction
Units Tested (Unit #'s)
950
9.9
48
960
23
43
960
10
55
10
61
11
56
960
13
53
99
95
97
11,12
920
110
140
930
160
190
920
150
210
170
200
160
210
930
150
190
84
80
82
11,12
1000
980(1)
860
1100
1100
970
1200
1100
1100
1000
930
990
990
1100
1000
970
9
12
9
11, 12
950
9
50
960
27
44
960
10
57
10
55
10
57
960
13
53
99
95
97
11, 12
730
60
85
750
91
130
740
92
120
98
120


740
81
110
89
85
—
—
750
64
70
750
84
94
750
93
100
94
100


750
80
88
89
88
—
—
    (1) Number only the average of two of the triplicate analysis numbers, analytical error with the third.
The reject water sample data are given in Table 4-4. The values presented are the arithmetic
means of the duplicate sample analyses, except where indicated. The individual sample results
are presented in Table A-7 of Appendix A. The reject water levels are as expected, given that
the ERO-R450E has an efficiency rating of 9.7% (see Section 2.5 for further discussion).  This
efficiency means the reject water should have approximately  10% more of the challenge
chemical than the influent water, assuming almost 100% rejection by the membrane.
                                          22

-------
                 Table 4-4.  Inorganic Chemicals Challenge Reject Water Data
               Sample	Cadmium (M-g/L)  Cesium (M-g/L)   Mercury (M-g/L)  Strontium (M-g/L)
Start-up
1/2 through 1st Tank
3/4 through 1st tank
1/2 through 5th Tank
Unit Sampled
1200
1200
1100
1100
11
1100
1100
1000
1000
11
880
1200
1000
1200
11
1200
1200
1100
1100
11
  4.4.2   Organic Chemical Challenges
  The organic chemical challenge data are shown below in Table 4-5. Each data point is the
  arithmetic mean of the triplicate sample analyses, except where indicated, and for the post-rest
  first draw samples, which were only single samples. All individual sample values constituting
  the triplicate analyses are presented in Table A-5 in Appendix A. The water chemistry data for
  these challenges are presented in Table A-6 in Appendix A.
                 Table 4-5. RO Membrane Organic Chemical Challenge Data
        Sample
Aldicarb Benzene Carbofuran Chloroform Dichlorvos
 (Mg/L)  (Mg/L)   (ng/L)
                                                        Dicrotophos Fenamiphos Mevinphos Oxamyl Strychnine
Start-up Influent
Start-up Effluent, Unit 1
Start-up Effluent, Unit 2
3rd Tank Influent
3rd Tank Effluent, Unit 1
3rd Tank Effluent, Unit 2
5th Tank Influent
5th Tank Effluent, Unit 1
5th Tank Effluent, Unit 2
Post-Rest 1st Draw, Unit 1
Post-Rest 1st Draw, Unit 2
Post-Rest 2nd Sample, Unit 1
Post-Rest 2nd Sample, Unit 2
Mean Influent
Mean Effluent, Unit 1
Mean Effluent, Unit 2
Percent Reduction, Unit 1
Percent Reduction, Unit 2
Overall Percent Reduction
1100
11
21
980
25
14
1000
16
27
16
27
16(1)
26
1000
17
24
98
98
98
980
ND(0.5)
ND(0.5)
1100
7.7
3.1
930
15
7.0
	 9."7 	
7.1
13
7.0
980
9
5
>99
>99
>99
1100
17
15
	 1106 	
20
18
	 iioo 	
20
18
	 21 	
19
20
	 19 	
1100
20
18
98
98
98
1100
2.5
2.4
1100
45
59
1100
65
87
74
100
80
100
1100
53
70
95
94
94
1400
34
34
1300
65
72
1300
81
86
#
87
74
87
1300
66
73
95
94
95
1100
30
50
	 iTbo 	
40
70
	 TOGO 	
50
80
	 50 	
80
50
80
1100
40
70
96
94
95
910
ND(4)
ND(4)
950
ND(4)
ND(4)
930
ND(4)
ND(4)
5
5
5
4
930
4
4
>99
>99
>99
1200
31
41
1200
42
53
1200
45
53
46
54
43
56
1200
41
51
97
96
96
950
10
6
1000
11
8
970
11
9
11
9
11
9
980
11
8
99
>99
99
1100
ND(5)
7
1100
8
11
1100
13
8
8
13
10
14
1100
9
11
>99
99
>99
Units Tested (Unit #'s)      11,12  21,22   13,14     9,10     1,2      3,4       7,8      15,16    5,6    19,20
Note: The detection limit values were used for calculating the mean effluents and percent reductions.
(1) Number only the average of two of the triplicate analyses, analytical error with the third.
# Data point not reported due to analytical error.	
  As discussed in Section 3.1.1, the challenge water also contained TDS to serve as a membrane
  integrity check. The TDS reduction data are presented in Table 4-6.

  The reject water data are shown in Table 4-7.  The values presented are the arithmetic means of
  the duplicate sample analyses.  The individual sample results are presented in Table A-8 of
  Appendix A.
                                               23

-------
             Table 4-6.  TDS Reduction Data for Organic Chemical Challenges
      Sample
Aldicarb Benzene Carbofuran Chloroform Dichlorvos Dicrotophos Fenamiphos
 TDS   TDS    TDS     TDS     TDS      TDS      TDS
(mg/L)  (mg/L)  (mg/L)   (mg/L)    (mg/L)    (mg/L)     (mg/L)
Mevinphos Oxamyl Strychnine
  TDS    TDS    TDS
 (mg/L)  (mg/L)  (mg/L)
Start-up Influent
Start-up Effluent, Unit 1
Start-up Effluent, Unit 2
IFT^In^
3rd Tank Effluent, Unit 1
3rd Tank Effluent, Unit 2
5ffi Tank Influent
5th Tank Effluent, Unit 1
5th Tank Effluent, Unit 2
Post-Rest 1st Draw, Unit 1
Post-Rest 1st Draw, Unit 2
Mean Influent
Mean Effluent, Unit 1
Mean Effluent, Unit 2
Percent Reduction, Unit 1
Percent Reduction, Unit 2
740
36
43
740
59
50
740
55
65
55
65
740
51
56
93
92
760
42
42
750
65
62
750
68
67
67
68
750
61
60
92
92
750
38
36
730
55
55
730
59
57
61
59
730
53
52
93
93
760
41
44
730
59
67
750
63
68
65
72
750
57
63
92
92
730
39
43
730
60
59
730
68
67
74
87
730
60
64
92
91
720
46
69
730
68
91
730
78
100
84
110
730
69
93
91
87
760
35
39
760
52
63
760
58
69
66
72
760
53
61
93
92
760
41
47
760
57
63
760
61
68
67
73
760
57
63
93
92
760
42
40
760
60
59
760
66
60
68
60
760
59
55
92
93
750
37
36
752
59
52
750
62
58
64
59
750
56
51
93
93
                Table 4-7.  Organic Chemical Challenge Reject Water Data

               Aldicarb  Benzene  Carbofuran Chloroform Dichlorvos Dicrotophos Fenamiphos Mevinphos Oxamyl  Strychnine
    Sample	(pg/L)   (|xg/L)   (pg/L)    (ng/L)    (ng/L)    (ng/L)    (pg/L)     (pg/L)   (ng/L)   (pg/L)
Start-up
1/2 through 1st
3/4 through 1st
1/2 through 5th
Unit Sampled

Tank
tank
Tank

1200
1200
1100
1100
11
890
910
980
1200
21
1500
1400
1400
1300
13
900
950
990
1200
9
1600
1500
1500
1500
1
1400
1300
1400
1200
3
1300
1100
1200
950
7
1600
1400
1500
1400
15
1100
1200
1300
1100
5
1400
1400
1400
1200
11
The RO membrane removed all chemicals by 94% or more. The effluent levels of many
chemicals increased from the start-up to the 3rd tank samples. This trend is also evident in the
TDS reduction data for all chemicals.  The effluent levels of most chemicals then leveled off and
did not increase significantly through the end of the challenges.  Benzene, chloroform,
dicrotophos, and dichlorvos did continue to increase from the 3rd tank to 5th tank samples, and
chloroform also increased in concentration from the 5th tank sample to the post-rest samples.
The effluent TDS levels associated with the dichlorvos, dicrotophos, fenamiphos, and mevinphos
challenges also increased from each sample point to the next through the entire challenge
periods. Note however, that the effluent TDS levels did not increase to above those measured
during the TDS system check tests.  Thus, the rising TDS levels likely do not indicate that the
membranes were becoming significantly compromised due to exposure to the chemicals.  More
research would be needed to evaluate whether the membranes were actually adversely affected
by chemical exposure.

The increases may be an artifact of the challenge protocol. The challenges began with empty
storage tanks, so there was no back-pressure on the membranes when  the water collected for the
start-up samples passed through the membranes.  The rest of the samples were collected when
the storage tanks were full, so the membranes had been operating with back-pressure. RO
membranes perform better without back pressure, so the 3rd tank, 5th tank, and post-rest samples
are likely more indicative of the true performance of the system as used by the consumer.
                                            24

-------
The rise in effluent chloroform levels could also be due to the substance adsorbing onto and
diffusing through the membrane. The small size of the chloroform molecule may have also
played a role in its passage, since RO membranes remove organic chemicals by size exclusion.

The adsorption theory is lent some weight by an examination of the reject water data in Table 4-
7.  The average concentration of chloroform is lower than for the other chemicals, as is that of
benzene.  The reject water concentrations for all other chemicals are above the influent challenge
levels, indicating that they did not adsorb onto the membrane or internal surfaces in  contact with
the water.


4.5    Post-Membrane Carbon Filter Challenges

Based on the RO membrane challenge results, and the criteria discussed in Section 3.1.2, the
post-membrane carbon filter was challenged with cesium, mercury, chloroform, dichlorvos,
dicrotophos, and mevinphos.  The target challenge levels were the maximum effluent levels
measured during the RO membrane challenges. Based on the data in Table 4-2, the  carbon filters
were operated at 1.15 gpm on an operation cycle where the "on" portion was five minutes and
eleven seconds, and the "off  portion was one hour and ten minutes.

The carbon challenge results are shown below in Table 4-8. Each data point is the arithmetic
mean of the triplicate sample analyses. All individual sample values constituting the triplicate
analyses are presented in Table A-9 in Appendix A.  The water chemistry data for these
challenges can be found in Table A-10 of Appendix A.
Table 4-8. Post-Membrane
Cesium Mercury
Sample (|ag/L) (|ag/L)
Target Influent Level 220
Start-up Influent 230
Start-up Effluent, Unit 1 210
Start:up Effluent, Unit 2 200
7.5 Hours influent 230
7.5 Hours Effluent, Unit 1 220
ZrlHours^Efflu^ntUnin 230
15 Hours influent 230
15 Hours Effluent, Unit 1 230
	 15 Hours .Effluent, .Unit. 2 	 230 	
Mean Influent 230
Mean Effluent, Unit 1 220
Mean Effluent, Unit 2 220
Percent Reduction, Unit 1 4.3
Percent Reduction, Unit 2 4.3
Overall Percent Reduction 4.3
Units Tested (Unit #'s) 1, 2
1000
910
43
21
710
47
26
650
46
760
45
24
94
97
95
9, 10
Carbon Filter Challenge Data
Chloroform Dichlorvos Dicrotophos
(HB/L) (ng/L) (nfi/L)
100
99
ND (0.5)
100
ND (0.5)
100
1.6
100
0.9
0.5
>99
>99
>99
7,8
95
100
ND (0.2)
8.5
	 ioo 	
0.3
7.3
	 ioo 	
0.2
7.2
100
0.2
7.9
>99
92
96
11, 12
90
80
ND(10)
ND (10)
	 90 	
ND(10)
ND (10)
	 90 	
ND(10)
	 ND(10) 	
90
ND (10)
ND (10)
89(D
89(D
89(D
3,4
Mevinphos
(H8/L)
61
24
ND (0.2)
2.7
	 49 	
ND (0.2)
4.3
	 46 	
0.3
5.1 	
40
0.2
3.9
>99
90
95
13, 14
      Note: The detection limit values were used for calculating the mean effluents and percent reductions.
      (1) Percent reductions limited by the chemical detection limit.
                                           25

-------
The post-membrane carbon filter performed well against mercury and the organic chemicals, as
expected, but not against cesium. As discussed in Section 4.2, units 12 and 14 both
demonstrated chloroform breakthrough during conditioning. For the carbon filter challenges,
both units were paired with units that did not show breakthrough, and both gave higher effluent
levels of the challenge chemicals than did the other unit of the pair.  However, units  12 and 14
still removed 92% and 90%, respectively, of the challenge chemicals.
Units 9 and 10, used for the mercury challenge, also both demonstrated chloroform breakthrough
during conditioning. These units gave average effluent mercury concentrations (45 and 24 |o,g/L)
in the same range as the maximum effluent chloroform concentrations during conditioning (36
and 29 ng/L). However, the mercury percent reductions are much higher, at 94% and 97%,
because the mercury challenge concentration was much higher.


4.6   Conclusions

Table 4-9 gives an estimate of the combined performance of both the RO  membrane and  post-
membrane carbon filter, using the  data from Tables 4-3, 4-5, and 4-8.  An examination of the
data in Table 4-9, along with the data in Tables 4-3 and 4-5, shows that the full  ERO-R450E
system with the RO membrane and post-membrane carbon filter working in concert removed all
of the challenge chemicals but cesium by 96% or more.
 Table 4-9.  Combined Performance of RO Membrane and Post-Membrane Carbon Filter
                           Cesium   Mercury  Chloroform  Dichlorvos  Dicrotophos Mevinphos
            Sample	(nfi/L)    fcg/L)     (ng/L)     (nfi/L)      (nfi/L)
Mean Influent
Mean Effluent, Unit 1
Mean Effluent, Unit 2
Percent Reduction, Unit 1
Percent Reduction, Unit 2
Overall Percent Reduction
930
150
190
84
80
82
1100
45
24
96
98
97
1100
0.9
0.5
>99
>99
>99
1300
0.2
7.9
>99
>99
>99
1100
ND (10)
ND (10)
>99
>99
>99
1200
0.2
3.9
>99
>99
>99
                                          26

-------
                                       Chapter 5
                                        QA/QC
5.1    Introduction

An important aspect of verification testing is the QA/QC procedures and requirements.  Careful
adherence to the procedures ensured that the data presented in this report was of sound quality,
defensible, and representative of the equipment performance.  The primary areas of evaluation
were representativeness, precision, accuracy, and completeness.

Because the ETV was conducted at the NSF testing lab, all laboratory activities were conducted
in accordance with the provisions of the NSF International Laboratories Quality Assurance
Manual.

5.2    Test Procedure QA/QC

NSF testing laboratory staff conducted the tests by following an NSF SOP created specifically
for the tests. NSF QA Department Staff performed an informal audit during testing to ensure the
proper procedures were followed.

All water chemistry measurements were within the specifications in Sections 3.2.3.1 and 3.2.3.2.
All chemical challenge levels for the RO membranes were within the allowable range of 1.0 +
0.5 mg/L.  There were no allowable challenge level ranges specified for the carbon filter
challenges, but the measured challenge levels for the mercury and mevinphos challenges were
significantly low. The initial mercury challenge level was 910 ng/L, fairly close to the target
challenge level of 1000 ng/L. However, the 7.5-hour influent was down to 710 |J,g/L, and the
15-hour influent was even lower, at 650 |J,g/L. This phenomenon was not observed during the
RO membrane challenge, indicating that plating of the mercury on the internal surfaces of the
test rig plumbing was not the cause of the drop in the challenge level.

The mevinphos challenge target was 61 ng/L. The average influent at start-up was only 24 ng/L,
with a 95% confidence interval of 6 |J,g/L. The results from the 7.5-hour and 15-hour influent
samples were higher - 49 |j,g/L and 46 ng/L, respectively.


5.3    Sample Handling

All samples analyzed by the NSF  Chemistry Laboratory were labeled with unique ID numbers.
These ID numbers  appear on the NSF laboratory reports for the tests. All samples were analyzed
within allowable holding times.


5.4    Analytical  Methods QA/QC

The calibrations of all analytical instruments, and the analyses of all parameters complied with
the QA/QC provisions of the NSF International Laboratories Quality Assurance Manual.
                                          27

-------
The NSF QA/QC requirements are all compliant with those given in the USEPA Method or
Standard Method for the parameter. Also, every analytical instrument has an NSF SOP
governing its use.


5.5    Documentation

All laboratory activities were documented using specially prepared laboratory bench sheets and
NSF laboratory reports.  Data from the bench sheets and laboratory reports were entered into
Microsoft Excel spreadsheets. These spreadsheets were used to calculate average influents and
effluents, and percent reductions for each challenge chemical. One hundred percent of the data
entered into the spreadsheets was checked by a reviewer to confirm all data and calculations
were correct.


5.6    Data Review
NSF QA/QC staff reviewed the raw data records for compliance with QA/QC requirements.
NSF ETV staff checked  100% of the data in the NSF laboratory reports against the lab bench
sheets..


5.7    Data Quality Indicators
The quality of data generated for this ETV is established through four indicators of data quality:
representativeness, accuracy, precision, and completeness.


5.7.1   Representativeness

Representativeness refers to the degree to which the data accurately and precisely represent the
conditions or characteristics of the parameter represented by the data, or the expected
performance of the RO system under normal use conditions.  Representativeness was ensured by
consistent execution of the test protocol for each challenge chemical, including timing of sample
collection, sampling procedures, and sample preservation.  Representativeness was also ensured
by using each analytical  method at its optimum capability to provide results that represent the
most accurate and precise measurement it is capable of achieving.


5.7.2   Accuracy

Accuracy was quantified as the percent recovery of the parameter in a sample of known quantity.
Accuracy was measured through use of LFB and/or LFM  samples of a known quantity, and
certified standards during calibration of the instrument. The following equation was used to
calculate percent recovery:

             Percent ReCOVery = 100 X [(Xknown - Xmeasured)/Xknown]

       where: Xkn0wn   = known concentration  of the measured parameter
                      = measured concentration of parameter
                                           28

-------
The accuracy of the benchtop chlorine, pH, TDS, and turbidity meters were checked daily during
the calibration procedures using certified check standards. For samples analyzed in batches
(gravimetric TDS, TOC, all challenge chemicals), certified QC standards, and LFB and/or LFM
samples were run with each batch.

The percent recoveries of all fortified samples and standards were within the allowable limits for
all analytical methods.


5.7.3   Precision

Precision refers to the degree of mutual agreement among individual measurements and provides
an estimate of random error.  One sample per batch was analyzed in duplicate for the gravimetric
TDS and TOC analyses. LFB and/or LFM samples were analyzed to measure precision for the
challenge chemical analyses.  Duplicate drinking water samples were analyzed as part of the
daily calibration process for the benchtop chlorine, pH, TDS, and turbidity meters.

Precision of the duplicate analyses was measured by use of the following equation to calculate
relative percent deviation (RPD):
                                  RPD =
:200
       where:
              Sl = sample analysis result; and
              S2 = sample duplicate analysis result.

Precision of the LFB and LFM sample analyses was measured through calculation of the RSD as
follows:
                    %RSD = S(100)/Xaverage

       where: S = standard deviation and
              Xaverage = the arithmetic mean of the recovery values.

       Standard Deviation is calculated as follows:
              Standard Deviation =
                                      n-1

       Where: X; = the individual recovery values;
              X = the arithmetic mean of then recovery values; and
              n = the number of determinations.

All RPDs were within NSF's established allowable limits for each parameter.
                                           29

-------
5.7.4   Completeness
Completeness is the proportion of valid, acceptable data generated using each method as
compared to the requirements of the test/QA plan.  The completeness objective for data
generated during verification testing is based on the number of samples collected and analyzed
for each parameter and/or method.
                        Table 5-1.  Completeness Requirements
                     Number of Samples per Parameter
                    	and/or Method	Percent Completeness
                                (MO                    80%
                                11-50                    90%
                                > 50                    95%
Completeness is defined as follows for all measurements:

                                   %C = (V/T)X100

       where:
             %C = percent completeness;
             V = number of measurements judged valid; and
             T = total number of measurements.


5.7.4.1    Number of Systems Tested

Twenty systems were tested, as called for in the test/QA plan, giving a completeness
measurement of 100% for this category.


5.7.4.2    Water Chemistry Measurements

All of the planned samples were collected and reported for every parameter but total chlorine.
The technician did not collect total chlorine samples for any of the post-membrane carbon filter
challenges except  mevinphos. However, during the timeframe of the carbon filter challenges,
free chlorine in the test water described in Section 3.2.3.2 was measured for other tests.  The
DWTS Laboratory provided three measurements: 1.8 mg/L, 2.1 mg/L, and 2.1 mg/L. These
measurements were taken on the same days as the mercury, chloroform, and cesium carbon filter
challenges, respectively. No data was provided for the days of the dichlorvos, dicrotophos, or
mevinphos challenges. While any spikes in the chlorine level much above 2.1 mg/L were
unlikely, the lack of chlorine data does not allow an evaluation of whether the chlorine in the test
water may have impacted the carbon's ability to adsorb the challenge chemicals.  A total of 15
samples were not collected out of 50 planned samples.  This gives a completeness percentage of
70% for total chlorine.
                                          30

-------
5.7.4.3    Challenge Chemicals

All planned samples were collected, but results for a few were not reported due to analytical
errors.
   •   RO membrane mercury challenge:  Triplicate sample 1 for the unit 1 start-up effluent was
       an outlier, and was not reported.  Thirty-four of thirty-five samples were reported, for a
       completeness percentage of 97%.
   •   RO membrane aldicarb challenge:  Triplicate sample 3 for the unit 1 post-rest 2nd sample
       result was not reported due to an analytical error. Thirty-four of thirty-five samples were
       reported, for a completeness percentage of 97%.
   •   RO membrane dichlorvos challenge:  The post-rest first draw sample result for unit 1  was
       not reported due to an analytical error. Thirty-four of thirty-five samples were reported,
       for a completeness percentage of 97%.
                                           31

-------
                                      Chapter 6
                                      References
APHA, AWWA and WEF (1998). Standard Methods for Examination of Water and
    Wastewater. 20th ed. Washington, D.C. APHA.

NSF International (2005). NSF/ANSI 53-2005, Drinking water treatment units - health effects.
    Ann Arbor, MI, NSF International.

NSF International (2005).  NSF/ANSI 58 - 2005, Reverse osmosis drinking water treatment
    systems.  Ann Arbor, NSF International.

Slovak, Robert (2000). A Practical Application Manual for Residential, Point of Use Reverse
    Osmosis Systems. Lisle, IL, Water Quality Association

USEPA (2004).   Water Security Research and Technical  Support Action Plan.  EPA/600/R-
    04/063.
                                          32

-------
                 Appendix A
Conditioning and Chemical Challenges Data Tables
                     33

-------
          Table A-l.  RO Membrane Conditioning Water Chemistry Data
      Sample	Day 1	Day 2	Day 3	Day 4	Day 5	Day 6
                                                               Day 7
PH
Temperature (°C)
Total Chlorine (mg/L)
TDS (mg/L)
Turbidity (NTU)
7.7
25
ND (0.05)
750
0.1
7.0
25
ND (0.05)
750
ND(O.l)
7.1
25
ND (0.05)
750
0.1
7.1
25
ND (0.05)
750
0.2
7.0
25
ND (0.05)
750
0.3
7.2
26
ND (0.05)
750
0.1
7.1
25
ND (0.05)
750
ND(O.l)
Table A-2. Post-Membrane Carbon Filter Conditioning Influent Water Chemistry
Sample Point
Group 1, Start-Up








Group 1, 25% of Capacity








Group 1, 50% of Capacity









Influent
Unit 1
Unit 2
Unit3
Unit 4
UnitS
Unite
Unit?
Unit 8
Influent
Unit 1
Unit 2
Unit3
Unit 4
UnitS
Unite
Unit?
Unit 8
Influent
Unit 1
Unit 2
UnitS
Unit 4
UnitS
Unite
Unit?
Unit 8
Chloroform Temperature Total Organic Turbidity
(Hg/L) pH (°C) Carbon (mg/L)(1) (NTU)
340 7.2 21 38 0.1
ND(0.5)
ND(O.S)
ND(0.5)
ND(O.S)
ND(0.5)
13
ND(O.S)
ND(0.5)
310 7.2 20 38 0.1
ND(O.S)
ND(0.5)
ND(O.S)
ND(0.5)
ND(O.S)
22
ND(0.5)
ND(O.S)
310 7.3 20 38 ND(O.l)
ND(0.5)
ND(O.S)
ND(0.5)
ND(O.S)
ND(0.5)
24
ND(O.S)
ND(0.5)
  Group 2, Start-Up
  Group 2, 25% of Capacity
  Group 2, 50% of Capacity
Influent
 Unit 9
Unit 10
Unit 11
Unit 12
Unit 13
Unit 14
Unit 15
Influent
 Unit 9
Unit 10
Unit 11
Unit 12
Unit 13
Unit 14
Unit 15
Influent
 Unit 9
Unit 10
Unit 11
Unit 12
Unit 13
Unit 14
Unit 15
  310
  2.6
  12
ND(0.5)
  9.0
ND(0.5)
  9.0
  34
  270
  9.1
  23
  30
  21
ND(0.5)
  21
  68
  360
  36
  29
ND(0.5)
  30
ND(0.5)
  36
  73
                                              7.3
                                                        20
                                                                     38
                                                                                   0.1
                                              7.2
                                                        20
                                                                     37
ND(O.l)
                                              7.4
                                                        21
                                                                     42
                                                                                   0.2
  (1) TOC measured after addition of chloroform, which was in a methanol solution.  High TOC readings were due to
  the methanol.
                                            34

-------
Table A-3. RO Membrane TDS Reduction System Check Data
Sample
Influent
Unitl
Unit 2
Unit3
Unit 4
UnitS
Unite
Unit?
UnitS
Unit 9
Unit 10
Unit 11
Unit 12
Unit 13
Unit 14
Unit 15
Unit 16
Unit 17
Unit 18
Unit 19
Unit 20
Unit 21
Unit 22
TDS
Total Influent Effluent
Temperature Chlorine Turbidity TDS Sample 1
pH (°C) (mg/L) (NTU) (mg/L) (mg/L)
7.2 25 ND(0.05) ND(O.l) 750
68
68
79
100
76
58
68
70
64
67
59
99
69
66
68
74
62
67
67
65
66
66
TDS
Effluent
Sample 2
(mg/L)

70
68
81
100
77
60
68
70
65
68
60
100
70
67
69
76
62
67
68
66
67
67
TDS
Effluent
Sample 3
(mg/L)

70
69
81
100
77
59
68
71
65
68
60
100
70
67
69
76
62
67
68
67
67
67
Percent
Reduction

91
91
89
87
90
92
91
91
91
91
92
87
91
91
91
90
92
91
91
91
91
91
                        35

-------
Table A-4.  RO Membrane Inorganic Chemicals Challenge Data
Sample
Start-up Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Post-Rest 1st Draw, Unit 1
Post-Rest 1st Draw, Unit 2
Post-Rest 2nd Sample, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Post-Rest 2nd Sample, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Cadmium
(Hg/L)

950
950
940
950

9.9
10
9.7
9.9

43
51
51
48

950
930
1000
960

48
9.5
11
23

57
59
12
43

960
980
950
960

10
9.6
11
10

56
55
54
55
10
61

11
12
11
11

52
62
55
56
Cesium
(re/L)

920
920
910
920

110
110
110
110

130
150
150
140

930
910
960
930

180
150
150
160

220
210
150
190

930
920
920
920

160
140
160
150

220
200
220
210
170
200

160
160
160
160

200
210
210
210
Mercury
(MS/L)

1000
1000
1100
1000

2000(1)
980
970
980

890
980
710
860

1100
1000
1100
1100

1000
960
1400
1100

1000
910
1000
970

1300
1200
1200
1200

1100
1000
1100
1100

1100
1000
1200
1100
1000
930

980
1000
1000
990

1000
970
1000
990
Strontium
(re/L)

960
950
950
950

9
9
9
9

53
48
48
50

950
930
1000
960

59
10
11
27

59
63
10
44

960
970
950
960

10
10
10
10

57
57
57
57
10
55

10
10
10
10

59
5
57
57
     (1) Sample result not included in mean calculation due to analytical error.
                               36

-------
Table A-5. RO Membrane Organic Chemical Challenge Data
 Aldicarb Benzene Carbofuran Chloroform Dichlorvos Dicrotophos Fenamiphos  Mevinphos Oxamyl Strychnine
Sample
Start-up Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
3rd Tank Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
5th Tank Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Post-Rest 1st Draw, Unit 1
Post-Rest 1st Draw, Unit 2
Post-Rest 2nd Sample, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Post-Rest 2nd Sample, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
(Hg/L)

1100
1100
1000
1100

11
11
11
11

21
21
21
(|xg/L)

920
1100
930
980

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)

ND(0.5)
ND(0.5)
ND(0.5)
21 ND (0.5)

980
1000
950
980

25
25
24
25

14
14
14
14

1000
1000
1000
1000

16
16
17
16

27
27
27
27
16
27

16
16
1600(1)
16

26
27
26
26

1100
990
1200
1100

7.3
8.4
7.4
7.7

3.0
2.7
3.5
3.1

930
860
990
930

15
13
18
15

8.3
7.0
5.6
7.0
9.7
7.1

17
10
11
13

8.2
5.5
7.3
7.0
(|xg/L)

1100
1100
1100
1100

17
17
17
17

15
15
16
15

1100
1100
1100
1100

20
20
19
20

18
18
18
18

1100
1100
1100
1100

20
20
20
20

18
18
19
18
21
19

20
21
20
20

19
19
20
19
(|xg/L)

1100
1100
1100
1100

1.7
2.0
1.9
2.5

2.5
2.6
2.2
	 2.4 	

1100
1100
1100
1100

43
47
45
45

59
58
60
59

1100
1100
1100
1100

67
68
61
65

85
89
86
	 87 	
74
100

82
81
77
80

100
100
100
100
(|xg/L)

1500
1300
1300
1400

43
39
19
34

42
35
24
34 	

1300
1300
1300
1300

66
64
65
65

71
72
72
72

1300
1300
1400
1300

83
76
85
81

93
76
88
86 	
#
87

71
80
70
74

86
81
94
87
(|xg/L)

1100
1100
1100
1100

20
30
30
30

30
60
60
50

1200
1100
1100
1100

30
40
40
38

70
70
80
70

1000
1000
1000
1000

50
40
50
50

80
70
90
80
50
80

50
50
40
50

80
70
80
80
(|xg/L)

860
920
950
910

ND(4)
ND(4)
ND(4)
ND(4)

ND(4)
ND(4)
ND(4)
ND(4)

1000
930
920
950

ND(4)
ND(4)
ND(4)
ND(4)

ND(4)
ND(4)
ND(4)
ND(4)

860
1000
930
930

ND(4)
ND(4)
ND(4)
ND(4)

ND(4)
ND(4)
ND(4)
ND(4)
5
5

5
5
5
5

4
4
ND(4)
4
(|xg/L)

1300
1200
1200
1200

29
32
33
31

40
42
40
41

1300
1200
1200
1200

43
42
41
42

54
53
52
53

1200
1200
1300
1200

50
46
40
45

53
56
51
53
46
54

47
42
39
43

55
51
61
56
(|xg/L)

960
960
940
950

10
9
10
10

6
6
6
6

1100
1000
980
1000

11
11
11
11

8
8
8
8

950
980
990
970

12
11
11
11

9
9
9
9
11
9

11
11
11
11

9
9
9
9
(|xg/L)

1100
1100
1100
1100

ND(5)
ND (5)
ND(5)
ND(5)

10
ND(5)
ND(5)
7

1100
1100
1100
1100

8
7
8
8

11
11
11
11

1100
1100
1100
1100

14
13
13
13

8
8
9
8
8
13

9
12
9
10

15
14
13
14
(1) Sample result not included in mean calculation due to analytical error.
                               37

-------
                       Table A-6.  RO Membrane Challenges Water Chemistry Data
Sample
Start-up Influent
PH
Temperature (°C)
Total Chlorine (mg/L)
Turbidity (NTU)
5th Tank Influent
PH
Temperature (°C)
Total Chlorine (mg/L)
Turbidity (NTU)
Cd, Cs, Sr
Challenge

6.3
24
ND (0.05)
0.1

6.2
25
ND (0.05)
ND(O.l)
Mercury
Challenge

6.5
25
ND (0.05)
ND(O.l)

6.4
24
ND (0.05)
0.2
Aldicarb Benzene
Challenge Challenge

7.5 7.6
25 25
ND (0.05) ND (0.05)
0.1 0.1

7.5 7.2
24 25
ND (0.05) ND (0.05)
ND(O.l) ND(O.l)
Carbofuran Chloroform
Challenge Challenge

7.6
24
ND (0.05)
ND(O.l)

7.5
25
ND (0.05)
0.1

7.1
26
ND (0.05)
ND(O.l)

7.2
25
ND (0.05)
0.2
Dichlorvos
Challenge

7.4
25
ND (0.05)
ND(O.l)

7.4
25
ND (0.05)
ND(O.l)
Dicrotophos
Challenge

7.7
25
ND (0.05)
ND(O.l)

7.2
25
ND (0.05)
ND(O.l)
Fenamiphos
Challenge

7.3
25
ND (0.05)
0.1

7.1
25
ND (0.05)
0.1
Mevinphos
Challenge

7.3
25
ND (0.05)
0.2

7.3
25
ND (0.05)
0.3
Oxamyl
Challenge

7.3
24
ND (0.05)
ND(O.l)

7.2
25
ND (0.05)
0.2
Strychnine
Challenge

7.2
24
ND (0.05)
0.4

7.1
24
ND (0.05)
ND(O.l)
              Table A-7.  RO Membrane Inorganic Chemicals Challenge Reject Water Data
                                 Sample
                              Cadmium
                               (Mg/L)
Cesium
(Mg/L)
Mercury
 (Mg/L)
Strontium
 (Mg/L)
                         Start-up
                            Duplicate Sample 1          1200       1100        970         1200
                            Duplicate Sample 2          1200       1100        780         1200
                            Mean                    1200       1100        880         1200

                         1/2 Through First Tank
                            Duplicate Sample 1          1100       1000        1400        1100
                            Duplicate Sample 2          1200       1100        1000        1200
                            Mean                    1200       1100        1200        1200

                         3/4 Through First Tank
                            Duplicate Sample 1          1100       1000        990         1100
                            Duplicate Sample 2          1100       1000        1000        1100
                            Mean                    1100       1000        1000        1100

                         1/2 Through 5th Tank
                            Duplicate Sample 1          1100       1000        1200        1100
                            Duplicate Sample 2          1100       1000        1200        1100
                            Mean                    1100       1000        1200        1100
               Table A-8. RO Membrane Organic Chemical Challenges Reject Water Data
       Sample
Aldicarb  Benzene  Carbofuran Chloroform  Dichlorvos  Dicrotophos  Fenamiphos Mevinphos
 (Mg/L)    (Mg/L)     (Mg/L)     (Mg/L)      (Mg/L)     (Mg/L)      (Mg/L)     (Mg/L)
                                      Oxamyl   Strychnine
                                       (Mg/L)    (Mg/L)
Start-up
   Duplicate Sample 1    1200      790      1400       830       1600        1300       1100      1600      1100      1400
   Duplicate Sample 2    1200      990      1500       970       1500        1400       1400      1600      1100      1400
   Mean               1200      890      1500       900       1600        1400       1300      1600      1100      1400

1/2 Through First Tank
   Duplicate Sample 1    1200      840      1400       940       1500        1300       1200      1400      1200      1400
   Duplicate Sample 2    1200      970      1400       960       1500        1200       1000      1400      1200      1400
   Mean               1200      910      1400       950       1500        1300       1100      1400      1200      1400

3/4 Through First Tank
   Duplicate Sample 1    1100      1100      1400       970       1400        1300       1100      1500      1300      1300
   Duplicate Sample 2    1100      860      1400       1000       1500        1400       1300      1500      1200      1400
   Mean               1100      980      1400       990       1500        1400       1200      1500      1300      1400

1/2 Through 5th Tank
   Duplicate Sample 1    1100      1200      1300       1000       1600        1300       1000      1300      1100      1200
   Duplicate Sample 2    1100      1200      1300       1400       1400        1100       890       1400      1100      1200
   Mean               1100      1200      1300       1200       1500        1200       950       1400      1100      1200
                                                         38

-------
     Table A-9.  Post-Membrane Carbon Filter Challenges Data
                 Cesium    Mercury   Chloroform    Dichlorvos    Dicrotophos   Mevinphos
Sample
Target Influent Level
Start-up Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
Start-up Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
7.5 Hours Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
7.5 Hours Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
7.5 Hours Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
1 5 Hours Influent
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
15 Hours Effluent, Unit 1
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
15 Hours Effluent, Unit 2
Triplicate Sample 1
Triplicate Sample 2
Triplicate Sample 3
Mean
220

230
230
230
230

210
220
210
210

200
200
200
200

220
230
230
230

220
220
210
220

240
230
230
230

230
230
220
230

230
230
230
230

220
230
230
230
1000

890
910
940
910

41
43
44
43

18
24
22
21

750
680
690
710

46
47
47
47

26
26
26
26

660
620
670
650

48
43
47
46

28
27
25
27
100

100
97
100
99

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)

100
100
110
100

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)

100
100
100
100

1.7
1.6
1.6
1.6

ND(0.5)
ND(0.5)
ND(0.5)
ND (0.5)
95

96
110
100
100

ND (0.2)
ND (0.2)
ND (0.2)
ND (0.2)

5.1
5.5
15
8.5

110
100
100
100

ND (0.2)
ND (0.2)
0.5
0.3

7.8
7.3
6.7
7.3

100
100
100
100

0.2
ND (0.2)
ND (0.2)
0.2

6.7
7.3
7.7
7.2
90

80
80
90
SO

ND (10)
ND (10)
ND (10)
ND (10)

ND(10)
ND(10)
ND(10)
ND (10)

100
100
80
90

ND (20)(1)
ND (10)
ND (10)
10

ND(10)
ND(10)
ND(10)
ND (10)

90
80
90
90

ND (10)
ND(10)
ND (10)
ND (10)

ND(10)
ND (10)
ND (10)
ND (10)
61

28
26
18
24

ND (0.2)
ND (0.2)
ND (0.2)
ND (0.2)

2.2
3.1
2.7
	 2.7 	

51
46
50
49

ND (0.2)
ND (0.2)
ND (0.2)
ND (0.2)

4.6
4.2
4.1
	 4.3 	

43
47
47
46

ND (0.2)
0.5
ND (0.2)
0.3

5.1
5.1
5.2
5.1
(1) Detection limit higher due to dilution of the sample prior to analysis.
                                 39

-------
Table A-10.  Post-Membrane Carbon Filter Challenges Water Chemistry Data
Sample
Start-up Influent
PH
Temperature (°C)
Total Chlorine (mg/L)
TOC (mg/L)
TDS (mg/L)
Turbidity (NTU)
7.5 Hour Influent
PH
Temperature (°C)
Total Chlorine (mg/L)
TOC (mg/L)
TDS (mg/L)
Turbidity (NTU)
1 5 Hour Influent
PH
Temperature (°C)
Total Chlorine (mg/L)
TOC (mg/L)
TDS (mg/L)
Turbidity (NTU)
Challenge

7.3
21
#
2.9
450
0.2

7.3
20
#
2.3
370
0.2

7.3
21
#
2.1
360
0.3
Challenge

7.5
20
#
2.5
310
0.1

7.3
22
#
2.6
320
0.1

7.3
21
#
2.8
360
0.1
Challenge

7.5
20
#
2.6
340
ND(O.l)

7.3
21
#
29(D
320
0.3

7.4
21
#
2.7
340
0.2
Challenge

7.3
20
#
2.7
390
0.1

7.3
20
#
2.2
320
0.3

7.3
20
#
2.5
330
0.1
Challenge

7.3
20
#
2.2
310
0.1

7.3
21
#
2.3
300
0.1

7.3
22
#
2.3
310
0.1
Challenge

7.3
20
1.6
2.3
320
0.1

7.2
21
1.6
2.3
310
0.1

7.3
21
2.4
2.3
320
0.1
# Technician missed sample collection
(1) TOC measured after addition of chloroform, which was in a methanol solution. High TOC reading was due to
the methanol.
                                        40

-------